MU1H-1546GE23 R0908
18
Honeywell GmbH
GB
14. Determination of the maximum capacity of the softening cartridge
14.1GERMANY: Requirements according to VDI 2035 page 1
14.2AUSTRIA: Requirements according to ÖNORM H 5195-1
The determination of the maximum capacity of the softening cartridge (tables A and B) is carried out in accor-
dance with VDI (Verein Deutscher Ingenieure - Society of German Engineers) in relation to the overall
heating power.
Overall heating
power
Specific system volume (system volume/smallest individual heating power)
0 to less than 20 litres/kW 20 to less than 50 litres/kW as of 50 and more litres/kW
0 to 50 kW
Reference value:
Softening to less than 16,8°*
Recommendation:
Softening to less than 8.4°
⇒
See table A
Minimum requirement:
Softening to less than 11.2°
Recommendation:
Softening to less than 8.4°
⇒
See table A
Minimum requirement:
Softening to less than 0.11°
⇒
See table B
50 to 200 kW
Minimum requirement:
Softening to less than 11.2°
Recommendation:
Softening to less than 8.4°
⇒
See table A
Minimum requirement:
Softening to less than 8.4°
⇒
See table A
Minimum requirement:
Softening to less than 0.11°
⇒
See table B
200 to 600 kW
Minimum requirement:
Softening to less than 8.4°
⇒
See table A
Minimum requirement:
Softening to less than 0.11°
⇒
See table B
Minimum requirement:
Softening to less than 0.11°
⇒
See table B
more than 600 kW
Minimum requirement:
Softening to less than 0.11°
⇒
See table B
Minimum requirement:
Softening to less than 0.11°
⇒
See table B
Minimum requirement:
Softening to less than 0.11°
⇒
See table B
* For equipment with circulating water heaters and for systems with electrical heating elements, the equated refe-
rence value for the sum of alkaline earth metals
≥
3.0mol/m
³
, equivelent to 16.8 °dH.
The determination of the maximum capacity of the softening cartridge (tables C and D) is carried out in accor-
dance with the Önorm (Österreichisches Normungsinstitut - Austrian standardisation institute) in relation to
the overall water content of the entire heating system.
Overall water content of the entire heating system
0 to 1000 litres
1000 to 5000 litres
Over 5000 litres
Minimum requirement:
Softening to less than 17°
Recommendation:
Softening to less than 6°
⇒
See table C
Minimum requirement:
Softening to less than 6°
⇒
See table C
Minimum requirement:
Softening to less than 0.5°
⇒
See table D