Honeywell SUPER TRADELINE S8610U Скачать руководство пользователя страница 18

S8610U UNIVERSAL INTERMITTENT PILOT GAS IGNITION CONTROL

69-1955

18

TROUBLESHOOTING

WARNING

Fire, Explosion, or Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.

Do not attempt to modify the physical or electrical 
characteristics of this device in any way. Replace 
it if troubleshooting indicates a malfunction.

IMPORTANT

1. The following service procedures are provided 

as a general guide. Follow appliance manufac-
turer’s service instructions if available.

2. Meter readings between the gas control and igni-

tion control module must be taken within the trial 
for ignition period. Once the ignition control mod-
ule shuts off, it must be reset by setting the ther-
mostat down for at least 30 seconds before 
continuing.

3. If any component does not function properly, 

make sure it is correctly installed and wired 
before replacing it.

4. The ignition control module cannot be repaired. 

If it malfunctions, it must be replaced.

5. Only trained, experienced service technicians 

should service intermittent pilot systems.

6. After troubleshooting, check out the system 

again to be sure it is operating normally.

The general troubleshooting sequence is as follows:

1.

Refer to “LED Status and Troubleshooting” on 
page 19 
for LED status codes.

2.

Perform the “Checkout” on page 15 as the first step 
in troubleshooting. 

3.

Check the troubleshooting guide (Fig. 11 on 
page 21) t
o pinpoint the cause of the problem. 

4.

If troubleshooting indicates an ignition problem, see 
Ignition System Checks below to isolate and correct 
the problem.

5.

Following troubleshooting, perform the “Checkout” 
on page 15 ag
ain to be sure system is operating 
normally.

Ignition System Checks

Step 1: Check Ignition Cable.

Make sure:

1.

Ignition cable is not damaged, cracked, burned, or 
dirty. Replace if necessary.

2.

Ignition cable does not run in contact with any metal 
surfaces.

3.

Ignition cable is no more than 36 in. (0.9 m) long.

4.

Connections to the ignition control module and to 
the igniter or igniter-sensor are clean and tight.

5.

Ignition cable provides good electrical continuity.

STEP 2: Check Ignition System Grounding.

Nuisance shutdowns are often caused by a poor or erratic 
ground. A common ground, is required for the ignition 
control module and the pilot burner bracket.

1.

Check for good metal to metal contact between the 
pilot burner bracket and the main burner.

2.

Check the ground circuit from the GND (BURNER) 
terminal on the ignition control module to the pilot 
burner. Make sure connections are clean and tight. 
If the wire is damaged or deteriorated, replace it 
with 14- to 18-gauge, moisture-resistant, thermo-
plastic insulated wire with 221°F (105°C) minimum 
rating.
a. Check the ceramic flame rod insulator for 

cracks or evidence of exposure to extreme heat, 
which can permit leakage to ground. Replace 
pilot burner/igniter-sensor and provide shield, if 
necessary.

b. If the flame rod or bracket is bent out of position, 

restore to correct position.

STEP 3: Check Spark Ignition Circuit. 

You will need a short jumper wire made from ignition 
cable or other heavily insulated wire.

1.

Close the manual gas valve.

2.

Disconnect the ignition cable at the SPARK terminal 
on the ignition control.

WARNING

Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.

When performing the following steps, do not touch 
the stripped end of jumper or SPARK terminal. 
The ignition circuit generates over 10,000 volts 
and electrical shock can result.

3.

Energize the ignition control module and immedi-
ately touch one end of the jumper firmly to the GND 
terminal on the ignition control module. Move the 
free end of the jumper slowly toward the SPARK 
terminal until a spark is established.

4.

Pull the jumper slowly away from the terminal and 
note the length of the gap when sparking stops. 
Check Table 12 below.

Table 12. Arc Troubleshooting.

Arc Length

Action

No arc or arc less 
than 1/8 in. (3 mm)

Check external fuse, if provided.
Verify power at the ignition 
control module’s control input 
terminal. Replace control if fuse 
and power are okay.

Arc 1/8 in. (3 mm) 
or longer

Voltage output is okay.

Содержание SUPER TRADELINE S8610U

Страница 1: ... adapt the existing spark cable Rajah stud nail or other to the spark terminal on the control module It also help assure proper marking of the wires attached to the existing control and a label with LED code information that can be affixed in the appliance IMPORTANT The S8610U control module is not designed to replace controls with Flame sensing other than by flame rectification White Rodgers Cycl...

Страница 2: ...610C1013 S8610C3001 S8610F1008 S8610F1016 S8610F1024 S8610F1032 OFF OFF S8610H1004 OFF ON S8610H1012 OFF OFF S8610H1020 OFF ON S8610H1038 S8610H1046 S8610H1053 OFF OFF S8610H1061 OFF ON S8610H1079 S8610H1095 S8610H3000 OFF OFF S8610H3018 OFF ON S8610H3026 S8610M1003 OFF OFF S8610M1011 OFF ON S8610M1029 S8610M3009 OFF OFF S8610M3017 OFF ON S8610U1003 S8610U1011 OFF OFF S8620C1003 S8620C1011 OFF ON ...

