Shielded cable and grounding
During installing you need to consider
consequences of remote
grounding.
When you connect RS-485 devices, if a
ground cable (drain) is available,
this MUST NOT be connected at
both the ends to devices’ chassis.
Grounding cable must be connected
ONLY to the control panel’s end.
Leave the other end not connected
and insulated.
A
B
Schermo:
collegare
assieme le due
calze dei cavi
A
B
Schermo:
Connettere al
telaio con un
anello M5 e vite
Utilizzare la
posizione sul
telaio più vicina al
connettore
Tipico collegamento
dell’ultima periferica
Tipico collegamento alla
centrale
RS-485 shielding and grounding
LDC-6000A board topographic
Linking cables technical data
Up to 1.200 m
18 AWG
Belden 9574
Up to 1.500 m
16 AWG
Belden 9575
CN1 terminal board
CNT connector for front keyboard