background image

PRO TH3110B Non-programmable Digital Thermostat

11

Installation Guide

10

Inside

Set To

75

75

Heat On

Cool On

°

°

Replace Batt

Quick reference to display screen

Current inside temperature 

Low battery warning 

Temperature setting

System status 

On when “calling” for
heating or cooling; 
flashes when waiting for
compressor restart

Quick reference to controls

Digital display screen

Temperature buttons

Press to adjust temperature 
settings 

System switch

Cool:

Thermostat controls only

the cooling system.

Heat:

Thermostat controls only

the heating system.

Off:

Heating and cooling 

systems are off.

Fan switch
On:

Fan runs continuously.

Auto:

Fan runs only when heating 

or cooling system is on.

In case of difficulty

If you have difficulty with your thermostat, please try the suggestions below. Most
problems can be corrected quickly and easily.

Display is blank

Make sure fresh AA alkaline batteries are correctly installed (see page 7).

Fan does not
turn on in a 
call for heat

Make sure the Fan Operation switch is set to the proper system (see page 6).

Heating system
does not respond
(“Heat On”
appears on
screen)

Check for 24 Vac at the equipment on the secondary side of the trans-
former between power and common. If voltage is not present, check the
heating equipment to find the cause of the problem.

Check for 24 Vac between the heat terminal (W) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
heating equipment to find the cause of the problem.

Check for loose or broken wires between the thermostat and the heating
equipment.

Cooling system
does not respond
(“Cool On”
appears on
screen)

Check for 24 Vac at the equipment on the secondary side of the trans-
former between power and common. If voltage is not present, check the
cooling equipment to find the cause of the problem

Check for 24 Vac between the cooling terminal (Y) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
cooling system to find the cause of the problem.

Check for loose or broken wires between the thermostat and the cooling
equipment.

Temperature 
settings do not
change

Make sure heating and cooling temperatures are set to acceptable ranges:

Heat: 40° to 90°F (4.5° to 32°C).

Cool: 50° to 99°F (10° to 37°C).

“Cool On” or
“Heat On” 
is flashing

Compressor protection timeout is engaged. Wait 5 minutes for the 
system to restart safely, without damage to the compressor.

“Heat On” is
not displayed

Set the System switch to Heat, and set the temperature level above the
current room temperature (see page 10).

“Cool On” is 
not displayed

Set the System switch to Cool, and set the temperature level below the
current room temperature (see page 10).

Inside

Set To

75

75

Cool On

°

°

Built-in compressor protection (Setup Function 15)

This feature helps prevent damage to the
compressor in the air conditioning or heat
pump system.

Damage can occur if the compressor is re-
started too soon after shutdown.This feature
forces the compressor to wait for a few min-
utes before restarting.

During the wait time, the message Cool On
(or Heat On if you have a heat pump) will
flash on the display.When the safe wait time
has elapsed, the message stops flashing and
the compressor turns on.

Message flashes until safe
restart time has elapsed

Содержание PRO TH3110B

Страница 1: ...Installation Guide TH3110B Non programmable Digital Thermostat ...

Страница 2: ... control that contains mercury in a sealed tube do not place the old control in the trash Contact your local waste management authority for instructions regarding recycling and proper disposal Install the thermostat about 5 feet 1 5m above the floor in an area with good air circulation at average temperature Do not install in locations where the thermostat can be affected by Drafts or dead spots b...

Страница 3: ... control that contains mercury in a sealed tube do not place the old control in the trash Contact your local waste management authority for instructions regarding recycling and proper disposal Install the thermostat about 5 feet 1 5m above the floor in an area with good air circulation at average temperature Do not install in locations where the thermostat can be affected by Drafts or dead spots b...

Страница 4: ...or drywall 7 32 for plaster Hammer Pencil Electrical tape Level optional Remove the wallplate from the ther mostat as shown at left then follow directions below for mounting 1 Pull wires through wire hole 2 Position wallplate on wall level and mark hole positions with pencil 3 Drill holes at marked positions as shown below then tap in supplied wall anchors 4 Place wallplate over anchors insert and...

Страница 5: ...or drywall 7 32 for plaster Hammer Pencil Electrical tape Level optional Remove the wallplate from the ther mostat as shown at left then follow directions below for mounting 1 Pull wires through wire hole 2 Position wallplate on wall level and mark hole positions with pencil 3 Drill holes at marked positions as shown below then tap in supplied wall anchors 4 Place wallplate over anchors insert and...

Страница 6: ...umper in place between R Rc Remove metal jumper if two transformer system Heat pump systems If wiring to a heat pump use a small piece of wire not supplied to connect terminals W and Y Wire specifications Use 18 to 22 gauge thermostat wire Shielded cable is not required Keep wires in this shaded area CAUTION ELECTRICAL HAZARD Can cause electrical shock or equipment damage Disconnect power before w...

Страница 7: ...umper in place between R Rc Remove metal jumper if two transformer system Heat pump systems If wiring to a heat pump use a small piece of wire not supplied to connect terminals W and Y Wire specifications Use 18 to 22 gauge thermostat wire Shielded cable is not required Keep wires in this shaded area CAUTION ELECTRICAL HAZARD Can cause electrical shock or equipment damage Disconnect power before w...

Страница 8: ...ted to the G G terminal Set fan operation switch Fan operation settings Install batteries in back of thermostat Install two AA alkaline batteries in the back of the thermostat as shown at left Fresh batteries should be installed immediately when the R RE EP PL LA AC CE E B BA AT TT T warn ing begins flashing see page 10 The warning flashes about two months before batteries are depleted Even if the...

Страница 9: ...ted to the G G terminal Set fan operation switch Fan operation settings Install batteries in back of thermostat Install two AA alkaline batteries in the back of the thermostat as shown at left Fresh batteries should be installed immediately when the R RE EP PL LA AC CE E B BA AT TT T warn ing begins flashing see page 10 The warning flashes about two months before batteries are depleted Even if the...

Страница 10: ...t and fan turn off 1 Heat turns on Fan also turns on immediately if Fan Operation Switch is set to Electric Heat Heat Pump see page 6 0 Compressor and fan turn off 1 Compressor and fan turn on 71 Software revision number major revisions 72 Software revision number minor revisions 73 Configuration identification code major 74 Configuration identification code minor 75 Production configuration date ...

Страница 11: ...t and fan turn off 1 Heat turns on Fan also turns on immediately if Fan Operation Switch is set to Electric Heat Heat Pump see page 6 0 Compressor and fan turn off 1 Compressor and fan turn on 71 Software revision number major revisions 72 Software revision number minor revisions 73 Configuration identification code major 74 Configuration identification code minor 75 Production configuration date ...

Страница 12: ...e thermostat and the heating equipment Cooling system does not respond Cool On appears on screen Check for 24 Vac at the equipment on the secondary side of the trans former between power and common If voltage is not present check the cooling equipment to find the cause of the problem Check for 24 Vac between the cooling terminal Y and the transformer common If 24 Vac is present the thermostat is f...

Страница 13: ...e thermostat and the heating equipment Cooling system does not respond Cool On appears on screen Check for 24 Vac at the equipment on the secondary side of the trans former between power and common If voltage is not present check the cooling equipment to find the cause of the problem Check for 24 Vac between the cooling terminal Y and the transformer common If 24 Vac is present the thermostat is f...

Страница 14: ... 90 F 4 5 to 32 C Cool 50 to 99 F 10 to 37 C Operating Ambient Temperature 32 to 120 F 0 to 48 9 C Shipping Temperature 20 to 120 F 28 9 to 48 9 C Operating Relative Humidity 5 to 90 non condensing Physical Dimensions 3 13 16 H x 5 3 8 W x 1 1 4 D 97 mm H x 137 mm W x 32 mm D Electrical Ratings System Voltage 50 60Hz Running Current Heating 20 30 Vac 0 02 1 0 A Powerpile 750 mV DC 100 mA DC Coolin...

Страница 15: ... 90 F 4 5 to 32 C Cool 50 to 99 F 10 to 37 C Operating Ambient Temperature 32 to 120 F 0 to 48 9 C Shipping Temperature 20 to 120 F 28 9 to 48 9 C Operating Relative Humidity 5 to 90 non condensing Physical Dimensions 3 13 16 H x 5 3 8 W x 1 1 4 D 97 mm H x 137 mm W x 32 mm D Electrical Ratings System Voltage 50 60Hz Running Current Heating 20 30 Vac 0 02 1 0 A Powerpile 750 mV DC 100 mA DC Coolin...

Страница 16: ...Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 Automation and Control Solutions U S Registered Trademark Patents pending Copyright 2005 Honeywell International Inc All rights reserved Printed in U S A Document number 69 1793 Date 01 2005 www honeywell com yourhome ...

Отзывы: