OUTPUT MODULES
ABBREVIATION
TYPE OF DEVICE
CON
Output module with supervision of the device connection line
FORC
Output module with relay contacts free from voltage
OUTPUT MODULES FOR GENERAL SIGNALLINGS
ABBREVIATION
TYPE OF DEVICE
PWRC
FORC Output module used to temporarily interrupt power supply, during SYSTEM RESET, for the 4-
wire conventional smoke sensors, powered by a remote power supply.
N.B.: this type SHALL NOT be programmed for the SILENCING
GPND
FORC output module activated at each alarm or Fault
It is reset by ACK.
APND
FORC output module activated at each alarm. It is reset by ACK.
GAC
FORC output module activated at each alarm. It is reset by RESET.
GAS
FORC output module activated at each alarm. It is reset by RESET.
TPND
FORC output module activated at each breakdown. It is reset by ACK or through the Faultelimination
GTC
FORC output module activated at each breakdown. It is reset by RESET.
GTS
CON output module activated at each breakdown. It is reset by RESET.
TRS
FORC output module activated at each breakdown. It is only reset through the Fault elimination.
HORN
Output module activated at each alarm and follows the output state of the control unit Siren
ZDIS
Output module activated in case of exclusion of a point or a zone.
MAINF
Output module (non supervised output) activated when a MAINS Fault is present
MAINFC
Same as MAINF but supervised output
MAINFV
Same as MAINF but supervised output ( complies VDC standard )
N.B.: the output modules used for the above-mentioned functions, do not accept CBE.