OPERATION

The actuator is designed to be used in ventilating and air 
conditioning installations to operate valves, dampers, 
ventilation flaps and louvers requiring torque up to the 
rating. (For ratings, see the Specifications section.) If the 
power fails, the actuator will spring return to the start 
position.

The actuator is operated by a proportional controller. When 
using a proportional controller, the actuator drives toward 
its fully open position when the input signal increases; the 
actuator drives toward the fully closed position when the 
input signal decreases. The actuator stops when the input 
signal reaches the desired proportional control point.

IMPORTANT

The actuator is designed to respond to DDC 
Controller instantaneous contact closures. Take 
care not to short cycle the actuator. Unstable 
damper control can cause premature actuator fail-
ure.

Actuator Override

To override the control signal (for freeze protection or 
similar applications):

1.

Override to full open:
a. Disconnect the input signal (from terminal 3).
b. Apply 24 Vac to terminal 3.
c. See Fig. 32.

2.

Override to full closed:
a. Disconnect the input signal (from terminal 3).
b. See Fig. 33.

Fig. 32. Override to full open.

Fig. 33. Override to full close.

End Switches

Some models include end switches (see Table 2). For wiring 
details, see Fig. 12.

SPDT Switches (Fig. 34)

For SPDT end switch wiring, see Fig. 12.

Fig. 34. SPDT End Switch Operation.

ACTUATOR

0/2 TO 10 VDC
PROPORTIONING
CONTROLLER

24 VAC

1

1

2

3

2

LINE VOLTAGE POWER SUPPLY. 
PROVIDE DISCONNECT MEANS AND 
OVERLOAD PROTECTION AS REQUIRED.

24 VDC SUPPLY ACCEPTABLE.

SET SWITCH TO MODULATING.

V

OR +

OR N/A

FEEDBACK

+

FEEDBACK

5

4

3

1

2

M19576A

2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev

3

SPDT

ACTUATOR

0/2 TO 10 VDC
PROPORTIONING
CONTROLLER

24 VAC

1

1

2

3

2

LINE VOLTAGE POWER SUPPLY. 
PROVIDE DISCONNECT MEANS AND 
OVERLOAD PROTECTION AS REQUIRED.

24 VDC SUPPLY ACCEPTABLE.

SET SWITCH TO MODULATING.

V

OR +

OR N/A

FEEDBACK

+

FEEDBACK

5

4

3

1

2

M19577A

2-10 VDC
10-2 VDC
0-10 VDC
10-0 VDC
Fltg, fwd
Fltg, rev

3

SPST

M19578

95

SWITCH CONNECTIONS

ACTUATOR POSITION

85

7

3

0

S4

S1

S6

S5

S3

S2

CONTACT OPEN

CONTACT MADE

+

-

3

+

-

Содержание MS 10 Series

Страница 1: ...age valves mounted with linkages to provide linear actuation FEATURES Brushless DC submotor with electronic stall protection for floating modulating models Floating Modulating models can provide two position SPST control Brush DC submotor with electronic stall protection for two position models Self centering shaft adapter shaft coupling for wide range of shaft sizes Access cover to facilitate con...

Страница 2: ...r greater shaft diameter recommended Minimum Damper Shaft Length 1 in 25 mm 3 in 76 mm recommended Cable Specification 300 V 75 C Plenum Rated 3 ft length from end of access cover 18 AWG Table 1 Features Model Number Model Number including 3 ft whip Torque Power Supply Drive2 sec Control Input Output Description SPDT Aux Switch Voltage VA Driving1 MS7510A2008 MS7510W2008 88 lb in 10 Nm 24 Vac dc 1...

Страница 3: ... available on 75 and 81 Series only M Electrical Motor S Fail Safe Function Spring Return 31 24 Vac communicating Sylk Enabled 41 120 Vac Two Position Control Reversible Mount 71 24 Vac Modulating Control Reversible Mount 75 24 Vac Modulating and Floating Control Reversible Mount 81 24 Vac Two Position Control Reversible Mount 10 88 lb in 10 Nm 20 175 lb in 20 Nm Aa Standard U S Model Bb Standard ...

Страница 4: ...ctuator 50001194 001 Foot Mount Kit 50005859 001 NEMA4 4X Enclosure 50006427 001 Anti Rotation Bracket supplied with actu ator SW2 US Auxiliary Switch Package See also Form 63 2620 Sylk Bus Sylk is a two wire polarity insensitive bus that provides communications between a Sylk enabled actuator and a Sylk enabled controller For wiring the Sylk enabled actuator may be mounted up to 200 ft 61m from t...

Страница 5: ...can damage actuator Mount actuator to allow it to float along its vertical axis Preparation Before mounting the actuator onto the damper shaft determine the Damper valve opening direction for correct spring return rotation The actuator can be mounted to provide clockwise or counterclockwise spring return Damper shaft size see the Specifications section Determine Appropriate Mounting Orientation Th...

Страница 6: ... the control signal Non Standard Stroke Mechanical Stroke Limit Reduction For applications requiring a span less than 95 degrees a simple adjustment can be made When the rotational mounting of the shaft coupling is changed the actuator drives less than the full 95 degrees stroke The stroke is adjustable in 5 degree increments Once adjusted the actuator drives until the shaft coupling reaches the m...

Страница 7: ... end point signal 7 Allow the actuator to open fully 8 Slowly adjust span toward the maximum setting until the actuator hub moves slightly from fully open 9 Carefully adjust span knob toward minimum until the actuator hub returns to fully open Auto Adapt When using these actuators for standard stroke applications this function can be ignored When it is desirable to use a mechanically limited strok...

Страница 8: ...elf tapping sheet metal screws 5 Turn damper blades to desired normal closed posi tion 6 Place actuator and mounting bracket back into posi tion and secure bracket to damper box with sheet metal screws 7 Using 10 mm wrench tighten shaft coupling securely onto damper shaft using minimum 120 lb in 13 6 Nm maximum 180 lb in 20 3 Nm torque NOTE See Fig 8 for proper mounting to a square damper shaft Fi...

Страница 9: ...e cover set the screw aside 2 Pull the cover along the long axis of the actuator 3 If the actuator is not yet mounted set it aside 4 Remove conduit dust covers as necessary 5 Thread wire through conduit holes 6 Connect wires as appropriate to the terminal block s See Fig 11 and 12 NOTE With US Models use 1 2 in NPS strain relief gland or 1 2 in conduit adapters Recom mend using flex conduit With E...

Страница 10: ...oating Modulating Two Position Colora 24 Vac 120 Vac 240 Vac Sylk enabled 1 power power power power power Red 2 common common common neutral common Black 3 cw input s bus White 4 ccw s bus 5 feedback feedback Brown ACTUATOR SPST 24 VAC 1 1 2 2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE ENSURE PROPER GROUNDING OF ACTUATOR CASE V 1...

Страница 11: ...Fltg fwd Fltg rev 3 4 ENSURE PROPER GROUNDING OF ACTUATOR CASE 4 NOTES AFTER TRANSFORMER SELV SAFETY EXTRA LOW VOLTAGE FOR INTERNAL CIRCUIT AND MOTOR 5 A JUMPER WIRE IS NOT REQUIRED BETWEEN PIN 1 AND PIN 3 IF SWITCH IS SET TO 10 2 VDC 5 24 VAC 1 1 2 3 2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE SET SWITCH TO FLOATING M35125 ACTU...

Страница 12: ...2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 2 3 ENSURE PROPER GROUNDING OF ACTUATOR CASE 3 NOTES AFTER TRANSFORMER SELV SAFETY EXTRA LOW VOLTAGE FOR INTERNAL CIRCUIT AND MOTOR ACTUATOR CONTROLLER 24 VAC 1 1 2 LINE VOLTAGE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED SET SWITCH TO FLOATING V OR OR N A FEEDBACK HOT COM 5 4 3 1 2 M35128 24 VAC 1 2 10 VDC 10 2 VDC 0 10 VDC 1...

Страница 13: ...ITCH TO MODULATING LOCATE RESISTOR AT THE LAST ACTUATOR V OR OR N A FEEDBACK FEEDBACK 5 4 3 1 2 M35098 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 ACTUATOR V OR OR N A FEEDBACK 5 4 3 1 2 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 500 OHMS 5 ENSURE PROPER GROUNDING OF ACTUATOR CASE 5 NOTES AFTER TRANSFORMER SELV SAFETY EXTRA LOW VOLTAGE FOR INTERNAL CIRCUIT AND MOTOR ACTUAT...

Страница 14: ... POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 24 VDC SUPPLY ACCEPTABLE SET SWITCH TO MODULATING V OR OR N A FEEDBACK 5 4 3 1 2 M35100 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 ACTUATOR V OR OR N A FEEDBACK 5 4 3 1 2 2 10 VDC 10 2 VDC 0 10 VDC 10 0 VDC Fltg fwd Fltg rev 3 24 VAC 1 24 VAC 1 2 24 VAC 1 HOT COM 4 ENSURE PROPER GROUNDING OF ACTUATOR CASE NOTES...

Страница 15: ...lications 1 Override to full open a Disconnect the input signal from terminal 3 b Apply 24 Vac to terminal 3 c See Fig 32 2 Override to full closed a Disconnect the input signal from terminal 3 b See Fig 33 Fig 32 Override to full open Fig 33 Override to full close End Switches Some models include end switches see Table 2 For wiring details see Fig 12 SPDT Switches Fig 34 For SPDT end switch wirin...

Страница 16: ...ves towards 100 position Feedback Operation 1 Connect a multi meter set for Vdc to terminals 2 and 5 2 Apply the same signal as in step 4 of Modulating Operation 3 The multi meter reading increases to match the input signal as actuator drives towards 100 position 4 Apply the same signal as in step 6 of Modulating Operation 5 The multi meter reading decreases to match the input signal as actuator d...

Отзывы: