S8610U UNIVERSAL INTERMITTENT PILOT GAS IGNITION CONTROL

69-1955

2

For module replacement, the following table indicates the proper Dip Switch settings for Prepurge timing (SW1) and 
Trial For Ignition timing (SW2). See “Settings and Adjustments” on page 15 for Dip Switch information.

Table 2. S8610U Replaces These 

Modules

Vendor / 

Model

SW1

SW2

Honeywell

S86A1001

S86A1019

S86A1027

S86A1035

S86B1009

S86B1017

S86B1025

S86C1007

S86C1015

OFF

OFF

S86C1023

OFF

ON

S86C1031

S86C1049

S86C1056

S86D1005

OFF

OFF

S86D1013

OFF

ON

S86D1021

S86E1002

S86E1010

S86E1028

S86E1036

S86E1044

S86E1051

S86E1069

S86E1077

S86E1101

S86E1119

S86E1127

S86F1000

S86F1018

S86F1026

S86F1042

S86F1059

S86F1067

S86F1075

S86F1083

S86F1091

S86G1008

S86G1016

OFF

OFF

S86G1024

OFF

ON

S86G1032

S86G1057

S86G1073

S86H1006

OFF

OFF

S86H1014

OFF

ON

S86H1022

S86H1048

S86H1055

OFF

OFF

S86H1063

OFF

ON

S86H1089

S86H1097

S86H1105

OFF

OFF

S86H1113

OFF

ON

S86H1121

OFF

OFF

S86H1139

OFF

ON

S86H1147

S90A1005

S90B1003

S90B1011

OFF

OFF

S860C1000

S860D1009

ON

OFF

S860D1017

ON

ON

S8600A1001

S8600B1009

OFF

OFF

S8600B1025

S8600B3005

OFF

ON

S8600B3013

S8600C1015

S8600C3003

S8600F1000

S8600F1034

S8600F1042

S8600H1006

OFF

OFF

S8600H1014

OFF

ON

S8600H1022

S8600H1048

S8600H1055

OFF

OFF

S8600H1063

OFF

ON

S8600H1071

S8600H1089

S8600H1097

S8600H1105

S8600H3002

OFF

OFF

S8600H3010

OFF

ON

S8600M1005

S8600M1013

S8600M1021

S8600M2003

S8600M3001

S8600M4009

S8610A1009

S8610B1007

S8610B1015

OFF

OFF

S8610B1023

S8610B3003

OFF

ON

S8610C1005

S8610C1013

S8610C3001

S8610F1008

S8610F1016

S8610F1024

S8610F1032

OFF

OFF

S8610H1004

OFF

ON

S8610H1012

OFF

OFF

S8610H1020

OFF

ON

S8610H1038

S8610H1046

S8610H1053

OFF

OFF

S8610H1061

OFF

ON

S8610H1079

S8610H1095

S8610H3000

OFF

OFF

S8610H3018

OFF

ON

S8610H3026

S8610M1003

OFF

OFF

S8610M1011

OFF

ON

S8610M1029

S8610M3009

OFF

OFF

S8610M3017

OFF

ON

S8610U1003

S8610U1011

OFF

OFF

S8620C1003

S8620C1011

OFF

ON

S8620H1002

OFF

OFF

S8620H1010

OFF

ON

S8620H1028

OFF

OFF

S8660D1002

ON

OFF

S8660D1010

ON

ON

S8660J1008

S8660J1016

S8660J1024

S8660K1006

S8660K1014

S8660K1022

S8670D1000

S8670D1018

ON

OFF

S8670D1026

S8670D3006

ON

ON

S8670D3014

S8670E1007

S8670E3003

ON

OFF

S8670J3002

ON

ON

S8670J3010

S8670K3000

ON

OFF

S8680J1004

ON

ON

Table 2. S8610U Replaces These 

Modules (Continued)

Vendor / 

Model

SW1

SW2

Johnson Controls

CSA35A-617R

CSA35A-618R

CSA42A-600R

CSA42A-601R

CSA42A-602R

CSA42A-603R

CSA42A-604R

CSA43A-600R

CSA44A-600R

CSA45A-601R

CSA45A-602R

CSA46A-600R

CSA48A-600R

CSA49A-600R

CSA49A-605R

CSA51A-601R

CSA52A-600R

OFF

OFF

G60AAA-1

G60AAG-1

G60AAG-2

G60AAG-3

G60AAG-4

G60AAG-5

G60AAG-6

G60AAG-7

G60CAA-1

G60CAA-3

G60CAG-1

G60CAG-2

G60CAG-3

G60CAG-4

G60CAG-5

G60CAG-6

G60CAG-7

G60CAG-8

G60CAG-9

G60CBA-1

G60CBA-2

G60CBA-3

G60CBG-1

G60CBG-2

G60CBG-3

G60CBG-4

G60CBG-5

G60CBG-6

G60CBG-7

G60CBG-8

G60CBG-9

G60CBG-10

G60CBG-11

G60CBG-12

G60CBG-13

G60CBG-14

G60CBG-15

G60CBG-16

G60CBG-17

G60CCA-1

G60CCG-1

G60CPG-1

G60DBG-1

G60DCG-1

G60DCG-2

G60DCG-3

G60DCG-4

G60PAG-1

G60PAG-2

G60PAG-3

G60PAG-4

G60PAG-5

G60PAG-6

G60PAJ-1

G60PAK-1

G60PAK-2

G60PFH-1

G60PFH-2

G60PFL-1

G60PFQ-1

G60PVL-1

G60QAG-1

G60QAG-2

G60QAG-3

OFF

OFF

Table 2. S8610U Replaces These 

Modules (Continued)

Vendor / 

Model

SW1

SW2

Содержание SUPER TRADELINE S8610U

Страница 1: ... adapt the existing spark cable Rajah stud nail or other to the spark terminal on the control module It also help assure proper marking of the wires attached to the existing control and a label with LED code information that can be affixed in the appliance IMPORTANT The S8610U control module is not designed to replace controls with Flame sensing other than by flame rectification White Rodgers Cycl...

Страница 2: ...610C1013 S8610C3001 S8610F1008 S8610F1016 S8610F1024 S8610F1032 OFF OFF S8610H1004 OFF ON S8610H1012 OFF OFF S8610H1020 OFF ON S8610H1038 S8610H1046 S8610H1053 OFF OFF S8610H1061 OFF ON S8610H1079 S8610H1095 S8610H3000 OFF OFF S8610H3018 OFF ON S8610H3026 S8610M1003 OFF OFF S8610M1011 OFF ON S8610M1029 S8610M3009 OFF OFF S8610M3017 OFF ON S8610U1003 S8610U1011 OFF OFF S8620C1003 S8620C1011 OFF ON ...

Страница 3: ...BKG 1 G65BKG 2 G65BKG 3 G65BKM 1 G65BKM 2 G65BKM 3 G65BLG 1 G65BLG 2 G65DBG G65DBM 1 G65DBM 2 G65DBM 3 G65DCM 1 G65DFG G65DFM 1 G65DKG G65DKM G65DKM 1 G65DLM 1 G65FBG G65FFG G65FKG OFF OFF Table 2 S8610U Replaces These Modules Continued Vendor Model SW1 SW2 G66AG 1 G66AG 2 G66BG 1 G66MG 1 G66MG 2 G66NG 1 OFF OFF G67AG 3 G67AG 4 G67AG 7 G67AG 8 G67AG 9 G67AG 10 G67AG 11 G67BG 2 G67BG 3 G67BG 4 G67B...

Страница 4: ...for the ignition control module Corrosive Chemicals Corrosive chemicals can attack the ignition control module and gas control eventually causing a failure If chemicals are used for routine cleaning make sure they do not reach the controls Where chemicals are suspended in air as in some industrial or agricultural applications use a NEMA 4 enclosure for the ignition control module Dust or Grease Ac...

Страница 5: ...rm Pre Installation Safety Check The pre installation checks described below must be done before the replacement ignition control module is installed If a condition that could result in unsafe operation is detected the appliance should be shut off and the owner advised of the unsafe condition Correct any potentially unsafe condition before proceeding with the installation The following safety chec...

Страница 6: ...ield wiring terminals Operating ambient temperatures between 40 F 40 C and 165 F 74 C Relative humidity below 95 non condensing Protection from water steam or corrosive chemicals that are used to clean the appliance Protection from dripping water such as from an overfilled humidifier or from condensation Protection from dust or grease accumulation IMPORTANT Do not mount with terminals facing up Fi...

Страница 7: ...sor stud on the pilot burner igniter sensor Connect Ignition Control Module CAUTION Equipment Damage Hazard Check the wiring diagram provided on the appliance and compare with Table 5 through Table 8 beginning on page 8 Carefully follow any special instructions affecting the general wiring procedures outlined in this section 1 Connect the wires to the module as shown in the wiring tables Table 5 t...

Страница 8: ...t a vent damper was not installed or if it did not have a vent damper connector then connect the 25V 2 or 24V wire from the old module to the TH W terminal on the S8610U Do not use the 24V terminal on the S8610U If the old module had a vent damper connect it to the P1 connector on the module and wire the terminals as indicated in the table 25V 2 or 24V used only in systems where plug in cable conn...

Страница 9: ...79 Y79A module b b Discard wires between Y79A and module as follows Red to 3 Black to 2 White to GR Discard wire between transformer and 6 Y79A module c c Discard wires between Y79B and module as follows White to 3 Black to 1 Brown to GR Discard wire between transformer and 6 Main Valve Operator MV 3 3 Y79B MV MV 3 Main Valve and Pilot Common MV PV GR GR GR GROUND 5 Pilot Valve Operator PV 1 1 Y79...

Страница 10: ...om E1 which is tagged Thermostat Flame Sensor SENSE d d Important If the USI 715U with combination igniter sensor is not used remove black jumper quick connect from Remote Sense terminal of S8610U Cut jumper wire at circuit board and discard e e Labeled OPT SENSOR on USI 715U No external connection if combination igniter sensor is used d d Igniter Sensor SPARK IGN IGN IGN Table 8 Conversion from C...

Страница 11: ...ves as the common grounding area If there is not good metal to metal contact between the pilot burner and ground run a lead from the pilot burner to ground NOTE Earth ground is not required Wiring Connections Use Fig 2 and Table 9 to make the remaining wiring connections Fig 3 Fig 5 beginning on page 12 illustrate typical wiring connections in heating systems with atmospheric burners and with powe...

Страница 12: ... LEG TO TRANSFORMER ONCE POWERED UP WITH VENT DAMPER CONNECTED MODULE WILL OPERATE ONLY WITH DAMPER CONNECTED FOR SINGLE ROD APPLICATIONS CONNECT JUMPER WIRE TO THE REMOTE SENSE CONNECTOR FOR TWO ROD APPLICATIONS REMOVE JUMPER WIRE BY CUTTING IT AS CLOSE AS POSSIBLE TO THE BASE OF THE MODULE DISCARD CLIPPED WIRE AND FIRMLY ATTACH THE SENSOR WIRE FROM THE IGNITER SENSOR ASSEMBLY TO THE REMOTE SENSE...

Страница 13: ...R WIRE TO THE REMOTE SENSE CONNECTOR FOR TWO ROD APPLICATIONS REMOVE JUMPER WIRE BY CUTTING IT AS CLOSE AS POSSIBLE TO THE BASE OF THE MODULE DISCARD CLIPPED WIRE AND FIRMLY ATTACH THE SENSOR WIRE FROM THE IGNITER SENSOR ASSEMBLY TO THE REMOTE SENSE CONNECTOR M23617 1 2 3 4 5 6 THERMOSTAT L1 HOT L2 LIMIT CONTROLLER 2ND OPERATOR 1ST OPERATOR PILOT COM MAIN VALVE DUAL VALVE COMBINATION GAS CONTROL P...

Страница 14: ...ROD APPLICATIONS REMOVE JUMPER WIRE BY CUTTING IT AS CLOSE AS POSSIBLE TO THE BASE OF THE MODULE DISCARD CLIPPED WIRE AND FIRMLY ATTACH THE SENSOR WIRE FROM THE IGNITER SENSOR ASSEMBLY TO THE REMOTE SENSE CONNECTOR 1 2 3 4 5 6 REMOTE SENSE JUMPER WIRE CLIPPED CLOSE TO BOARD TWO ROD SENSOR WIRE FROM IGNITER SENSOR 6 THERMOSTAT L1 HOT L2 1 LIMIT CONTROLLER 2 4 3 M23586 AIR PROVING SWITCH COMBUSTION ...

Страница 15: ...out the gas control system At initial installation of the appliance As part of regular maintenance procedures Maintenance intervals are determined by the application For additional information See Planning the Installation on page 4 As the first step in troubleshooting Any time work is done on the system WARNING Fire or Explosion Hazard Failure to heed these warnings may cause fire or explosion wi...

Страница 16: ...r main burner 6 Set thermostat below room temperature and wait one minute before continuing Step 6 Check Normal Operation 1 Turn on the gas supply 2 Set thermostat or controller above room tempera ture to Call for Heat 3 Make sure pilot lights smoothly when gas reaches the pilot burner 4 Make sure main burner lights smoothly without flashback 5 Make sure burner operates smoothly without float ing ...

Страница 17: ...rating Sequence OPERATING SEQUENCE CALL FOR HEAT RECEIVED FROM THERMOSTAT POWER TO MODULE AND SELF CHECK IDLE NOT POWERED RUN YES TRIAL FOR IGNITION TIMER STARTED SPARK ON OPEN PILOT GAS VALVE FLAME PROVED FLAME STABILIZATION 2 SECONDS YES NO RETRY OPEN MAIN GAS VALVE CLOSE MAIN GAS VALVE AND PILOT GAS VALVE FLAME LOST NO CLOSE PILOT GAS VALVE SPARK OFF CALL FOR HEAT ENDS YES NO RETRY DELAY 5 MINU...

Страница 18: ...trol module and to the igniter or igniter sensor are clean and tight 5 Ignition cable provides good electrical continuity STEP 2 Check Ignition System Grounding Nuisance shutdowns are often caused by a poor or erratic ground A common ground is required for the ignition control module and the pilot burner bracket 1 Check for good metal to metal contact between the pilot burner bracket and the main ...

Страница 19: ...ems and their causes i If necessary adjust pilot flame by turning the pilot adjustment screw on the gas control clock wise to decrease or counterclockwise to increase pilot flame Following adjustment always replace pilot adjustment cover screw and tighten firmly to assure proper gas control operation j Set thermostat below room temperature to end Call for Heat 4 Recheck ignition sequence as follow...

Страница 20: ...al for ignition Flash code will remain through the ignition trial until flame is proved If system fails to light on next trial for ignition check gas supply pilot burner flame sense wiring contamination of flame rod burner ground connection 4 Flame sensed out of sequence If situation self corrects within 10 seconds control module returns to normal sequence If flame out of sequence remains longer t...

Страница 21: ... FOR HEAT IS ALWAYS CONNECTED TO THE TH W TERMINAL ON THE MODULE START BEFORE TROUBLESHOOTING FAMILIARIZE YOURSELF WITH THE STARTUP AND CHECKOUT PROCEDURES TURN THERMOSTAT CONTROLLER TO CALL FOR HEAT CHECK LINE VOLTAGE POWER LOW VOLTAGE TRANSFORMER LIMIT CONTROLLER THERMOSTAT CONTROLLER AND WIRING ALSO CHECK AIR PROVING SWITCH ON COMBUSTION AIR BLOWER SYSTEM IF USED AND THAT THE END SWITCH IF USED...

Страница 22: ...S8610U UNIVERSAL INTERMITTENT PILOT GAS IGNITION CONTROL 69 1955 22 ...

Страница 23: ...S8610U UNIVERSAL INTERMITTENT PILOT GAS IGNITION CONTROL 23 69 1955 ...

Страница 24: ...d Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2006 Honeywell International Inc 69 1955 M S 11 06 ...

Отзывы: