background image

 

LCD6000A 

Installing manual 

PAGINA - 3 

LCD6000A_manu-inst 

Doc. M-185.1- LCD6000A-ENG Rev A.1 

NOTIFIER ITALIA 

FUNCTIONS 

 

LCD-6000A 

can execute the following functions: 

 

 Local 

ACK 

 Lamp 

test 

 Buzzer 

test 

 Peripheral 

address 

programming 

 

FUNCTIONING

 

Needs local programming to assign peripheral address. 

LCD-6000A

 shows time, date and events previously 

programmed, that come from AM series control panels. 

 

Technical features

 

 

Microprocessor based system 

 

LCD graphic 320 x 240 pixel display 

 

Keyboard with dedicated keys for special functions: Buzzer silencing, Reset, Lamp Test. 

 

 

Serial lines

- 2 RS-485 interfaces 

 

 

Power supply

 

 10 ÷ 30Vdc  

 

 

Connections

 

- 2 power cables 
- 2 cables for serial line connection (3 wires if power supplies are not in common) with control panel 
 

 

Mechanics

 

LCD-6000 mechanical features are suitable for wall-mounting 
Dimensions: 180 (W) x 168 (H) x 55 (D) mm 
Protection grade: IP20 
Operating temperature: -5°C to +40°C 

 

Содержание NOTIFIER LCD6000A

Страница 1: ...LCD6000A Remote Panel Installing Manual ...

Страница 2: ...CTIONS 3 INSTALLATION 4 FRONT PANEL CONTROLS 5 USER INTERFACE DESCRIPTION 6 Normal condition 6 Alarm zone events condition 7 Condition with zone events fault 8 Condition with excluded zone events 8 PROGRAMMING MENU 10 SERIAL LINE RS485 11 SHIELDED CABLE AND GROUNDING 12 LDC 6000A BOARD TOPOGRAPHIC 12 CN1 TERMINAL BOARD 13 ELECTRICAL FEATURES 13 POWER SUPPLY 13 ...

Страница 3: ...ed by NOTIFIER as compatible with its control panels In case of doubt check with NOTIFIER technical assistance This system and all its solid state components can be damaged by induced electrostatic discharges handle the boards picking them on borders and avoid to touch electronic components A good grounding connection ensures noise sensitivity reduction Consult Technical Service NOTIFIER if you ar...

Страница 4: ... Sensors Zones Zones exclusion LCD 6000A can be configured ONLY with AM series control panels Upload software LCD 6000A can be programmed in Master configuration to repeat through its auxiliary serial line pin 7 and 8 its events towards other 4 LCD 6000A devices Slave that show a copy of the same events see the picture Summary tables that describe the maximum number of LCD devices that can be inst...

Страница 5: ...that come from AM series control panels Technical features Microprocessor based system LCD graphic 320 x 240 pixel display Keyboard with dedicated keys for special functions Buzzer silencing Reset Lamp Test Serial lines 2 RS 485 interfaces Power supply 10 30Vdc Connections 2 power cables 2 cables for serial line connection 3 wires if power supplies are not in common with control panel Mechanics LC...

Страница 6: ...heating sources radiators etc The panel is designed to be wall mounted through 4 self blocking nogs stone walls or self tapping screws pre built panels etc Screws diameter must be 5mm max We advice not to install the panel near heating sources radiators etc Fixing screws 5mm max Fix the incoming cable with a bend Plug in the cable into CN1 Fixing screws for front panel are in the lower part ...

Страница 7: ...esent and it s not been acknowledged Remains fixed if all faults have been acknowledged SILENCING Yellow Enabled if buzzer silencing key has previously been pressed PROGRAMMING BUZZER SILENCING Pressing this key results in LCD6000A buzzer silencing Buzzer Test pressing this key will enable Buzzer for a few seconds LAMP TEST pressing this key lamp test function is launched all led blink for a few s...

Страница 8: ...only if LCD 6000A is configured for their visualization Date Time Alarm zones counter Fault zones counter RS485 serial connection status In case of trouble on serial connection OFF LINE signal is shown Serial connection system signalling icon In case of trouble on serial connection the following icon is shown User programmable label max 32 characters System fault signalling icon it s shown only wh...

Страница 9: ...fic zone alarmed devices you must scroll down the list until the chosen one is in first event visualization area Pressing key you can enter the list of alarmed points in the selected zone With the arrow keys you can scroll down the list of alarmed devices Alarm zones counter date and time of the first alarm event First zone in alarm Label programmed for the zone Last zone in alarm Label programmed...

Страница 10: ... list until the chosen one is in first event visualization area Pressing key you can enter the list of faulted points of the selected zone With the arrow keys you can scroll down the list of devices in fault condition Condition with excluded zone events The following screen is shown when in the control panel excluded zones are present and it s programmed to show exclusion signalling on LCD 6000A F...

Страница 11: ...ization you need to Press key to enter the main menu Use the arrow keys to select Exclusion voice and press Lists key to confirm selection In this window the number of excluded zones is shown Press Lists key to show excluded zones list in detail With the arrow keys you can scroll the list of excluded zones Press the key to get back to main menu ...

Страница 12: ...configuration and modify programming The following menu is shown Where Address Select Address voice to assign peripheral number to LCD 6000A terminal device Use the arrow keys to select peripheral s number and press Lists key to confirm data Useful addresses that can be assigned to LCD 6000A are described in the table on page 2 Use the arrow keys to select the function you want to modify and press...

Страница 13: ... configuration daisy chain Each peripheral must be programmed with an address Refer to each peripheral s installing manual INSTALLING Connect two wires between RS 485 pins on the control panel LIN and LIN pins to the corresponding pins of the first device on the line Complete cabling from the first device to the second and so on Install End Of Line resistor 120 150 0 5W both on control panel s pin...

Страница 14: ... be connected ONLY to the control panel s end Leave the other end not connected and insulated A B Schermo collegare assieme le due calze dei cavi A B Schermo Connettere al telaio con un anello M5 e vite Utilizzare la posizione sul telaio più vicina al connettore Tipico collegamento dell ultima periferica Tipico collegamento alla centrale RS 485 shielding and grounding LDC 6000A board topographic L...

Страница 15: ...485 serial line 4 GND Reference negative for RS 485 serial line 3 LIN RS 485 serial line 2 GND Power input 1 24Vcc ELECTRICAL FEATURES Operating temperature 5 C 40 C Relative humidity without condensate 10 93 Stocking temperature 10 C 50 C Weight Kg 0 54 POWER SUPPLY Operating voltage 10 30Vdc Current absorption without anomalies faults or alarms with display off 30 mA Current absorption with anom...

Страница 16: ...55 696706 Fax 055 6529294 00118 Roma Via Del Casale Santarelli 51 Tel 06 7988021 Fax 06 79880250 E mail notifier roma notifier it 80143 Napoli Via G Porzio 4 Centro Direzionale Isola E2 Scala B Piano 5 int 19 Tel 081 7879398 Fax 081 7879159 E mail notifier napoli notifier it 70125 Bari Via Della Costituente 29 Tel 080 5013247 Fax 080 5648114 E mail notifier bari notifier it 95126 Catania Via Alcid...