Honeywell Notifier NFS-320SYS Скачать руководство пользователя страница 3

DN-60637:N • 9/15/2022 — Page 3 of 7

          

Optional addressable sounder base for Temp-3 (fire) or Temp-4
(CO) tone.

Automatic drift compensation of smoke sensor and CO cell.

High nuisance-alarm immunity.

ULC listed models available; -A models are ULC Listed.

FPTI-951(A) I

NTELLIGENT

 M

ULTI

-C

RITERIA

 D

ETECTOR

Combined photoelectric, thermal, and infrared sensor

UL 268 7th Edition and UL 521 Listed; Canadian models CAN/
ULC S529 and CAN/ULC S530 

Microprocessor-based technology; combination photo, thermal,
and infrared technology.

FPC-951(A) P

HOTOELECTRIC

/CO S

ENSOR

Combined photoelectric and carbon monoxide sensor 

FSCO-951 I

NTELLIGENT

 CO S

ENSOR

Carbon monoxide sensor 

FS-OSI-RI(A) A

DDRESSABLE

 

INTELLIGENT

 

SINGLE

-

ENDED

 

BEAM

SMOKE

 

DETECTOR

Intelligent addressable reflector-type linear optical beam smoke
detector

Fast, easy, and intuitive beam alignment indicated by directional
LED arrows

Long range coverage of 16-328 ft (5-100 m) is standard; no sepa-
rate long-range kit required

I

NTELLIGENT

 VESDA-E D

ETECTORS

 

Intelligent aspiration smoke detectors connect directly to the SLC
loop of compatible ONYX® Series panels: 

VEA-040-A00-NTF, VEA-040-A10-NTF 

VEP-A00-P-NTF, VEP-A10-P-NTF, VEP-A00-1P-NTF

VEU-A00-NTF, VEU-A10-NTF

VES-A00-P-NTF-UL, VES-A10-P-NTF-UL

Models offer LED display, LCD display, or both

Coverage options for spaces up to 69,965 square feet

FlashScan, Exclusive 
World-Leading Detector Protocol

At the heart of the NFS-320SYS is a set of detection devices and
device protocol — FlashScan (U.S. Patent 5,539,389). FlashScan is
an all-digital protocol that gives superior precision and high noise
immunity.

In addition to providing quick identification of an active input device,
this protocol can also activate many output devices in a fraction of
the time required by competitive protocols. This high speed also
allows the NFS-320SYS to have the largest device per loop capacity
in the industry — 318 points — yet every input and output device is
sampled in less than two seconds. The microprocessor-based
FlashScan detectors have bicolor LEDs that can be coded to provide
diagnostic information, such as device address during Walk Test.

ONYX Intelligent Sensing

Intelligent sensing is a set of software algorithms that provides the
NFS-320SYS with industry-leading smoke detection capability.
These complex algorithms require many calculations on each read-
ing of each detector, and are made possible by the high-speed
microcomputer used by the NFS-320SYS.

Drift Compensation and Smoothing: 

Drift compensation allows

the detector to retain its original ability to detect actual smoke, and
resist false alarms, even as dirt accumulates. It reduces mainte-
nance requirements by allowing the system to automatically perform
the periodic sensitivity measurements required by NFPA 72.

Smoothing filters are also provided by software to remove transient
noise signals, such as those caused by electrical interference.

Maintenance Warnings: 

When the drift compensation performed

for a detector reaches a certain level, the performance of the detec-
tor may be compromised, and special warnings are given. There are
three warning levels: (1) Low Chamber value; (2) Maintenance Alert,
indicative of dust accumulation that is near but below the allowed
limit; (3) Maintenance Urgent, indicative of dust accumulation above
the allowed limit.

Sensitivity Adjust: 

Nine sensitivity levels are provided for alarm

detection. These levels can be set manually, or can change automat-
ically between day and night. Nine levels of pre-alarm sensitivity can
also be selected, based on predetermined levels of alarm. Pre-alarm
operation can be latching or self-restoring, and can be used to acti-
vate special control functions.

Self-Optimizing Pre-Alarm: 

Each detector may be set for “Self-

Optimizing” pre-alarm. In this special mode, the detector “learns” its
normal environment, measuring the peak analog readings over a
long period of time, and setting the pre-alarm level just above these
normal peaks.

Cooperating Multi-Detector Sensing: 

A patented feature of ONYX

intelligent sensing is the ability of a smoke sensor to consider read-
ings from nearby sensors in making alarm or pre-alarm decisions.
Without statistical sacrifice in the ability to resist false alarms, it
allows a sensor to increase its sensitivity to actual smoke by a factor
of almost two to one.

