Page 112
SMV800 Modbus User's Guide
Revision 1.0
3.2.10.
Implementing calibration
Each process variable in the SMV800 Modbus device (diffrential Pressure [DP],
static pressure[SP], and process temperature[PT]) can be calibrated through a trim
process, either a zero trim or two-point trim. The lower trim value acts the same as
zero trim. The upper trim serves to adjust the span (or slope) of the device. The trim
value should be written to the appropriate Floating Point Registers in
Table 3-5
.
For accurate calibration, the user should be prompted to wait for the process variable
to stabilize before attempting to trim the transmitter. For best result, a Lower Trim
should be completed before attempting the Upper Trim.
Refer section
4.1
on Calibration for more information.
Содержание SMV800
Страница 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Страница 86: ...Page 74 SMV800 Modbus User s Guide Revision 1 0 Use method Reset Tamper Counter to reset the tamper attempts ...
Страница 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Страница 98: ...Page 86 SMV800 Modbus User s Guide Revision 1 0 2 7 SMV 800 Modbus Host Menu tree Device Setup Menu ...
Страница 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Страница 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Страница 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Страница 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Страница 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Страница 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Страница 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Страница 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Страница 116: ......