Page 126
SMV800 Modbus User's Guide
Revision 1.0
Information
121
Bit - 5
ps_no_factory_c
alibration
Factory Calibration for the
Pressure
module is missing.
Accuracy will be
compromised.
Return the device for
Factory Calibration
Bit - 6
pres_unreliable_
comm
Internal communication
quality between the
Communication Module
and Pressure Sensor is
degrading.
Either the transmitter is
installed in a noisy
environment or internal
communication quality
between the
Communication Module
and Pressure Sensor
module is degrading.
Verify the connector for
bent pins.If
cable/connector is not the
problem, replace the
Communication module.If
problem still persists,
replace the Terminal
board.
Bit - 7
ps_sensor_over
_temperature
The Meter Body
temperature is too high.
Accuracy and life span
may decrease if it
remains high.
Verify the environmental
temperature is within
specification. Take steps to
insulate the
Temperature module from
the temperature
source.
Bit 8 -
15
Unsed
NA
NA
Information
122
Bit - 0
common_db_co
rrupt
NVM copy of Common
database block found
corrupt.
Power cycle the device. If
the problem persists,
replace the transmitter
Bit -1
vital_config_db_
corrupt
NVM copy of Vital
Configuration database
block found corrupt.
Power cycle the device. If
the problem persists,
replace the transmitter
Bit - 2
general_config_
db_corrupt:1;
NVM copy of General
Configuration database
block found corrupt.
Power cycle the device. If
the problem persists,
replace the transmitter
Bit - 3
config_change_
db_corrupt
NVM copy of Configuration
Change database block
found corrupt.
Power cycle the device. If
the problem persists,
replace the transmitter
Bit - 4
adv_diag_db_co
rrupt
NVM copy of Advanced
Configuration database
block found corrupt.
Power cycle the device. If
the problem persists,
replace the transmitter
Bit - 5
meter_view_db_
corrupt
NVM copy of Display
View/Screens
Configuration database
block found corrupt.
Power cycle the device. If
the problem persists
reconfigure Display Screen
parameters. If still problem
is seen replace
communication module.
Содержание SMV800
Страница 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Страница 86: ...Page 74 SMV800 Modbus User s Guide Revision 1 0 Use method Reset Tamper Counter to reset the tamper attempts ...
Страница 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Страница 98: ...Page 86 SMV800 Modbus User s Guide Revision 1 0 2 7 SMV 800 Modbus Host Menu tree Device Setup Menu ...
Страница 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Страница 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Страница 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Страница 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Страница 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Страница 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Страница 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Страница 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Страница 116: ......