PRO TH3110B Non-programmable Digital Thermostat
11
Installation Guide
10
Inside
Set To
75
75
Heat On
Cool On
°
°
Replace Batt
Quick reference to display screen
Current inside temperature
Low battery warning
Temperature setting
System status
On when “calling” for
heating or cooling;
flashes when waiting for
compressor restart
Quick reference to controls
Digital display screen
Temperature buttons
Press to adjust temperature
settings
System switch
•
Cool:
Thermostat controls only
the cooling system.
•
Heat:
Thermostat controls only
the heating system.
•
Off:
Heating and cooling
systems are off.
Fan switch
On:
Fan runs continuously.
Auto:
Fan runs only when heating
or cooling system is on.
In case of difficulty
If you have difficulty with your thermostat, please try the suggestions below. Most
problems can be corrected quickly and easily.
Display is blank
•
Make sure fresh AA alkaline batteries are correctly installed (see page 7).
Fan does not
turn on in a
call for heat
•
Make sure the Fan Operation switch is set to the proper system (see page 6).
Heating system
does not respond
(“Heat On”
appears on
screen)
•
Check for 24 Vac at the equipment on the secondary side of the trans-
former between power and common. If voltage is not present, check the
heating equipment to find the cause of the problem.
•
Check for 24 Vac between the heat terminal (W) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
heating equipment to find the cause of the problem.
•
Check for loose or broken wires between the thermostat and the heating
equipment.
Cooling system
does not respond
(“Cool On”
appears on
screen)
•
Check for 24 Vac at the equipment on the secondary side of the trans-
former between power and common. If voltage is not present, check the
cooling equipment to find the cause of the problem
•
Check for 24 Vac between the cooling terminal (Y) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
cooling system to find the cause of the problem.
•
Check for loose or broken wires between the thermostat and the cooling
equipment.
Temperature
settings do not
change
Make sure heating and cooling temperatures are set to acceptable ranges:
•
Heat: 40° to 90°F (4.5° to 32°C).
•
Cool: 50° to 99°F (10° to 37°C).
“Cool On” or
“Heat On”
is flashing
•
Compressor protection timeout is engaged. Wait 5 minutes for the
system to restart safely, without damage to the compressor.
“Heat On” is
not displayed
•
Set the System switch to Heat, and set the temperature level above the
current room temperature (see page 10).
“Cool On” is
not displayed
•
Set the System switch to Cool, and set the temperature level below the
current room temperature (see page 10).
Inside
Set To
75
75
Cool On
°
°
Built-in compressor protection (Setup Function 15)
This feature helps prevent damage to the
compressor in the air conditioning or heat
pump system.
Damage can occur if the compressor is re-
started too soon after shutdown.This feature
forces the compressor to wait for a few min-
utes before restarting.
During the wait time, the message Cool On
(or Heat On if you have a heat pump) will
flash on the display.When the safe wait time
has elapsed, the message stops flashing and
the compressor turns on.
Message flashes until safe
restart time has elapsed