Pag. 24
Programming Manual
SERIEAM
NOTIFIER ITALIA
Doc. M-160.2-AM-8000-ENG Rev A1
AM8000_manu-prog-ENG
Where:
The
PROT ( Protocol )
control
can display the table of devices for one of the two possible protocols: CLIP or ADV
TYPE
=
Type of devices found ( see table above)
NEW
= N
ew device found
NFO
= Devices previously programmed but not coherent with what was detected during the Auto-Learn
procedure
TOT
= total of devices detected on the line ( NEW + INC + correctly programmed devices.)
MAN
= Devices previously programmed but not detected during the Auto-Learn
The
CONF
control saves the devices detected during the Self-Learn according to the following mode:
-
NEW and INC
are initialised through the default data.
-
MAN
are removed
-
The correctly programmed devices keep the current programming
The data relevant to the initialized devices can be subsequently changed by entering the point programming
procedure.
Auto-Learn
Summary
Type
NEW
NFO
TOT
MIS
PHOT
000 000 002 000
THER
000 000 005 000
CMA1
000 000 004 000
MMA1
000 000 005 000
Sample screen for CLIP detectors.
Important Note :
On Each Line can be installed
a max number of 10 device using CLIP protocol.