Specifications
Overview
1.6.2 EIA-485 - TB2
EIA-485 Serial Interface (EIA-485+, EIA-485–, Ref).
Power-limited source must be used. Supervised by control panel and UDACT-2.
12 - 18 AWG twisted shielded pair, characteristic impedance: 120 Ohms, +/- 20%.
1.6.3 Earth - TB2
12 AWG solid wire to provide lightning protection.
An earth ground connection to the UDACT-2 is required for transient protection.
1.6.4 Relay Drive - TB4
Output rated at 40 mA. Power limited, unsupervised.
Drives UL-listed relay MR-101/C or MR-201/C.
Normal output condition is ON (energized).
1.6.5 Telephone
Circuitry
Ringer Equivalence Number (REN) = 0.0B
• AC Impedance 10.0 Mega Ohm
• Mates with RJ31X Male Connector
• Supervision Threshold: less than 4.0 volts for 2 minutes
• FCC Registration Number: US:1W6AL00BUDACT2
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive REN on the telephone
line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the REN should not
exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total REN, contact the
telephone company to determine the maximum REN for the calling area.
Before connecting the UDACT-2 to the public switched telephone network, the installation of two RJ31X jacks is necessary. The follow-
ing information is provided if required by the local telephone company:
1.6.6 Telephone Company Rights and Warnings
The telephone company under certain circumstances may temporarily discontinue services and/or make changes in its facilities, ser-
vices, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give
advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service.
Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided
as soon as possible. The opportunity will be given to correct any problems and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START, OR PARTY LINE SERVICES..
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone system at the protected
premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to the telephone net-
work or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant.
1.6.7 For Canadian Applications
The following is excerpted from CP-01 Issue 5:
NOTE:
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the back of
the UDACT-2 is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. If
requested, this number must be provided to the telephone company.
Manufacturer:
Honeywell Life Safety
12 Clintonville Road
Northford, CT 06472
Product Model Number:
UDACT-2
FCC Registration Number:
US:1W6AL00BUDACT2
Ringer Equivalence:
0.0B
!
CAUTION:
THE UDACT-2 MUST NOT BE USED TO DIAL A PHONE NUMBER THAT IS CALL-FORWARDED PER
REQUIREMENTS OF UL 864 10TH EDITION.