Honeywell Notifier NFS-320SYS Скачать руководство пользователя страница 5

DN-60637:N • 9/15/2022 — Page 5 of 7

          

AEM-48A: 

Same LED capabilities as ACM-48A, expands the ACM-

48A to 96 points. 

See DN-6862.

ACM-8R: 

Remote Relay Module with eight Form-C contacts. Can be

located up to 6,000 ft. (1828.8 m) from panel on four wires. 

See DN-

3558. 

FDU-80: 

Terminal mode. 80-character, backlit LCD display. Mounts

up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. 

See DN-

6820.

LCD2-80: 

Terminal and ACS mode. 80-character, backlit LCD dis-

play. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per
FACP. 

See DN-60548.

LDM: 

Lamp Driver Modules LDM-32, LDM-E32, and LDM-R32;

remote custom driver modules. 

See DN-0551. 

SCS: 

Smoke control stations SCS-8, SCE-8, with lamp drivers SCS-

8L, SCE-8L; eight (expandable to 16) circuits (HVAC only). 

See DN-

4818. 

TM-4: 

Transmitter Module. Includes three reverse-polarity circuits

and one municipal box circuit; mount on NFS-320 chassis or
remotely. 

See DN-6860.

UDACT-2: 

Universal Digital Alarm Communicator Transmitter, 636

channel. 

See DN-60686. 

UZC-256: 

Programmable Universal Zone Coder provides positive

non-interfering successive zone coding. Microprocessor-controlled,
field-programmable from IBM

®

-compatible PCs (requires optional

programming kit). Mounts in 

BB-UZC

See DN-3404. 

C

OMPATIBLE

 I

NTELLIGENT

 D

EVICES

 

NOTE:

 “A” suffix indicates ULC-Listed model:

FWSG(A) Wireless SWIFT Gateway:

 Addressable gateway sup-

ports wireless SLC devices. Order FWSGA for ULC applications.

See DN-60820. 

FCO-951

/-IV

 FlashScan, Addressable intelligent multi-criteria smoke

sensors, photo, carbon monoxide, fixed temperature heat detector
and infra-red (IR). ULC: FCO-951A/-IV

FPC-951

. FlashScan, Combined photoelectric and carbon monoxide

sensor. ULC: FPC-951A.

FSCO-951

. FlashScan, Addressable carbon monoxide sensor. ULC:

FSCO-951A.

FPTI-951, FPTI-951-IV:

 Addressable intelligent multi-criteria photo-

electric, thermal and IR sensors. ULC: FPTI-951A, FPTI-951A-IV.

FS-OSI-RI

Addressable intelligent single-ended beam smoke detec-

tor. ULC: FS-OSI-RIA. 

FSP-951:

 White, low-profile intelligent photoelectric sensor,

FlashScan only. ULC: FSP-951A. 

FSP-951-IV:

 Ivory, low-profile intelligent photoelectric sensor.

ULC: FSP-951A-IV

FSP-951T:

 White, same as FSP-951 but includes a built-in 135°F

(57°C) fixed-temperature thermal device. FlashScan only.
ULC: FSP-951TA. 

FSP-951T-IV:

 Ivory, same as FSP-951T but includes a built-in 135°F

(57°C) fixed-temperature thermal device. ULC: FSP-951TA-IV.

FSP-951R:

 White, low-profile intelligent photoelectric sensor, remote

test capable. For use with DNR/DNRW. FlashScan only. ULC: FSP-
95RA

FSP-951R-IV

: Ivory, low-profile intelligent photoelectric sensor,

remote test capable. FlashScan only. ULC: FSP-95RA-IV, for use
with DNRA. 

FST-951: 

White, low-profile intelligent 135°F fixed thermal sensor,

FlashScan only. Must be mounted to one of the bases listed below.
ULC: FST-951A. 

See DN-60975.

FST-951-IV: 

Ivory, low-profile intelligent 135°F fixed thermal sensor,

FlashScan and CLIP. Must be mounted to one of the bases listed
below. ULC: FST-951A-IV.

FST-951R: 

White, low-profile intelligent rate-of-rise thermal sensor,

FlashScan only. Must be mounted to one of the bases listed below.
ULC: FST-951A

FSP-951R-IV

: Ivory, low-profile intelligent photoelectric sensor,

remote test capable. FlashScan only. ULC: FSP-95RA-IV, for use
with DNRA. 

FSV-951, FSV-951R:

White, intelligent high-sensitivity photoelectric

smoke detector. ULC: FSV-951A, FSV-951RA

FSV-951-IV, FSV-951R-IV

Ivory, intelligent high-sensitivity photoelec-

tric smoke detector. ULC: FSV-951A-IV, FSV-951RA-IV.

FSV-951/-IV, FSV-951A/-IV, FSV-951R/-IV, FSV-951RA-IV: 

Intelli-

gent high-sensitivity photoelectric smoke detector.

VEP-A00-P-NTF:

 Intelligent aspiration smoke detector with LED dis-

play, 4 pipes, covers up to 21,520 square feet. 

See DN-61029. 

UL/

ULC Listed.

VEP-A10-P-NTF:

 Intelligent aspiration smoke detector with LED and

LCD display, 4 pipes, covers up to 21,520 square feet. 

See DN-

61029. 

VEP-A00-1P-NTF:

 Intelligent aspiration smoke detector with LED

display, single pipe, covers up to 10,760 square feet. 

See DN-

61029. 

UL/ULC Listed.

VEU-A00-NTF:

 Intelligent aspiration smoke detector with LED dis-

play, 4 pipes, covers up to 69,965 square feet. 

See DN-61034. 

UL/

ULC Listed.

VEU-A10-NTF:

 Intelligent aspiration smoke detector with LED and

LCD display, 4 pipes, covers up to 69,965 square feet. 

See DN-

61034. 

UL/ULC Listed.

VEA-040-A00-NTF

: Intelligent aspiration with LED display, 40 point-

addressable detection points. Covers 36,000 square feet. 

See DN-

61036. 

UL/ULC Listed.

VEA-040-A10-NTF:

 Intelligent aspiration with LED and LCD display,

40 point-addressable detection points. Covers 36,000 square feet.

See DN-61036. 

UL/ULC Listed.

VES-A00-P-NTF-UL:

 Intelligent scanning aspiration detector with

LEDs. 

See DN-62040. 

UL 268 7th edition. 

VES-A10-P-NTF-UL:

 Intelligent scanning aspiration detector with

3.5” display. 

See DN-62040. 

UL 268 7th edition. 

DNR:

 InnovairFlex low-flow non-relay duct-detector housing. ULC:

DNRA. (Order FSP-951R(A) separately.) See DN-60429. 

DNRW:

 Same as above with NEMA-4 rating, watertight. 

See 

DN-

60429

B224RB-WH: 

White, low-profile relay base. 

See DN-60054. 

ULC:

B224RBA-WH.

B224RB-IV: 

Ivory, plug-in System Sensor relay base. ULC:

B224RBA-IV. 

B224BI-WH:

 White, isolator base for low-profile detectors. 

See DN-

60054. 

ULC: B224BIA-WH.

B224BI-IV: 

Ivory isolator detector base. ULC: B224BIA-IV.

B300-6: 

White, standard flanged low-profile mounting base. (For 10-

pack order B300-6-BP.) ULC: B300A-6.

B300-6-IV: 

Ivory, standard flanged low-profile mounting base. ULC:

B300A-6-IV.

B501-WHITE:

 European-style, 4" (10.16 cm) base. 

See DN-60054.

(For 10-pack order B501-WHITE-BP.) UL/ULC listed.

B501-BL:

 Black, 4” standard European flangeless mounting base.

UL/ULC listed.

B501-IV:

 Ivory color, 4” standard European flangeless mounting

base. UL/ULC listed.

B200S-WH:

 White, intelligent programmable sounder base, capable

of producing a variety of tone patterns including ANSI Temporal 3.
Compatible with synchronization protocol. See DN-60054. ULC:
B200SA-WH.

Содержание Notifier NFS-320SYS

Страница 1: ...detectors notification or relay wireless modules are available for use with the FWSG A Standard 80 character display Network options High speed network for up to 200 nodes N16e x NFS2 3030 NFS2 640 NFS 320 C NFS 320SYS NCD NCA 2 DVC EM ONYXWorks NFS 3030 NFS 640 and NCA Standard network for up to 103 nodes N16e x NFS2 3030 NFS2 640 NFS 320 C NFS 320SYS NCD NCA 2 DVC EM ONYXWorks NCS NFS 3030 NFS 6...

Страница 2: ...overlapping net work coverage RELEASING FEATURES Ten independent hazards Sophisticated cross zone three options Delay timer and Discharge timers adjustable Abort four options Low pressure CO2 listed VOICE FEATURES Integrates with FirstCommand Series See DN 60772 Telephone applications require NFC FFT HIGH EFFICIENCY OFFLINE SWITCHING 3 0 A POWER SUPPLY 6 0 A IN ALARM 120 VAC NFS 320 NFS 320C 240 V...

Страница 3: ...ls 1 Low Chamber value 2 Maintenance Alert indicative of dust accumulation that is near but below the allowed limit 3 Maintenance Urgent indicative of dust accumulation above the allowed limit Sensitivity Adjust Nine sensitivity levels are provided for alarm detection These levels can be set manually or can change automat ically between day and night Nine levels of pre alarm sensitivity can also b...

Страница 4: ...h speed Network Commu nications Modules Wire single mode fiber multi mode fiber and media conversion models are available See DN 60454 NCD As part of a standalone NFS 320SYS system the NCD can serve as Primary Display for the panel to provide control and status capabilities on displayless nodes On network systems the NCD connects to and requires a standard Network Communication Mod ule or High Spe...

Страница 5: ...gent 135 F fixed thermal sensor FlashScan and CLIP Must be mounted to one of the bases listed below ULC FST 951A IV FST 951R White low profile intelligent rate of rise thermal sensor FlashScan only Must be mounted to one of the bases listed below ULC FST 951A FSP 951R IV Ivory low profile intelligent photoelectric sensor remote test capable FlashScan only ULC FSP 95RA IV for use with DNRA FSV 951 ...

Страница 6: ... MB for systems using 100 AH batteries For a full list of required and optional equipment see DN 60688 NFS LBB Battery Box required for batteries larger than 26 AH NFS LBBR Same as above but red SEISKIT 320 B26 Seismic mounting kit Required for seismic certi fied applications with NFS 320 and BB 26 Includes battery bracket for two 26 AH batteries SEISKIT BB25 Seismic mounting kit for the BB 25 Inc...

Страница 7: ... the useful life of the system s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity Therefore it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 27 C 60 80 F AGENCY LISTINGS AND APPROVALS The listings and approvals below apply to the basic NFS 32SYS control pane...

Отзывы: