background image

P7810A-D PRESSURETROL® CONTROLLER

11

65-0268—1

Table 8. LED Fault Codes and Recommended Troubleshooting.

CHECKOUT

WARNING

Electrical Shock Hazard and Explosion Hazard.

Can cause severe injury, death or property 

damage.

1. Live voltage is present at the P7810 and all 

controller circuits. Use extreme care during 

checkout.

2. This checkout procedure disables the Safety High 

Limit function.

IMPORTANT

1. Do not put the system into service until all applicable 

tests described in the Checkout section of the 

instructions for the primary safety control and any 

additional tests required by the burner or boiler 

manufacturer are satisfactorily completed.

2. Close all manual fuel shutoff valves when trouble 

occurs.

After installation and wiring, check out the P7810 

Pressuretrol® Controller with the system in operation. 

Checkout

1.

Allow the system to stabilize.

2.

Observe the operation of the P7810 while raising and 

lowering the setpoint. Pressure increases when the 

setpoint is increased and decreases when the setpoint 

is decreased.

3.

Check the make and break points of the P7810. If they 

do not agree with a separate, accurately calibrated 

pressure gauge, make a slight adjustment according to 

the scale. Use accurate pressure testing equipment 

when checking out the P7810. Do not rely on 

inexpensive gauges. The P7810 is carefully calibrated 

at the factory.

Test the P7810 Pressuretrol® Controller as follows:

NOTE: Make sure the P7810 is operating properly by 

checking the LED indicators. If the P7810 LEDs 

indicate a lockout condition, press the manual reset 

button.

NOTE: This procedure simulates pressure changes using 

knob setpoint adjustments. Make knob adjustments 

very slowly because of filtering delays within the 

P7810 (20 to 25 seconds for full scale change). 

Inaccuracy can result if knob adjustments are not 

made very slowly. To observe actual P7810 control 

accuracy, set the knobs to normal operating values. 

Compare the knob settings to the boiler pressure 

readings where P7810 actions occur.

To check the control setpoint of the P7810A,B,C,D:

1.

Note the boiler pressure by checking the boiler pressure 

gauge. To properly perform these tests, the boiler 

pressure should be near the middle of the P7810 

pressure range.

2.

Turn the P7810 limit setpoint knob fully clockwise to 

make sure this limit does not interfere during steps 

4

 

and 

5

. This setting must return to the proper operating 

position when returning the system to normal operation.

3.

Check the control setpoint and control differential.

4.

Set the control differential knob to the center of its 

range.

5.

Turn the control setpoint knob fully counterclockwise 

and make sure the P7810 control circuit is open and the 

green LED is off (no call for heat).

6.

Read the boiler pressure gauge and add this number to 

the control differential setting.

7.

Turn the control setpoint knob slowly clockwise and 

make sure the control circuit closes and the P7810 indi-

cates a call for heat (green LED on) when the P7810 

control setpoint passes through the value determined in 

step 

6

.

8.

Turn the control setpoint knob slowly counterclockwise 

and make sure the control circuit opens and the P7810 

no longer indicates a call for heat (green LED off) when 

the control setpoint passes through the boiler pressure 

gauge value.

Check the modulation setpoint and modulation range of the 

P7810B,C as follows:

1.

Set the P7810 modulation range knob to the center of 

the range.

2.

Turn the modulation setpoint knob fully clockwise and 

make sure the firing rate motor travels to the fully open 

position (boiler is firing).

3.

Turn the modulation setpoint knob slowly 

counterclockwise and make sure the firing rate motor 

starts moving toward the closed position when the 

modulation setpoint passes through the boiler pressure 

gauge value. (Alternately, make sure the current starts 

decreasing toward 4 mA.)

Fault Code

System Failure

Recommended Troubleshooting

11

High Limit Setpoint Exceeded.

When pressure in vessel returns to normal, P7810 can be reset.

12-32, 

71-90, 92

Internal fault

Reset P7810; if same fault occurs again, replace P7810.

51, 54, 61

Internal fault—internal relays 

welded

Verify loads do not exceed rating of P7810 contacts, then replace P7810.

52-69, 91

Relay fault

Verify that no voltage potential exists on Output terminal.

If code repeats after normal operation, look for back feed of voltage greater 

than 50V (ac or dc) any time during boiler sequence.

Replacing P7810 will only result in same lockout on new control.

Содержание Pressuretrol P7810A

Страница 1: ...rode the pressure sensing element Models available with on off control function on off control and modulate high limit and modulate and on off control and safety high limit functions Models available in 15 150 and 300 psi 103 1034 and 2069 kPa maximum setpoints LED indicators show power call for heat function and lockout status Clear cover allows setpoint and differential to be read but not adjust...

Страница 2: ...ntact Ratings a P7810C D models only Sensor Material 304 stainless steel Pressure Connector P7810A B 1 4 in NPT P7810C D 1 2 in NPT Case Material Plastic Electrical Terminations Screw terminals Accuracy 4 0 percent full scale output operating range over operating temperature Environmental Ratings Operating Temperature Range 32 F to 140 F 0 C to 60 C Storage Temperature Range 20 F to 150 F 29 C to ...

Страница 3: ...fore removing old control 3 Follow all installation and checkout procedures for safe installation IMPORTANT Do not remove the overpressure inlet seal until ready to connect piping to prevent contamination of inlet Location Install the P7810 Pressuretrol Controller above the boiler water line when used with steam boilers Connect the siphon loop part number 14026 for P7810A B 209731A for P7810C D or...

Страница 4: ...with an approved weather tight enclosure CAUTION Equipment Damage Hazard Incorrect installation of the L404 Pressure Controller can damage the equipment and may require boiler replacement Install the L404C Pressuretrol as shown in Fig 2 and 3 to prevent equipment damage Fig 2 Connecting P7810A B Pressuretrol Controller to steam boiler Fig 3 Right and wrong mounting of steam trap siphon loop for th...

Страница 5: ...onnect may be involved All wiring must comply with applicable electrical codes ordinances and regulations Use NEC Class 1 line voltage wiring For normal installation use moisture resistant No 14 wire maximum size allowed suitable for at least 167 F 75 C or 194 F 90 C for Flame Safeguard Primary Controls Use shielded wire for 4 to 20 mA modulating output and terminate the shield to earth ground Do ...

Страница 6: ...1 2 12 13 15 14 R B W 4 TO 20mA ALARM FIELD WIRING 2K1 1K1 DEVICE WIRING OUTPUT 3K1 14 LOW FIRE 15 MODULATE 13 COMMON 8K1 8K2 9K2 9K1 AUTO MAN 66 5 OHM 237 OHM 12 HIGH FIRE 7800 SERIES PROGRAMMER W M20568C R B MODUTROL IV MOTOR CONTROLLER P7810 4 2O mA SERIES 90 1K OHM 7800 SERIES SHOWN REFER TO SPECIFICATIONS PACKED WITH THE PROGRAMMER FOR WIRING OF OTHER PRIMARY SAFETY CONTROLLERS 1 1 LOW FIRE 1...

Страница 7: ...ferential setting This cycle continues until power is removed opening the relay See Fig 11 Fig 11 P7810 on off control function versus pressure Modulate Control Function P7810B C Only When the pressure decreases to or below the modulation setpoint the current is 20 mA The current remains constant at all pressures below the modulation setpoint The modulation range is an additive value to the modula...

Страница 8: ...ed Stop Limit Value P7810C D CAUTION Equipment Damage Hazard Exceeding pressure vessel limits can damage equipment The Maximum Fixed Stop Limit pressure setting must not exceed the maximum working pressure rating of the pressure vessel Adjust the Maximum Fixed Stop Limit setting to maximum working pressure rating that is stamped on the pressure vessel by the manufacturer IMPORTANT The Maximum Fixe...

Страница 9: ...g fault code until the reset switch is released Both LEDs turn on after three seconds indicating the Maximum Fixed Stop Limit Value has been stored Wait for up to 30 seconds for a release Enter lockout after 30 seconds The green LED turns off and the yellow LED turns on waiting until the reset switch is released Both LEDs turn on Wait for up to 30 seconds for a release Lockout after 30 seconds If ...

Страница 10: ...te Control P7810B C Only The P7810B C adds 4 to 20 mA modulation output and uses two additional potentiometers The pressure sensor output is fed to an error and gain amplifier to perform the modulation determined by the control potentiometer settings The potentiometer knobs mounted on the P7810B C face adjust the current output for a given set of pressures The modulation range is an additive value...

Страница 11: ...form these tests the boiler pressure should be near the middle of the P7810 pressure range 2 Turn the P7810 limit setpoint knob fully clockwise to make sure this limit does not interfere during steps 4 and 5 This setting must return to the proper operating position when returning the system to normal operation 3 Check the control setpoint and control differential 4 Set the control differential kno...

Страница 12: ...obs to the required operating position 2 Press the reset button to clear the safety lockout condition 3 Start the system and observe the operation through at least one complete cycle to make sure the P7810 functions properly as described in the Operation section TROUBLESHOOTING WARNING Electrical Shock Hazard Can cause severe injury death or property damage Line voltage is present at the P7810 and...

Отзывы: