module. There are a variety of standoffs and hardware items avail-
able for different combinations and configurations of components.

Networking:

 If networking two or more control panels, each unit

requires a Network Communication Module or High-Speed Network
Communication Module (HS-NCM can support two nodes; see “Net-
working Options” on page 4). These modules can be installed in any
option board position (see manual), and additional option boards
can be mounted in front of them.

KDM-R2 Controls and Indicators

Program Keypad:

 QWERTY type (keyboard layout).

12 LED Indicators:

 Power; Fire Alarm; Pre-Alarm; Security; Super-

visory; System Trouble; Signals Silenced; Points Disabled; Control
Active; Abort; Pre-Discharge; Discharge.

Keypad Switch Controls:

 Acknowledge/Scroll Display; Signal

Silence; Drill; System Reset; Lamp Test.

LCD Display:

 80 characters (2 x 40) with long-life LED backlight.

Product Line Information

“Configuration Guidelines” on page 4

“Main System Components” on page 4

“Networking Options” on page 4

“Auxiliary Power Supplies and Batteries” on page 4

“Audio Options” on page 4

“Compatible Devices, EIA-232 Ports” on page 4

“Compatible Devices, EIA-485 Ports” on page 4

“Compatible Intelligent Devices” on page 5

“Enclosures, Chassis, and Dress Plates” on page 6

“Other Options” on page 6

C

ONFIGURATION

 G

UIDELINES

Stand-alone and network systems require a main display. On stand-
alone systems, the panel’s keypad provides the required display. On
network systems (two or more networked fire panel nodes), at least
one NCD, NCA-2/C, NCS, or ONYXWorks annunciation device is
required. (For NCA-2, see DN-7047. For NCD, see DN-60974.)

M

AIN

 S

YSTEM

 C

OMPONENTS

CPU-320SYS: 

FACP with integral 3.0 A (6.0 A in alarm) power supply

for an NFS-320SYS system. FACP is factory-mounted on a chassis
with one Signaling Line Circuit; includes 80-character display and doc-
umentation kit. 

Order one per system or as necessary on a network

system. (Non-English version also available: CPU-320SYS-FR.)

CPU-320SYSE: 

Same as CPU-320SYS but requires 220 VAC, 1.5 A,

(3.0 A in alarm).

CPU-320SYS-C: 

Same as CPU-320SYS for ULC applications.

NCA-2: 

Network Control Annunciator, 640 characters. On network

systems, the NCA-2 connects to (and requires) an NCM or HS-NCM
network communications module. Mounts in a row of FACP node or in
two annunciator positions. Non-English versions are available. For
ULC applications, order NCA-2C; for marine applications, order NCA-
2-M; for non-English Marine applications, order NCA-2-M and the
appropriate KP-KIT-XX. 

See DN-7047.

DP-DISP2: 

Dress panel for top row in cabinet with CPU-320SYS/E

installed.

BMP-1: 

Blank module for unused module positions.

BP2-4: 

Battery plate, required.

N

ETWORKING

 O

PTIONS

NCM-W, NCM-F: 

Standard Network Communications Modules. Wire

and multi-mode fiber versions available. 

See DN-6861. 

HS-NCM-W(-2), HS-NCM-MF, HS-NCM-SF, HS-NCM-WMF(-2),
HS-NCM-WSF(-2), HS-NCM-MFSF: 

High-speed Network Commu-

nications Modules. Wire, single-mode fiber, multi-mode fiber, and
media conversion models are available. 

See DN-60454. 

NCD: 

As part of a standalone NFS-320SYS system, the NCD can

serve as Primary Display for the panel, to provide control and status
capabilities on displayless nodes. On network systems, the NCD
connects to (and requires) a standard Network Communication Mod-
ule or High-Speed Network Communication Module. Mounting
options include the ABS-TD for standalone applications. In the
CAB-4 series the NCD can be mounted in the top row with a
DP-GDIS1 or lower rows using a DP-GDIS2. 

See DN-60974.

RPT-W, RPT-F, RPT-WF: 

Standard-network repeater board with wire

connection (RPT-W), multi-mode fiber connection (RPT-F), or allow-
ing a change in media type between wire and fiber (RPT-WF). Not
used with high-speed networks. 

See DN-6971. 

ONYXWorks: 

UL/ULC-listed graphics PC workstation, software, and

computer hardware. 

See DN-7048 for specific part numbers.

NFN-GW-EM-3: 

NFN Gateway, embedded. 

See DN-60499. 

NWS-3:

 

NOTI•FIRE•NET™ 

Web Server. 

See DN-6928.

CAP-GW:

 Common Alerting Protocol Gateway. 

See DN-60756. 

VESDA-HLI-GW:

 VESDAnet high-level interface gateway. 

See DN-

60753.

 

LEDSIGN-GW:

 UL-listed sign gateway. Interfaces with classic and

high-speed NOTI•FIRE•NET networks through the NFN Gateway.

See DN-60679. 

OAX2-24V: 

UL-listed LED sign, used with LEDSIGN-GW. 

See DN-

60679. 

A

UXILIARY

 P

OWER

 S

UPPLIES

 

AND

 B

ATTERIES

ACPS-610: 

6.0 A or 10.0 A addressable charging power supply. 

See

DN-60244. 

APS2-6R: 

Auxiliary Power Supply. Provides up to 6.0 amperes of

power for peripheral devices. Includes battery input and transfer
relay, and overcurrent protection. Mounts on two of four positions on
a CHS-4L or CHS-4 chassis. 

See DN-5952. 

FCPS-24S6/S8: 

Remote 6 A and 8 A power supplies with battery

charger. See 

DN-6927. 

BAT Series: 

Batteries. NFS-320SYS uses two 12 volt, 18 to 200 AH

batteries. 

See DN-6933. 

A

UDIO

 O

PTIONS

NFC-50/100:

 25 watt, 25 VRMS, emergency Voice Evacuation Con-

trol Panel (VECP) with integral commercial microphone, digital mes-
sage generator, and Class A or Class B speaker circuits. 

See DN-

60772. 

C

OMPATIBLE

 D

EVICES

, EIA-232 P

ORTS

PRN-7: 

80-column printer. See 

DN-60897. 

VS4095/5: 

Printer, 40-column, 24 V. Mounted in external backbox.

See DN-3260. 

DPI-232: 

Direct Panel Interface, specialized modem for extending

serial data links to remotely located FACPs and/or peripherals;
mount on NFS-320 chassis. 

See DN-6870. 

C

OMPATIBLE

 D

EVICES

, EIA-485 P

ORTS

ACM-24AT: 

ONYX Series ACS annunciator – 24 points, expandable

to 64 of annunciation with Alarm or Active LED, Trouble LED, and
switch per circuit. Active/Alarm LEDs can be programmed (by pow-
ered-up switch selection) by point to be red, green, or yellow; the
Trouble LED is always yellow. 

See DN-6862.

AEM-24AT: 

Same LED and switch capabilities as ACM-24AT,

expands the ACM-24AT to 48, 72, or 96 points. 

See DN-6862.

ACM-48A: 

ONYX Series ACS annunciator – 48 points, expandable

to 64 of annunciation with Alarm or Active LED per circuit. Active/
Alarm LEDs can be programmed (by powered-up switch selection)
in groups of 24 to be red, green, or yellow. 

See DN-6862.

Содержание Notifier NFS-320SYS

Страница 1: ...detectors notification or relay wireless modules are available for use with the FWSG A Standard 80 character display Network options High speed network for up to 200 nodes N16e x NFS2 3030 NFS2 640 NFS 320 C NFS 320SYS NCD NCA 2 DVC EM ONYXWorks NFS 3030 NFS 640 and NCA Standard network for up to 103 nodes N16e x NFS2 3030 NFS2 640 NFS 320 C NFS 320SYS NCD NCA 2 DVC EM ONYXWorks NCS NFS 3030 NFS 6...

Страница 2: ...overlapping net work coverage RELEASING FEATURES Ten independent hazards Sophisticated cross zone three options Delay timer and Discharge timers adjustable Abort four options Low pressure CO2 listed VOICE FEATURES Integrates with FirstCommand Series See DN 60772 Telephone applications require NFC FFT HIGH EFFICIENCY OFFLINE SWITCHING 3 0 A POWER SUPPLY 6 0 A IN ALARM 120 VAC NFS 320 NFS 320C 240 V...

Страница 3: ...ls 1 Low Chamber value 2 Maintenance Alert indicative of dust accumulation that is near but below the allowed limit 3 Maintenance Urgent indicative of dust accumulation above the allowed limit Sensitivity Adjust Nine sensitivity levels are provided for alarm detection These levels can be set manually or can change automat ically between day and night Nine levels of pre alarm sensitivity can also b...

Страница 4: ...h speed Network Commu nications Modules Wire single mode fiber multi mode fiber and media conversion models are available See DN 60454 NCD As part of a standalone NFS 320SYS system the NCD can serve as Primary Display for the panel to provide control and status capabilities on displayless nodes On network systems the NCD connects to and requires a standard Network Communication Mod ule or High Spe...

Страница 5: ...gent 135 F fixed thermal sensor FlashScan and CLIP Must be mounted to one of the bases listed below ULC FST 951A IV FST 951R White low profile intelligent rate of rise thermal sensor FlashScan only Must be mounted to one of the bases listed below ULC FST 951A FSP 951R IV Ivory low profile intelligent photoelectric sensor remote test capable FlashScan only ULC FSP 95RA IV for use with DNRA FSV 951 ...

Страница 6: ... MB for systems using 100 AH batteries For a full list of required and optional equipment see DN 60688 NFS LBB Battery Box required for batteries larger than 26 AH NFS LBBR Same as above but red SEISKIT 320 B26 Seismic mounting kit Required for seismic certi fied applications with NFS 320 and BB 26 Includes battery bracket for two 26 AH batteries SEISKIT BB25 Seismic mounting kit for the BB 25 Inc...

Страница 7: ... the useful life of the system s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity Therefore it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 27 C 60 80 F AGENCY LISTINGS AND APPROVALS The listings and approvals below apply to the basic NFS 32SYS control pane...

Отзывы: