Pag. 52
Programming Manual
SERIEAM
NOTIFIER ITALIA
Doc. M-160.2-AM-8000-ENG Rev A1
AM8000_manu-prog-ENG
SDEL
The “SEDEL” operator is equal to the “DEL” operator, with the difference that, if during the delay time the
equation is not true any longer, the timer continues to count and then it activates the output device.
To re-set this timer perform an alarm or Fault reset.
TIM
is the operator that allows to program output activations at periodic time intervals.
There can be two formats :
FORMAT Type 1 : TIM (SU MO TU WE TR FR SA 00.MM 00.MM)
Where : 00 = hours, MM = minutes
This format allows to perform programmings weekly, for specific days of the week
FORMAT Type 2 : TIM (MM GG AA OO.MM OO.MM)
Where : MM = month, GG = day, AA =year
This format allows to perform programmings yearly
Example: IF
the
G90
software group equation is :
TIM (SA SU 07.30 13.59)
THEN
the
G90
group will be active on
Saturday
and
Sunday
from
07.30
a.m. to
13.59
.
N.B.:
If the day, month or year is not specified, the value assumes the meaning of “All days”.
To not specify anything enter two signs “
“ refer to the following example:
TIM
(
07.30 13.59)
The start time and end time values, use the 24 hour format (midnight = 00.00 ... 23.59)
The value “00.MM” of end time MUST be higher than the value of the start time.
The maximum value for start time and end time is 23:59
activation days
(optional)
start time
end time
Enter a
space character
Enter a
space character
Activation date
(optional)
start time
end time
Enter a space
character
Enter a space
character