ML7295 SPRING RETURN DIRECT COUPLED ACTUATORS

63-2539—1

4

CAUTION

Deteriorating vapors and acid fumes
can damage the actuator.
Install actuator in areas free of acid fumes and other
deteriorating vapors that can attack the metal parts of
the actuator.

Location

Install the actuator in a location that allows enough clearance
for mounting accessories and for servicing.

Refer to Warnings and Cautions (above) for locations to avoid.

Mounting

The ML7295 DCA has a self-centering shaft coupling to
accommodate specific shaft lengths, sizes, and shapes. Proper
actuator location and means of actuator rotation prevention are
necessary to avoid excessive strain on the output gear.

The ML7295 DCA operates a damper or hydronic valve by
driving the shaft either cw or ccw, depending on the design.
All actuators are shipped with a 5

°

 preload on the spring.

When power is applied to the actuator, the preload is released
and the actuator spring-returns 5

°

 for tight closeoff.

The ML7295 DCA is designed for single-point mounting.
Single-point mounting is typically used when the actuator is
mounted on a damper frame. A mounting bracket (see Fig. 1)
is provided for installing the actuator.

CAUTION

Avoid damage to the damper or actuator.
Do not allow the mounting bracket to bind or clamp
the actuator to the duct.

Use the mounting bracket only to prevent the actuator
housing from rotating.

Preparation

Before installing the ML7295 on the shaft, determine the
opening direction of the damper or valve for correct spring
return rotation and wiring connections. The ML7295 can be
mounted to provide clockwise or counterclockwise spring
return.

Determine appropriate mounting orientation

See Fig. 2 for mounting orientation.

Measure shaft length

If the shaft is less than three inches in length, the shaft coupling
must be located between the damper/valve and actuator
housing. If the shaft length is more than three inches, the shaft
coupling may be located on either side of the actuator housing.

If the coupling must be moved from one side of the actuator
to the reverse, follow these instructions (see Fig. 3):

1. Remove the position indicator from the shaft coupling

and set it aside for later use.

2. Remove the retainer clip from the shaft coupling and

set it aside for later use.

3. Remove the shaft coupling from one side of the actuator.
4. Replace the shaft coupling on the opposite side of the

actuator aligning it with the mark on the housing.

5. Replace the retainer clip on the shaft coupling using the

inner groove of the coupling.

6. Replace the position indicator on the shaft coupling.

If the shaft coupling is located between the actuator housing
and damper/valve, the position indicator holder must be
attached to the other side of the actuator. If this is necessary,
perform the following (see Fig 4):

1. Slide the position indicator holder onto the shaft

coupling near the retainer clip and rotate it until it snaps
into place.

2. Place the position indicator on the holder.

Fig. 2. ML7295 Spring Return Direct Coupled

Actuator mounting orientation.

Fig. 3. Mounting shaft coupling to opposite side of actuator.

Fig. 4. Adding position indicator holder.

CW TO OPEN

CCW TO CLOSE
(FAIL-SAFE 
POSITION)

CW TO CLOSE
(FAIL-SAFE 
POSITION)

CCW TO OPEN

M12443

M12441

M12440

Содержание ML7295 Series

Страница 1: ... FEATURES Brushless DC motor achieves sophisticated control of speed torque and braking Provides 142 lb in 16 N m torque Mounts directly on 3 8 in to 1 in 9 to 25 mm round and 1 4 in to 3 4 in 6 to 18 mm square shafts Self centering shaft coupling minimizes installation time Spring return direction is field selectable to simplify installation Manual override permits unpowered positioning to simpli...

Страница 2: ...onsumption Running 9 VA Holding 5 VA Feedback Signal Voltage output 0 10 Vdc Maximum current output 0 5 mA Cable Ratings Control Standard models include non plenum UL CSA rated 30V 140 F 60 C 18 gauge cable Auxiliary Switch UL CSA rated 300V 194 F 90 C 18 gauge cable Controller Type 0 to 10 Vdc or 4 to 20 mA All models have a feedback signal Torque Rating at rated voltage Lift and Hold 142 lb in 1...

Страница 3: ...ation as provided in these instructions WARNING Installing the actuator near explosive vapors could result in serious injury or death A spark from the actuator or attached accessories could ignite escaping gas or explosive vapors Install actuator in areas free of escaping gas and other explosive vapors CAUTION Failure to disconnect power before installation can result in electrical shock or equipm...

Страница 4: ...on and wiring connections The ML7295 can be mounted to provide clockwise or counterclockwise spring return Determine appropriate mounting orientation See Fig 2 for mounting orientation Measure shaft length If the shaft is less than three inches in length the shaft coupling must be located between the damper valve and actuator housing If the shaft length is more than three inches the shaft coupling...

Страница 5: ...7 If necessary replace the holder and position indicator on the shaft coupling Installation Installing Actuator and Mounting Bracket Single Point Damper Mounting NOTE For valve mounting see the literature accompanying the mounting equipment or bracket With the direction of the damper shaft rotation determined either cw or ccw proceed as follows 1 Place the ML7295 DCA over the damper shaft 2 Positi...

Страница 6: ...ignal that will drive the motor closed It is factory set to 0 Vdc and can be adjusted as high as 5 Vdc U Span is factory calibrated and adjusts the motor response to travel full stroke through the selected input span It is factory set to 10 Vdc and is adjustable from 2 to 30 Vdc L1 HOT L2 1 1 24 VAC METER 8 GREY 9 PINK 1 RED S1 GREEN RED S2 GREEN BLUE S3 GREEN PINK S4 BLACK RED S5 BLACK BLUE S6 BL...

Страница 7: ...ch a signal will be given by the switch see Fig 9 Once power is restored the actuator will return to normal automated control 20 30 30 10 20 40 40 50 60 70 70 80 90 A B AUX SWITCH ADD 0 5 10 20 30 60 70 80 90 0 10 20 30 60 70 80 90 M11699 Fig 9 Actuator rotary range and auxiliiary switch signal locations CHECKOUT To perform a checkout of the ML7295 DCA proceed as follows 1 Check the damper or valv...

Страница 8: ... Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 Honeywell Latin American Division Miami Lakes Headquarters 14505 Commerce Way Suite 500 Miami Lakes FL 33016 Helping You Control Your World 63 2539 1 B B Rev 10 97 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed in U S A on recycled paper containing at least 10 post con...