UDACT-2 — Instruction Manual
P/N 54089:B3 10/29/2019
17
Installation Options
Installation and Wiring
BMP-1 Blank Module Plate
The UDACT-2 mounts on the back of a BMP-1 blank module plate, so it can be mounted on a DP-DISP, DP-DISP2, or ADP-4B dress
panel.
Remote Installation
For remote installation, the UDACT-2 can mount in an ABS-8RB, UBS-1B, or UBS-1R enclosure. The unit must be placed within the
same room and within 20 feet (6.1 meters) of the panel or network annunciator. Wiring must be enclosed in conduit.
Step
Action
1
Disconnect AC power and disconnect batteries.
2
Mount the BMP-1 onto a DP-DISP, DP-DISP-2, or ADP-4B dress panel by placing it over the two threaded studs and
fastening with two 4-40 KEPS hex nuts (included with BMP-1) as indicated.
3
Attach four 3/16” hex standoffs (p/n 42170, included with UDACT-2) to the BMP-1’s four threaded studs.
4
Align the UDACT-2 over the standoffs and fasten with four 4-40 screws (included with UDACT-2, p/n 38122).
UDA
CT-2
_CH
S
-M
3.wm
f
Screws
Rear Mounting
Front Mounting (two possible positions)
1
2
Screws
Screws
Tab
Tab
Figure 2.8 CHS-M3 Installation
Figure 2.9 BMP-1 and Dress Panel Installation
Screws
Nuts
Standoffs
ud
ac
t-
2
to
bm
p-
a t
o d
p-d
is
p
.wmf
Содержание NOTIFIER UDACT-2
Страница 1: ...Universal Digital Alarm Communicator Transmitter UDACT 2 Document 54089 Rev B3 10 29 2019 ECN 18 305 ...
Страница 50: ...50 UDACT 2 Instruction Manual P N 54089 B3 10 29 2019 Index ...
Страница 52: ...NOTIFIER 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 www notifier com ...