Страница 3: ...BKG 1 G65BKG 2 G65BKG 3 G65BKM 1 G65BKM 2 G65BKM 3 G65BLG 1 G65BLG 2 G65DBG G65DBM 1 G65DBM 2 G65DBM 3 G65DCM 1 G65DFG G65DFM 1 G65DKG G65DKM G65DKM 1 G65DLM 1 G65FBG G65FFG G65FKG OFF OFF Table 2 S8610U Replaces These Modules Continued Vendor Model SW1 SW2 G66AG 1 G66AG 2 G66BG 1 G66MG 1 G66MG 2 G66NG 1 OFF OFF G67AG 3 G67AG 4 G67AG 7 G67AG 8 G67AG 9 G67AG 10 G67AG 11 G67BG 2 G67BG 3 G67BG 4 G67B...

Страница 4: ...for the ignition control module Corrosive Chemicals Corrosive chemicals can attack the ignition control module and gas control eventually causing a failure If chemicals are used for routine cleaning make sure they do not reach the controls Where chemicals are suspended in air as in some industrial or agricultural applications use a NEMA 4 enclosure for the ignition control module Dust or Grease Ac...

Страница 5: ...rm Pre Installation Safety Check The pre installation checks described below must be done before the replacement ignition control module is installed If a condition that could result in unsafe operation is detected the appliance should be shut off and the owner advised of the unsafe condition Correct any potentially unsafe condition before proceeding with the installation The following safety chec...

Страница 6: ...ield wiring terminals Operating ambient temperatures between 40 F 40 C and 165 F 74 C Relative humidity below 95 non condensing Protection from water steam or corrosive chemicals that are used to clean the appliance Protection from dripping water such as from an overfilled humidifier or from condensation Protection from dust or grease accumulation IMPORTANT Do not mount with terminals facing up Fi...

Страница 7: ...sor stud on the pilot burner igniter sensor Connect Ignition Control Module CAUTION Equipment Damage Hazard Check the wiring diagram provided on the appliance and compare with Table 5 through Table 8 beginning on page 8 Carefully follow any special instructions affecting the general wiring procedures outlined in this section 1 Connect the wires to the module as shown in the wiring tables Table 5 t...

Страница 8: ...t a vent damper was not installed or if it did not have a vent damper connector then connect the 25V 2 or 24V wire from the old module to the TH W terminal on the S8610U Do not use the 24V terminal on the S8610U If the old module had a vent damper connect it to the P1 connector on the module and wire the terminals as indicated in the table 25V 2 or 24V used only in systems where plug in cable conn...

Страница 9: ...79 Y79A module b b Discard wires between Y79A and module as follows Red to 3 Black to 2 White to GR Discard wire between transformer and 6 Y79A module c c Discard wires between Y79B and module as follows White to 3 Black to 1 Brown to GR Discard wire between transformer and 6 Main Valve Operator MV 3 3 Y79B MV MV 3 Main Valve and Pilot Common MV PV GR GR GR GROUND 5 Pilot Valve Operator PV 1 1 Y79...

Страница 10: ...om E1 which is tagged Thermostat Flame Sensor SENSE d d Important If the USI 715U with combination igniter sensor is not used remove black jumper quick connect from Remote Sense terminal of S8610U Cut jumper wire at circuit board and discard e e Labeled OPT SENSOR on USI 715U No external connection if combination igniter sensor is used d d Igniter Sensor SPARK IGN IGN IGN Table 8 Conversion from C...

Страница 11: ...ves as the common grounding area If there is not good metal to metal contact between the pilot burner and ground run a lead from the pilot burner to ground NOTE Earth ground is not required Wiring Connections Use Fig 2 and Table 9 to make the remaining wiring connections Fig 3 Fig 5 beginning on page 12 illustrate typical wiring connections in heating systems with atmospheric burners and with powe...

Страница 12: ... LEG TO TRANSFORMER ONCE POWERED UP WITH VENT DAMPER CONNECTED MODULE WILL OPERATE ONLY WITH DAMPER CONNECTED FOR SINGLE ROD APPLICATIONS CONNECT JUMPER WIRE TO THE REMOTE SENSE CONNECTOR FOR TWO ROD APPLICATIONS REMOVE JUMPER WIRE BY CUTTING IT AS CLOSE AS POSSIBLE TO THE BASE OF THE MODULE DISCARD CLIPPED WIRE AND FIRMLY ATTACH THE SENSOR WIRE FROM THE IGNITER SENSOR ASSEMBLY TO THE REMOTE SENSE...

Страница 13: ...R WIRE TO THE REMOTE SENSE CONNECTOR FOR TWO ROD APPLICATIONS REMOVE JUMPER WIRE BY CUTTING IT AS CLOSE AS POSSIBLE TO THE BASE OF THE MODULE DISCARD CLIPPED WIRE AND FIRMLY ATTACH THE SENSOR WIRE FROM THE IGNITER SENSOR ASSEMBLY TO THE REMOTE SENSE CONNECTOR M23617 1 2 3 4 5 6 THERMOSTAT L1 HOT L2 LIMIT CONTROLLER 2ND OPERATOR 1ST OPERATOR PILOT COM MAIN VALVE DUAL VALVE COMBINATION GAS CONTROL P...

Страница 14: ...ROD APPLICATIONS REMOVE JUMPER WIRE BY CUTTING IT AS CLOSE AS POSSIBLE TO THE BASE OF THE MODULE DISCARD CLIPPED WIRE AND FIRMLY ATTACH THE SENSOR WIRE FROM THE IGNITER SENSOR ASSEMBLY TO THE REMOTE SENSE CONNECTOR 1 2 3 4 5 6 REMOTE SENSE JUMPER WIRE CLIPPED CLOSE TO BOARD TWO ROD SENSOR WIRE FROM IGNITER SENSOR 6 THERMOSTAT L1 HOT L2 1 LIMIT CONTROLLER 2 4 3 M23586 AIR PROVING SWITCH COMBUSTION ...

Страница 15: ...out the gas control system At initial installation of the appliance As part of regular maintenance procedures Maintenance intervals are determined by the application For additional information See Planning the Installation on page 4 As the first step in troubleshooting Any time work is done on the system WARNING Fire or Explosion Hazard Failure to heed these warnings may cause fire or explosion wi...

Страница 16: ...r main burner 6 Set thermostat below room temperature and wait one minute before continuing Step 6 Check Normal Operation 1 Turn on the gas supply 2 Set thermostat or controller above room tempera ture to Call for Heat 3 Make sure pilot lights smoothly when gas reaches the pilot burner 4 Make sure main burner lights smoothly without flashback 5 Make sure burner operates smoothly without float ing ...

Страница 17: ...rating Sequence OPERATING SEQUENCE CALL FOR HEAT RECEIVED FROM THERMOSTAT POWER TO MODULE AND SELF CHECK IDLE NOT POWERED RUN YES TRIAL FOR IGNITION TIMER STARTED SPARK ON OPEN PILOT GAS VALVE FLAME PROVED FLAME STABILIZATION 2 SECONDS YES NO RETRY OPEN MAIN GAS VALVE CLOSE MAIN GAS VALVE AND PILOT GAS VALVE FLAME LOST NO CLOSE PILOT GAS VALVE SPARK OFF CALL FOR HEAT ENDS YES NO RETRY DELAY 5 MINU...

Страница 18: ...trol module and to the igniter or igniter sensor are clean and tight 5 Ignition cable provides good electrical continuity STEP 2 Check Ignition System Grounding Nuisance shutdowns are often caused by a poor or erratic ground A common ground is required for the ignition control module and the pilot burner bracket 1 Check for good metal to metal contact between the pilot burner bracket and the main ...

Страница 19: ...ems and their causes i If necessary adjust pilot flame by turning the pilot adjustment screw on the gas control clock wise to decrease or counterclockwise to increase pilot flame Following adjustment always replace pilot adjustment cover screw and tighten firmly to assure proper gas control operation j Set thermostat below room temperature to end Call for Heat 4 Recheck ignition sequence as follow...

Страница 20: ...al for ignition Flash code will remain through the ignition trial until flame is proved If system fails to light on next trial for ignition check gas supply pilot burner flame sense wiring contamination of flame rod burner ground connection 4 Flame sensed out of sequence If situation self corrects within 10 seconds control module returns to normal sequence If flame out of sequence remains longer t...

Страница 21: ... FOR HEAT IS ALWAYS CONNECTED TO THE TH W TERMINAL ON THE MODULE START BEFORE TROUBLESHOOTING FAMILIARIZE YOURSELF WITH THE STARTUP AND CHECKOUT PROCEDURES TURN THERMOSTAT CONTROLLER TO CALL FOR HEAT CHECK LINE VOLTAGE POWER LOW VOLTAGE TRANSFORMER LIMIT CONTROLLER THERMOSTAT CONTROLLER AND WIRING ALSO CHECK AIR PROVING SWITCH ON COMBUSTION AIR BLOWER SYSTEM IF USED AND THAT THE END SWITCH IF USED...

Страница 22: ...S8610U UNIVERSAL INTERMITTENT PILOT GAS IGNITION CONTROL 69 1955 22 ...

Страница 23: ...S8610U UNIVERSAL INTERMITTENT PILOT GAS IGNITION CONTROL 23 69 1955 ...

Страница 24: ...d Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2006 Honeywell International Inc 69 1955 M S 11 06 ...

Отзывы: