background image

Honeywell 

INNCOM e7 Thermostat 

Installation Instructions 

FOR ALL UNITS IN CARTON. DO NOTTHR OW AWAY! 

LLcAuT10N 

Disconnect the power supply before beginning 

installation to prevent electrical shock or 

equipment damage. All wiring must comply with 

local codes and ordinances. 

• Read instructions carefully. Failure to follow them could

damage the product or create a hazard.

• Check the ratings given in the instructions and on the

product to make sure the product is suitable for your

application.

• Installer must be a trained, experienced service technician.

• After installation is complete, check product operation as

indicated in instructions.

• For variations of these systems, refer to the installation

instructions of the controlled equipment.

INSTALLATION 
Location 

Select a location about 1.5m (5ft.) above the floor with good 

air circulation at average temperature. Do not mount 

thermostat where it may be affected by: 
• Drafts or dead spots behind doors or in comers.

• Hot or cold air from ducts.

• Radiant heat from sun or appliances.

• Concealed pipes or chimneys.

• Unheated (un-cooled) areas behind the thermostat.

• If RF equipped, do not install near other RF sources/

transmitters.

• When the thermostat is equipped with PIR, consider view

angle, range characteristics, and mounting position for

proper coverage.

Mounting 

The INNCOM e7 thermostat is typically mounted on a 

standard double-gang (4 x 4) junction box. The installation 

kit provides a Smart Wall Plate and a Spacer Ring. When 

installing the Smart Wall Plate, use hand tools only (no 

power tools

!) to avoid bending or damaging the Smart 

Wall Plate or PO

GO pins that connect to the thermostat.  

The Spacer Ring is 

highly

 recommended for all installations 

and is required whenever a standard double-gang (4x4) 

junction box is not available. 

If mounted on a single-gang box, the right side (keypad side) of 

the e7 overlaps the wall area to the right. A low-voltage 

mounting plate, mud ring, or low-voltage caddy may be used 

for mounting 24 volt applications. 
To mount the e7, complete the following steps: 

INSTALLATION INSTRUCTIONS 

1. Position the Spacer Ring and Smart Wall Plate as shown

in Fig. 1.

2. Ensure the spacer ring and Smart Wall Plate are orient-

ed with the raised arrow pointing UP. Snap them to-

gether, ensuring all 4 comer snap hooks are attached,

then attach to the junction box using the supplied

screws (hand tools only, no power tools

!

), making sure

the Smart Wall Plate is flat and flush with the wall.

3. Use wire nuts to connect the Power and HVAC wiring

harness to the power and valve/fan control signal wires

within the electrical box. See the pre-defined commis­

sioning document for application-specific wire connec­

tions.

4. To connect the unit to the input power and the relays to

the loads, plug the pre-wired power and HVAC signal

harness connector into the female receptacle at the back

of the e7 (HI). When using mixed voltage, voltage sepa­

ration must be maintained. Line voltage must reside in

the left side of the gang box. Low voltage must reside in

the right side of the gang box.

5. Hook the tabs at the top rear of the e7 housing into the

matching depressions at the top of the Smart Mounting

Plate and rotate the bottom of the housing toward the

wall until it snaps into place.

6. Secure the housing to the Smart Wall Plate with the two

small captive screws at the bottom of the housing.

7. Apply power to the e7 by closing the applicable supply

breaker. After connecting power, wait 5 seconds. values

will begin appearing on the LCD display.

4x4 Junction  Box 

Spacer Ring 

Power/HVAC signal 

harness to thermostat 

Smart 

W

all Plate 

Fig. 1. e7 Exploded View Assembly Reference 