UDACT-2 — Instruction Manual
P/N 54089:B3 10/29/2019
43
AM2020/AFP1010 (UL 8th)
Panel-Specific Information
Below is a remote installation of a UDACT-2 with an NCA-2 using power supplied by an AMPS-24/E:
A.5 AM2020/AFP1010 (UL 8th)
A.5.1 General
The UDACT-2 is capable of reporting up to 2,040 ACS points when used with the AM2020/AFP1010. For the UDACT-2 to correctly
report a point to the Central Station, both the FACP and the UDACT-2 must have each point programmed as the same function type
(refer to “Zone and Point Assignments” on page 26). If a UDACT-2 point does not match the panel point in function, the point will
default to fire alarm and a fire alarm signal will be transmitted to the Central Station.
A.5.2 Mounting
The UDACT-2 may be mounted in the AM2020/AFP1010 control panel enclosure or be mounted remotely using an ABS-8RB, UBS-
1B, or UBS-1R enclosure. The unit must be placed within the same room and within 20 feet (6.1 meters) of the panel. Wiring must be
enclosed in conduit.
A.5.3 Wiring
Connections
Refer to Figures A.12 and A.13.
Connect the communication line between the EIA-485 terminal block on the AM2020/AFP1010 and EIA-485+ and EIA-485- terminals
on TB2 on the UDACT-2, being certain to observe polarity.
If the UDACT-2 is the only or last device connected to the EIA-485, set SW1 DIP 1:4 to ON to enable the UDACT-2’s 120 ohm termi-
nating resistor.
Connect the Ground Wire (PN 71073, provided) from the UDACT-2
EARTH
terminal on TB2 to the CHS-4 Chassis or to a solid building
earth ground.
CAB-3/4 Series Cabinet
To supervised
phone lines
Solid earth ground
EIA-485
(ACS Mode)
TB7 on NCA-2
+24 VDC
non-resettable power
TB3 AUX 24 output
on AMPS-24.
BB-100 or BB-200 Cabinet
Wires in conduit
Remote Cabinet
Figure A.11 UDACT-2 and NCA-2 powered by AMPS-24/E
NOTE:
The UDACT-2 does not support voice and burglary options when used with the AM2020/AFP1010. Refer to the panel’s
Installation Manual for additional restrictions and more information.
!
CAUTION:
REMOVE ALL POWER FROM THE CONTROL PANEL BY DISCONNECTING AC AND BATTERIES BEFORE MAKING
ANY CONNECTIONS TO PREVENT PERSONAL AND/OR CIRCUIT DAMAGE.