Field Programming Options

Autoprogram

 is a timesaving feature. The FACP “learns” what

devices are physically connected and automatically loads them in
the program with default values for all parameters. Requiring less
than one minute to run, this routine allows the user to have almost
immediate fire protection in a new installation, even if only a portion
of the detectors are installed.

Keypad Program Edit (with KDM-R2) 

The NFS-320SYS, like all

NOTIFIER intelligent panels, has the exclusive feature of program
creation and editing capability from the front panel keypad, while
continuing to provide fire protection. The architecture of the NFS-
320SYS software is such that each point entry carries its own pro-
gram, including control-by-event links to other points. This allows the
program to be entered with independent per-point segments, while
the NFS-320SYS simultaneously monitors other (already installed)
points for alarm conditions.

VeriFire

®

 Tools

 is an offline programming and test utility that can

greatly reduce installation programming time, and increase confi-
dence in the site-specific software. It is Windows

®

-based and pro-

vides technologically advanced capabilities to aid the installer. The
installer may create the entire program for the NFS-320SYS in the
comfort of the office, test it, store a backup file, then bring it to the
site and download from a laptop into the panel.

Placement of Equipment 
in Chassis and Cabinet

The following guidelines outline the NFS-320SYS’s flexible system
design.

Rows:

 The first row of equipment in the cabinet mounts in the chas-

sis shipped with the FACP. Mount the second, third, or fourth rows of
equipment in a CHS-4 Series chassis. Other options are available;
see your panel’s installation manual. 

Wiring:

 When designing the cabinet layout, consider separation of

power-limited and non-power-limited wiring as discussed in the
NFS-320SYS Installation Manual.

Positions:

 A chassis offers four basic side-by-side positions for

components; the number of modules that can be mounted in each
position depends on the chassis model and the size of the individual

Содержание Notifier NFS-320SYS

Страница 1: ...detectors notification or relay wireless modules are available for use with the FWSG A Standard 80 character display Network options High speed network for up to 200 nodes N16e x NFS2 3030 NFS2 640 NFS 320 C NFS 320SYS NCD NCA 2 DVC EM ONYXWorks NFS 3030 NFS 640 and NCA Standard network for up to 103 nodes N16e x NFS2 3030 NFS2 640 NFS 320 C NFS 320SYS NCD NCA 2 DVC EM ONYXWorks NCS NFS 3030 NFS 6...

Страница 2: ...overlapping net work coverage RELEASING FEATURES Ten independent hazards Sophisticated cross zone three options Delay timer and Discharge timers adjustable Abort four options Low pressure CO2 listed VOICE FEATURES Integrates with FirstCommand Series See DN 60772 Telephone applications require NFC FFT HIGH EFFICIENCY OFFLINE SWITCHING 3 0 A POWER SUPPLY 6 0 A IN ALARM 120 VAC NFS 320 NFS 320C 240 V...

Страница 3: ...ls 1 Low Chamber value 2 Maintenance Alert indicative of dust accumulation that is near but below the allowed limit 3 Maintenance Urgent indicative of dust accumulation above the allowed limit Sensitivity Adjust Nine sensitivity levels are provided for alarm detection These levels can be set manually or can change automat ically between day and night Nine levels of pre alarm sensitivity can also b...

Страница 4: ...h speed Network Commu nications Modules Wire single mode fiber multi mode fiber and media conversion models are available See DN 60454 NCD As part of a standalone NFS 320SYS system the NCD can serve as Primary Display for the panel to provide control and status capabilities on displayless nodes On network systems the NCD connects to and requires a standard Network Communication Mod ule or High Spe...

Страница 5: ...gent 135 F fixed thermal sensor FlashScan and CLIP Must be mounted to one of the bases listed below ULC FST 951A IV FST 951R White low profile intelligent rate of rise thermal sensor FlashScan only Must be mounted to one of the bases listed below ULC FST 951A FSP 951R IV Ivory low profile intelligent photoelectric sensor remote test capable FlashScan only ULC FSP 95RA IV for use with DNRA FSV 951 ...

Страница 6: ... MB for systems using 100 AH batteries For a full list of required and optional equipment see DN 60688 NFS LBB Battery Box required for batteries larger than 26 AH NFS LBBR Same as above but red SEISKIT 320 B26 Seismic mounting kit Required for seismic certi fied applications with NFS 320 and BB 26 Includes battery bracket for two 26 AH batteries SEISKIT BB25 Seismic mounting kit for the BB 25 Inc...

Страница 7: ... the useful life of the system s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity Therefore it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 27 C 60 80 F AGENCY LISTINGS AND APPROVALS The listings and approvals below apply to the basic NFS 32SYS control pane...

Отзывы: