background image

40007507-001 

T6570, T8570 SERIES DIGITAL FAN-COIL THERMOSTATS 

Mounting 

Any T6570, T8570 series thermostat can be mounted directly 

on the wall on a 65x65mm junction box, or a 2"x4" horizontal 

junction box. An optional adapter plate is available for 

mounting on a 4"x4" or vertical junction box. (See Fig. 2) 

Mounting screws are supplied for alternatives. 

1.

  

Feed leadwires through wiring access hole of wallplate 

and adaptor plate (if used). 

2.

  

Attach supply wires using wire nuts (not provided), or 

screw terminals, as appropriate. 

3.

  

Locate wallplate in the horizontal mounting position. See 

Fig. 2 if using the vertical junction box adapter plate. 

4.

  

Push leadwires into electrical junction box and attach 

wallplate to box using machine screws provided in the 

appropriate mounting holes. 

5.

  

Attach thermostat to wallplate: 

a.

  

Locate the two center side holes on the back of the 

thermostat. 

b.

  

Align the holes with the two wallplate side tabs. 

c.

  

Press down firmly to snap thermostat into place. 

M17505 

Fig. 2. Mounting the vertical junction box adapter plate 

M17505 Optional adapter plate. 

Removing the thermostat 

CAUTION 

Equipment Damage Hazard.

Improper removal can damage the thermostat. 

Carefully follow the thermostat removal directions. 

If it is necessary to remove the thermostat from the wallplate 

(see Fig. 3): 

1.

  

Use a screwdriver to pry thermostat left side away from 

the base. 

2.

  

Use the screwdriver to pry thermostat's right side away 

from the wallplate. 

3.

  

Use both hands to pull the thermostat straight away from 

the wallplate. 

1

 

2

 

3

 

M15396 

Fig. 3. Removing the thermostat 

Thoroughly check wiring to the wallplate before finally 

mounting the thermostat on the wall. 

OPERATION 

Control 

PROPOR INTEGRAL (P+I) CONTROL 

Like a mechanical thermostat, the T6570, T8570 Series have 

On/Off control output. However, this output is regulated by a 

P+I algorithm, enabling the thermostat to control closer to 

setpoint than conventional thermostats. This results in 

performance where the space temperature is maintained within 

0.75°C (1.5°F) of the setpoint regardless of fan speed. 

P+I action minimizes the difference between the temperature 

setpoint and the effective control point by adjusting the output 

on-time until the control point matches the setpoint. The on-

time is based on a fixed cycle rate of 4 cycles/hour for cooling 

(8 cycles/hour for heating), and the proportional band is 1.6°C 

(2.9°F). 

NOTE:

  

Integral action corrects the temperature control errors 

of proportional-only control, but it is slower to react to 

large temperature or setpoint changes. 

These thermostats also feature optional built-in time 

delays for equipment protection which can inhibit 

rapid response to large setpoint changes if active. 

SINGLE-STAGE COOLING OR HEATING CONTROL (SEE FIG. 4) 

In cooling mode the user setpoint will be positioned at the 

bottom of the Proportional Band, so the setpoint will effectively 

be the temperature where the cooling switches off. In heating 

mode the user setpoint will be positioned at the top of the 

Proportional Band, and this will be the temperature where the 

heating switches off. 

NOTE:

  

This also applies to models with manual heat/cool 

changeover. 

95C-10897–6

  

Содержание T6570 Series

Страница 1: ...t temperature with user activated temperature display Digital display shows mode icons when cooling or heating relays operate or when energy savings mode is active Push button setpoint adjustment Switches allow manual control of system operation and fan speed Energy savings mode external energy savings input from time switch occupancy sensors or hotel cardkey overrides comfort setpoint with setbac...

Страница 2: ...ectrical box or on 4 x 4 Operating Range 5 C to 45 C 41 F to 113 F box with optional 272878 adapter plate Shipping and Storage Range 20 C to 55 C 4 F to 131 F Wiring 11 terminals screw in terminals capable of accepting Humidity Range 5 to 95 RH non condensing at 26 C up to 2 x 18 AWG 1 x 14 AWG or 1 5 mm2 wires Some 79 F terminals pre fitted with color coded flyleads Thermostat Output 1spdt or 2 s...

Страница 3: ...Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service techni cian 4 After installation is complete check out product opera tion as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power s...

Страница 4: ...ostat straight away from the wallplate 1 2 3 M15396 Fig 3 Removing the thermostat Thoroughly check wiring to the wallplate before finally mounting the thermostat on the wall OPERATION Control PROPORTIONAL INTEGRAL P I CONTROL Like a mechanical thermostat the T6570 T8570 Series have On Off control output However this output is regulated by a P I algorithm enabling the thermostat to control closer t...

Страница 5: ...On the thermostat undergoes a startup and self checking sequence First all LCD display segments are illuminated to check the display Next a number appears to indicate the software version The final check is a check of the sensor On completion of the startup sequence after approximately 2 seconds the thermostat will resume normal control in either Comfort or Economy mode On initial power on the tem...

Страница 6: ...de The thermostat allows many of its operating parameters to be adjusted via an Installer Setup Mode Each operating parameter has a two letter identifier code which is shown on the display during the Installer Setup Mode programming sequence A description of these is shown in Table 5 PROGRAMMING PARAMETERS The installer setup mode is accessed by reducing the setpoint to 10 C 50 F waiting 3 seconds...

Страница 7: ...nt Low Limit CL Sets the minimum allowable cooling setpoint 10 10 to 30 50 50 to 90 Maximum Heating Setpoint High Limit HL Sets the maximum allowable heating setpoint 30 10 to 30 90 50 to 90 Energy Savings Configuration ES Activate energy savings mode by a choice of either contact closure or contact opening 1 1 normally open 0 normally closed 1 1 normally open 0 normally closed Display of Room Tem...

Страница 8: ...hangeover switch continuous fan switch Fig 11 Wiring 4 pipe auto heat cool changeover Fig 8 Wiring 2 pipe seasonal heat cool changeover with external aquastat fan On Auto switch Fig 12 Wiring 4 pipe auto heat cool changeover with fan On Auto switch Fig 9 Wiring 2 pipe heat cool with manual heat cool changeover switch continuous fan or cycled fan 95C 10897 6 8 ...

Страница 9: ...provides 24 Vac power three interlocked fan relays and wiring center terminations for valve relay and contactor loads The W6380 schematic can be found in Fig 14 Fig 16 Wiring 2 pipe 24V heat thermostat with fan On Auto switch Fig 17 Wiring 2 pipe heat cool with manual heat cool changeover switch continuous or cycled fan Fig 14 W6380 wiring diagram Fig 15 Wiring 2 pipe 24V cool only thermostat with...

Страница 10: ... use this for control To extend the sensor cable up to a maximum of 70 feet 20m use only shielded cable For example Beldfoil 18 AWG cable is a suitable cable The sensor connections are polarity sensitive so be sure to connect the shielded wire to the sensor blue wire as shown in Fig 21 below Fig 21 Wiring optional remote sensor for the T8575D model CAUTION Equipment Damage Hazard Operation at low ...

Страница 11: ...T6570 T8570 SERIES DIGITAL FAN COIL THERMOSTATS 95C 10897 6 11 ...

Страница 12: ...Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 95C 10897 6 M A Rev 09 05 ...

Отзывы: