manualshive.com logo in svg
background image

ML7295 SPRING RETURN DIRECT COUPLED ACTUATORS

63-2539—1

5

CAUTION

Manually turning the shaft coupling
can damage the actuator.
Never turn motor shaft coupling by hand or with a
wrench.

Range Stop Adjustment

The ML7295 has an adjustable range stop feature. When the
rotational mounting of the shaft coupling is changed, the
actuator drives less than the full 95

°

 stroke. The stroke is

adjustable in 5

°

 increments and once adjusted, the actuator

drives until the shaft coupling reaches the mechanical stop,
which is a part of the housing. The stop causes the motor to
disengage and the shaft coupling drives no farther. When the
actuator returns, it stops at the fail-safe position which is set
as follows:

1. Remove the position indicator; and if applicable, the

holder, and set aside for later use.

NOTE:

If possible, leave the position indicator attached
to the shaft coupling to aid in future steps.

2. Remove the retainer clip from the shaft coupling and

set it aside for later use.

3. Remove the shaft coupling from the actuator.
4. Rotate the shaft coupling to the desired fail-safe position.
5. Install the shaft coupling at this position.

NOTE:

The location of the shaft coupling determines
the number of degrees of travel.

Example:

Setting the shaft coupling at an approximate

fail-safe position of 20

°

 (as indicated on the

housing), limits the stroke to 70

°

.

IMPORTANT

If the 5

°

 preload was not released, see the Mounting

section, the fail-safe position moves 5

°

 when power

is applied, increasing the stroke 5

°

.

6. Replace the retainer clip on the shaft coupling using the

inner groove of the shaft coupling.

7. If necessary, replace the holder and position indicator

on the shaft coupling.

Installation

Installing Actuator and Mounting Bracket
(Single Point Damper Mounting)

NOTE:

For valve mounting, see the literature accompanying
the mounting equipment or bracket.

With the direction of the damper shaft rotation determined
(either cw or ccw), proceed as follows:

1. Place the ML7295 DCA over the damper shaft.
2. Position the actuator for best access to the actuator

damper shaft locking screw.

3. Install the mounting bracket (see Fig. 5). Mark the screw

holes for installing the mounting bracket on the damper
housing.

4. Remove the mounting bracket and actuator.
5. Drill or center punch the starting holes for the mounting

bracket screws (or use no.10 self-tapping sheet metal
screws).

6. Turn the damper blades to the desired normal position,

usually the closed position.

7. Place the actuator and mounting bracket back into

position over the damper shaft and install the mounting
bracket screws.

8. Tighten the shaft coupling set screw firmly by applying

7.5 lb-ft (10 N•m) of torque with a 13/32 in. (10mm)
wrench.

Fig. 5. Mounting bracket installation.

CAUTION

Using the actuator as a shaft bearing will damage
the device, reducing the functional life span.
In applications with side loads to the actuator shaft
coupling, a different coupling (such as the one
supplied with the foot mount kit) 

must be used.

Wiring

CAUTION

Prevent electrical shock or equipment damage.
Disconnect all power supplies before wiring.

All wiring must comply with local electrical codes, ordinances
and regulations. The ML7295 is designed for use with a Class 2
power supply. Voltage and frequency of the transformer used
must correspond with the characteristics of the motor and the
power supply. See Fig. 6 for typical wiring connections.

M12442

Содержание ML7295 Series

Страница 1: ... FEATURES Brushless DC motor achieves sophisticated control of speed torque and braking Provides 142 lb in 16 N m torque Mounts directly on 3 8 in to 1 in 9 to 25 mm round and 1 4 in to 3 4 in 6 to 18 mm square shafts Self centering shaft coupling minimizes installation time Spring return direction is field selectable to simplify installation Manual override permits unpowered positioning to simpli...

Страница 2: ...onsumption Running 9 VA Holding 5 VA Feedback Signal Voltage output 0 10 Vdc Maximum current output 0 5 mA Cable Ratings Control Standard models include non plenum UL CSA rated 30V 140 F 60 C 18 gauge cable Auxiliary Switch UL CSA rated 300V 194 F 90 C 18 gauge cable Controller Type 0 to 10 Vdc or 4 to 20 mA All models have a feedback signal Torque Rating at rated voltage Lift and Hold 142 lb in 1...

Страница 3: ...ation as provided in these instructions WARNING Installing the actuator near explosive vapors could result in serious injury or death A spark from the actuator or attached accessories could ignite escaping gas or explosive vapors Install actuator in areas free of escaping gas and other explosive vapors CAUTION Failure to disconnect power before installation can result in electrical shock or equipm...

Страница 4: ...on and wiring connections The ML7295 can be mounted to provide clockwise or counterclockwise spring return Determine appropriate mounting orientation See Fig 2 for mounting orientation Measure shaft length If the shaft is less than three inches in length the shaft coupling must be located between the damper valve and actuator housing If the shaft length is more than three inches the shaft coupling...

Страница 5: ...7 If necessary replace the holder and position indicator on the shaft coupling Installation Installing Actuator and Mounting Bracket Single Point Damper Mounting NOTE For valve mounting see the literature accompanying the mounting equipment or bracket With the direction of the damper shaft rotation determined either cw or ccw proceed as follows 1 Place the ML7295 DCA over the damper shaft 2 Positi...

Страница 6: ...ignal that will drive the motor closed It is factory set to 0 Vdc and can be adjusted as high as 5 Vdc U Span is factory calibrated and adjusts the motor response to travel full stroke through the selected input span It is factory set to 10 Vdc and is adjustable from 2 to 30 Vdc L1 HOT L2 1 1 24 VAC METER 8 GREY 9 PINK 1 RED S1 GREEN RED S2 GREEN BLUE S3 GREEN PINK S4 BLACK RED S5 BLACK BLUE S6 BL...

Страница 7: ...ch a signal will be given by the switch see Fig 9 Once power is restored the actuator will return to normal automated control 20 30 30 10 20 40 40 50 60 70 70 80 90 A B AUX SWITCH ADD 0 5 10 20 30 60 70 80 90 0 10 20 30 60 70 80 90 M11699 Fig 9 Actuator rotary range and auxiliiary switch signal locations CHECKOUT To perform a checkout of the ML7295 DCA proceed as follows 1 Check the damper or valv...

Страница 8: ... Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 Honeywell Latin American Division Miami Lakes Headquarters 14505 Commerce Way Suite 500 Miami Lakes FL 33016 Helping You Control Your World 63 2539 1 B B Rev 10 97 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed in U S A on recycled paper containing at least 10 post con...

Отзывы: