background image

1

0

PRO TH3110B Non-programmable Digital Thermostat

9

Installation Guide

8

1

5

9

14

15

System type

Heating cycle rate

(CPH: cycles/hour)

Compressor
cycle rate 

(CPH)

Temperature 
display

Compressor 
protection

0 Gas, oil or electric heat with air conditioning

1

Heat pump (5 minute compressor off time in heating and cooling)

5 For gas or oil furnaces of less than 90% efficiency

1

For steam or gravity systems

3

For hot water systems & furnaces of over 90% efficiency

9

For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]

3 Recommended for most compressors

[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]

0 Fahrenheit

1

Celsius

5 Five-minute compressor off time 

**See page 10

[Other options: 0, 1, 2, 3 or 4-minute off time]

Setup Function

Settings & Options

To begin, press and hold the and
buttons until the display changes

Function
number

Press 

to change settings

Press 

to advance to next function

Press and hold

to exit and save settings

Setting

Installer setup

Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.

Setup

10

0

Test

10

30

70

Heating system

Cooling system

Thermostat
information

(for reference only)

0

Heat and fan turn off.

1

Heat turns on. Fan also turns on immediately if Fan Operation
Switch is set to Electric Heat/Heat Pump (see page 6).

0

Compressor and fan turn off.

1

Compressor and fan turn on.

71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)

System Test

System Status 

Installer system test

CAUTION: EQUIPMENT DAMAGE HAZARD

Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.

System switch

System test
number

System status

Installer system test

After completing the installer setup above, press the 

button again to begin a

system test (see next page).

Press and hold both buttons

1

Set 

S

SY

YS

ST

TE

EM

M

switch to Cool.

2

Press 

to turn on cooling system, then check system status (see table, below).

3

Press 

to turn off cooling system.

4

Set 

S

SY

YS

ST

TE

EM

M

switch to Heat.

5

Press 

to turn on heating system, then check system status (see table, below).

6

Press 

to turn off heating system.

7

[Optional] Set 

S

SY

YS

ST

TE

EM

M

switch to Off to display thermostat information (see table, below).

Press 

to display 71-76.

8

Press and hold

to terminate system test at any time.

Follow the procedure below to test the heating and cooling system.

Содержание PRO TH3110B

Страница 1: ...Installation Guide TH3110B Non programmable Digital Thermostat ...

Страница 2: ... control that contains mercury in a sealed tube do not place the old control in the trash Contact your local waste management authority for instructions regarding recycling and proper disposal Install the thermostat about 5 feet 1 5m above the floor in an area with good air circulation at average temperature Do not install in locations where the thermostat can be affected by Drafts or dead spots b...

Страница 3: ... control that contains mercury in a sealed tube do not place the old control in the trash Contact your local waste management authority for instructions regarding recycling and proper disposal Install the thermostat about 5 feet 1 5m above the floor in an area with good air circulation at average temperature Do not install in locations where the thermostat can be affected by Drafts or dead spots b...

Страница 4: ...or drywall 7 32 for plaster Hammer Pencil Electrical tape Level optional Remove the wallplate from the ther mostat as shown at left then follow directions below for mounting 1 Pull wires through wire hole 2 Position wallplate on wall level and mark hole positions with pencil 3 Drill holes at marked positions as shown below then tap in supplied wall anchors 4 Place wallplate over anchors insert and...

Страница 5: ...or drywall 7 32 for plaster Hammer Pencil Electrical tape Level optional Remove the wallplate from the ther mostat as shown at left then follow directions below for mounting 1 Pull wires through wire hole 2 Position wallplate on wall level and mark hole positions with pencil 3 Drill holes at marked positions as shown below then tap in supplied wall anchors 4 Place wallplate over anchors insert and...

Страница 6: ...umper in place between R Rc Remove metal jumper if two transformer system Heat pump systems If wiring to a heat pump use a small piece of wire not supplied to connect terminals W and Y Wire specifications Use 18 to 22 gauge thermostat wire Shielded cable is not required Keep wires in this shaded area CAUTION ELECTRICAL HAZARD Can cause electrical shock or equipment damage Disconnect power before w...

Страница 7: ...umper in place between R Rc Remove metal jumper if two transformer system Heat pump systems If wiring to a heat pump use a small piece of wire not supplied to connect terminals W and Y Wire specifications Use 18 to 22 gauge thermostat wire Shielded cable is not required Keep wires in this shaded area CAUTION ELECTRICAL HAZARD Can cause electrical shock or equipment damage Disconnect power before w...

Страница 8: ...ted to the G G terminal Set fan operation switch Fan operation settings Install batteries in back of thermostat Install two AA alkaline batteries in the back of the thermostat as shown at left Fresh batteries should be installed immediately when the R RE EP PL LA AC CE E B BA AT TT T warn ing begins flashing see page 10 The warning flashes about two months before batteries are depleted Even if the...

Страница 9: ...ted to the G G terminal Set fan operation switch Fan operation settings Install batteries in back of thermostat Install two AA alkaline batteries in the back of the thermostat as shown at left Fresh batteries should be installed immediately when the R RE EP PL LA AC CE E B BA AT TT T warn ing begins flashing see page 10 The warning flashes about two months before batteries are depleted Even if the...

Страница 10: ...t and fan turn off 1 Heat turns on Fan also turns on immediately if Fan Operation Switch is set to Electric Heat Heat Pump see page 6 0 Compressor and fan turn off 1 Compressor and fan turn on 71 Software revision number major revisions 72 Software revision number minor revisions 73 Configuration identification code major 74 Configuration identification code minor 75 Production configuration date ...

Страница 11: ...t and fan turn off 1 Heat turns on Fan also turns on immediately if Fan Operation Switch is set to Electric Heat Heat Pump see page 6 0 Compressor and fan turn off 1 Compressor and fan turn on 71 Software revision number major revisions 72 Software revision number minor revisions 73 Configuration identification code major 74 Configuration identification code minor 75 Production configuration date ...

Страница 12: ...e thermostat and the heating equipment Cooling system does not respond Cool On appears on screen Check for 24 Vac at the equipment on the secondary side of the trans former between power and common If voltage is not present check the cooling equipment to find the cause of the problem Check for 24 Vac between the cooling terminal Y and the transformer common If 24 Vac is present the thermostat is f...

Страница 13: ...e thermostat and the heating equipment Cooling system does not respond Cool On appears on screen Check for 24 Vac at the equipment on the secondary side of the trans former between power and common If voltage is not present check the cooling equipment to find the cause of the problem Check for 24 Vac between the cooling terminal Y and the transformer common If 24 Vac is present the thermostat is f...

Страница 14: ... 90 F 4 5 to 32 C Cool 50 to 99 F 10 to 37 C Operating Ambient Temperature 32 to 120 F 0 to 48 9 C Shipping Temperature 20 to 120 F 28 9 to 48 9 C Operating Relative Humidity 5 to 90 non condensing Physical Dimensions 3 13 16 H x 5 3 8 W x 1 1 4 D 97 mm H x 137 mm W x 32 mm D Electrical Ratings System Voltage 50 60Hz Running Current Heating 20 30 Vac 0 02 1 0 A Powerpile 750 mV DC 100 mA DC Coolin...

Страница 15: ... 90 F 4 5 to 32 C Cool 50 to 99 F 10 to 37 C Operating Ambient Temperature 32 to 120 F 0 to 48 9 C Shipping Temperature 20 to 120 F 28 9 to 48 9 C Operating Relative Humidity 5 to 90 non condensing Physical Dimensions 3 13 16 H x 5 3 8 W x 1 1 4 D 97 mm H x 137 mm W x 32 mm D Electrical Ratings System Voltage 50 60Hz Running Current Heating 20 30 Vac 0 02 1 0 A Powerpile 750 mV DC 100 mA DC Coolin...

Страница 16: ...Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 Automation and Control Solutions U S Registered Trademark Patents pending Copyright 2005 Honeywell International Inc All rights reserved Printed in U S A Document number 69 1793 Date 01 2005 www honeywell com yourhome ...

Отзывы: