background image

T6570, T8570 SERIES DIGITAL FAN-COIL THERMOSTATS 

Table 4. Energy Saving Mode Default Settings 

Energy Savings Mode – Setpoints 

Heating Setpoint 

Cooling Setpoint 

Description 

Default 

Range 

Default 

Range 

°C Scale 

18°C 

10-18°C 

25°C 

25-30°C 

°F Scale 

65°F 

50-65°F 

77°F 

77-90°F 

Additional Switches 

FAN SPEED SWITCH (SP3T LINE VOLTAGE) 

Where supplied, the fan switch allows the selection of three 

different settings: low, medium, or high. 

NOTE:  The installer should select Constant Fan mode if the 

fan motor is a type that does not start reliably at low 

speed. 

SYSTEM HEAT/COOL SWITCH (SPST LOW VOLTAGE) 

Where supplied, this switch signals the microprocessor to 

operate the relays in either heating or cooling mode: In heating 

mode, the cooling relay is disabled. In cooling mode, the 

heating relay is disabled. 

User Programming Modes 

TEMPERATURE (COMFORT) SETPOINT 

The temperature setpoint can be adjusted between 10°C and 

30°C in steps of 0.5°C by using the [UP] and [DOWN] keys. If 

°F is set within the installer setup mode (see later), the range 

will be 50°F to 90°F, adjustable in 1°F steps. 

DISPLAY 

The measured room temperature is normally displayed (unless 

rt = 0

 in the installer setup mode), and the first press of the 

[UP] or [DOWN] keys will switch to display the user setpoint. If 

no key is pressed for 5 seconds, the display will return to 

showing the room temperature. 

When the cooling relay is closed, this will be indicated by a 

(snowflake) symbol, whereas closure of the heating relay will 

be indicated by a (flame) symbol. 

If there is a wiring problem or the room temperature is less 

than 5°C (40°F) or over 38°C (100°F) the display will return a 

SF (Sensor Failure) warning. If this warning is not due to a 

wiring problem it will disappear once the remote sensor or 

thermostat comes within the 4.5 to 37.8°C (40 to 100°F) range. 

If the SF warning is due to a faulty remote sensor connection 

the thermostat will not transfer measurement to the internal 

sensor. To resolve the faulty connection the thermostat must 

be powered down, the remote sensor connection must be 

removed or fixed and then the thermostat must be re-powered. 

Installer Setup Mode 

The thermostat allows many of its operating parameters to be 

adjusted via an Installer Setup Mode. Each operating 

parameter has a two-letter identifier code, which is shown on 

the display during the Installer Setup Mode programming 

sequence. A description of these is shown in Table 5. 

PROGRAMMING PARAMETERS 

The installer setup mode is accessed by reducing the setpoint 

to 10°C (50°F), waiting 3 seconds or until the room 

temperature is displayed, and then pressing the [UP] and 

[DOWN] keys simultaneously for 3 seconds. 

If the installer setup has previously been entered and the 

Minimum Cooling Setpoint increased above 10°C (50°F), the 

installer setup mode is accessed by reducing the setpoint to 

the new value before pressing the two buttons. 

The first parameter identifier will be displayed at this point and 

the parameter value can be changed by pressing the [UP] key. 

The first press displays the default value and any subsequent 

press alters the value. The values will wrap around. 

To select the parameter value and move to the next parameter, 

press [DOWN]. After the final parameter is selected, a further 

press of the [DOWN] key will exit from the programming mode. 

PARAMETER VALUES 

Each parameter has a default value that is used when the 

thermostat is first powered up. This value can be changed from 

within the Installer Setup Mode, and once changed, it will be 

stored in the EEPROM so it is not lost in the event of power 

interruption. 

If the user wishes to restore the parameters to the default 

values, this can be done by changing the temperature scale 

tS 

from °C to °F (or °F to °C) and back again. 

PROGRAMMING EXAMPLE 

To enter the installer setup mode: 

1.

  

Press to change the temperature setpoint to 10°C

 

(50°F).

 

2.

  

Wait 3 seconds, or until the room temperature is dis-

played. 

3.

  

Press and hold together until [

tS

] is displayed. 

4.

  

Press once to show the default Temperature Scale 

value. Continue to show all possible values of this 

parameter in sequence.

 

5.

  

When the desired value is displayed, it is selected by 

pressing once. This will also move to the next parameter, 

whose identifier will now be displayed. 

6.

  

Continue to use to move from one parameter to the next, 

and to alter the parameter value. 

7.

  

When the last parameter [

rt

] has been selected, a final 

press of will return the display to its normal operating 

mode. 

95C-10897–6

  

Содержание T6570 Series

Страница 1: ...t temperature with user activated temperature display Digital display shows mode icons when cooling or heating relays operate or when energy savings mode is active Push button setpoint adjustment Switches allow manual control of system operation and fan speed Energy savings mode external energy savings input from time switch occupancy sensors or hotel cardkey overrides comfort setpoint with setbac...

Страница 2: ...ectrical box or on 4 x 4 Operating Range 5 C to 45 C 41 F to 113 F box with optional 272878 adapter plate Shipping and Storage Range 20 C to 55 C 4 F to 131 F Wiring 11 terminals screw in terminals capable of accepting Humidity Range 5 to 95 RH non condensing at 26 C up to 2 x 18 AWG 1 x 14 AWG or 1 5 mm2 wires Some 79 F terminals pre fitted with color coded flyleads Thermostat Output 1spdt or 2 s...

Страница 3: ...Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service techni cian 4 After installation is complete check out product opera tion as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power s...

Страница 4: ...ostat straight away from the wallplate 1 2 3 M15396 Fig 3 Removing the thermostat Thoroughly check wiring to the wallplate before finally mounting the thermostat on the wall OPERATION Control PROPORTIONAL INTEGRAL P I CONTROL Like a mechanical thermostat the T6570 T8570 Series have On Off control output However this output is regulated by a P I algorithm enabling the thermostat to control closer t...

Страница 5: ...On the thermostat undergoes a startup and self checking sequence First all LCD display segments are illuminated to check the display Next a number appears to indicate the software version The final check is a check of the sensor On completion of the startup sequence after approximately 2 seconds the thermostat will resume normal control in either Comfort or Economy mode On initial power on the tem...

Страница 6: ...de The thermostat allows many of its operating parameters to be adjusted via an Installer Setup Mode Each operating parameter has a two letter identifier code which is shown on the display during the Installer Setup Mode programming sequence A description of these is shown in Table 5 PROGRAMMING PARAMETERS The installer setup mode is accessed by reducing the setpoint to 10 C 50 F waiting 3 seconds...

Страница 7: ...nt Low Limit CL Sets the minimum allowable cooling setpoint 10 10 to 30 50 50 to 90 Maximum Heating Setpoint High Limit HL Sets the maximum allowable heating setpoint 30 10 to 30 90 50 to 90 Energy Savings Configuration ES Activate energy savings mode by a choice of either contact closure or contact opening 1 1 normally open 0 normally closed 1 1 normally open 0 normally closed Display of Room Tem...

Страница 8: ...hangeover switch continuous fan switch Fig 11 Wiring 4 pipe auto heat cool changeover Fig 8 Wiring 2 pipe seasonal heat cool changeover with external aquastat fan On Auto switch Fig 12 Wiring 4 pipe auto heat cool changeover with fan On Auto switch Fig 9 Wiring 2 pipe heat cool with manual heat cool changeover switch continuous fan or cycled fan 95C 10897 6 8 ...

Страница 9: ...provides 24 Vac power three interlocked fan relays and wiring center terminations for valve relay and contactor loads The W6380 schematic can be found in Fig 14 Fig 16 Wiring 2 pipe 24V heat thermostat with fan On Auto switch Fig 17 Wiring 2 pipe heat cool with manual heat cool changeover switch continuous or cycled fan Fig 14 W6380 wiring diagram Fig 15 Wiring 2 pipe 24V cool only thermostat with...

Страница 10: ... use this for control To extend the sensor cable up to a maximum of 70 feet 20m use only shielded cable For example Beldfoil 18 AWG cable is a suitable cable The sensor connections are polarity sensitive so be sure to connect the shielded wire to the sensor blue wire as shown in Fig 21 below Fig 21 Wiring optional remote sensor for the T8575D model CAUTION Equipment Damage Hazard Operation at low ...

Страница 11: ...T6570 T8570 SERIES DIGITAL FAN COIL THERMOSTATS 95C 10897 6 11 ...

Страница 12: ...Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 95C 10897 6 M A Rev 09 05 ...

Отзывы: