ML7284 NON-SPRING RETURN DIRECT COUPLED DAMPER ACTUATOR

63-2504—2

8

IMPORTANT

The ML7284 can operate with a DDC controller. Do
not short cycle the actuator. Short cycling of the
actuator can cause premature failure.

The actuator has a position indicator to show shaft position.
As the indicator moves with the shaft, it gives an angular
representation of the damper position. There are two distinct
positions where the indicator can be placed. The indicator
can be removed (by first removing the output hub) and
turned to provide proper position indication. The indicator
can be indexed to show open or closed, using the detents
that are 90

°

 apart. See Fig. 3.

The ML7284D and ML7284F models provide a time-out
function that removes power from the actuator submotor if the
actuator remains in the fully open or fully closed position for
longer than a nominal 5 minutes. This time-out function helps
to extend actuator life.

CHECKOUT

Perform the following checkout procedure for the ML7284
Direct Coupled Damper Actuator.

1

Check the actuator position indicator and damper shaft
position to see that they agree.

2

Apply 24 Vac to the black (T1) and red (T2) leads.

3

Apply minimum control signal (0 Vdc, +2 Vdc, or 4 mA)
to the white (Input) lead  with respect to the black (T1)
lead:

If the reversing switch is in the direct position, the
actuator should drive the damper to the closed
(counterclockwise         ) position.

If the reversing switch is in the reverse position,
the actuator should drive the damper to the open
(clockwise         ) position.

4

Apply maximum control signal (+10 Vdc or 20 mA) to
the white (Input) lead with respect to the black (T1)
lead.

If the reversing switch is in the direct position, the
actuator should drive the damper to the open
(clockwise         ) position.

If the reversing switch is in the reverse position,
the actuator should drive the damper to the
closed (counterclockwise         ) position.

Helping You Control Your World

Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 2C9

63-2504—2     G. R.    Rev. 4-96     Printed in U.S.A.

Home and Building Control
Honeywell Inc.
1985 Douglas Drive North
Golden Valley, MN 55422

TROUBLESHOOTING

If the actuator does not operate properly during the checkout,
perform the following troubleshooting steps. Perform these
steps before replacing the actuator.

1

Check actuator label to verify proper power and control
signal requirements for the application.

2

Check for presence of 24 Vac at the black (T1) and red
(T2) leads when the actuator should be operating. If the
voltage is not present or is low, check the power supply
and actuator connections.

3

Check control signal voltage (or current) for proper
value and polarity at the actuator white (Input) and
black (T1) leads when the actuator should be driving. If
the signal is wrong, not present, or low, check the
controller. The positive (+) signal must go to the white
(Input) lead. If this signal point is negative, change the
control wiring.

4

Make sure the feedback wire is not connected to
24 Vac.

5

Change the reversing switch if the actuator does not
drive in the desired direction when a control signal is
applied and the wiring is correct.

6

Remove power and fully depress and hold the
disengage button while trying to turn the damper shaft
clockwise

      and counterclockwise         . If the

damper shaft turn freely throughout the 90

°

 stroke and

the actuator is installed correctly, replace the actuator.

7

If the damper shaft will not turn freely for the full 90

°

,

check for any binding and make sure the actuator is
loose on its mount bracket to prevent binding. If
necessary, adjust the mounting bracket to prevent
binding.

8

If no binding is noticed in the actuator and damper
assembly, remove the actuator and turn the damper
shaft clockwise         and counterclockwise         . If the
damper does not turn freely, fix or replace the damper.

9

If the damper turns, fully depress and hold the
disengage button and turn the actuator hub clockwise
and counterclockwise         . If the actuator does not
turn, replace the actuator.

J

If the actuator and damper turn freely, remount the
actuator to the damper following the instructions in the
Installation section. Make sure the actuator does not
bind, and that the damper and actuator are at the same
clockwise         or counterclockwise          end stop
when they are assembled. Connect all power and
control wiring and repeat the checkout. Troubleshoot if
necessary.

Содержание ML7284

Страница 1: ... 90 low leakage dampers Manual clutch allows for manual adjustment 92 second synchronous timing can eliminate need for feedback position indication in closed loop tempera ture control applications Removable splined output hub permits premounting of hub on damper shaft providing installation flexibility Includes standard reverse direct acting rotation switch on the outside cover Designed for both s...

Страница 2: ...torage Temperature 30 F to 150 F 40 C to 65 C Humidity 5 to 95 percent relative humidity noncondensing Mounting Mounts directly on 3 8 in to 3 4 in 12 to 19 mm round or square damper shaft Minimum shaft length required 2 5 in 64 mm when the shaft attachment is made on the side of the actuator opposite the duct 0 65 in 16 mm when the hub is mounted on the shaft before the actuator is installed Most...

Страница 3: ...tor and mounting bracket in in mm 9 32 7 3 PLACES 1 17 32 39 3 3 32 79 4 102 7 16 11 1 1 4 32 7 11 16 196 8 7 16 215 36 914 1 2 12 5 8 17 13 32 10 1 2 13 3 4 19 7 8 22 1 25 3 5 32 80 1 2 13 1 2 13 1 11 16 43 2 1 2 63 3 5 16 84 4 1 2 114 5 127 6 152 1 4 6 1 1 REMOVABLE RETAINING RING FOR REMOVAL OF HUB SLEEVE M7618B 1 4 6 1 8 3 2 51 15 16 24 1 29 32 48 ...

Страница 4: ...ion The ML7284 Non Spring Return Direct Coupled Damper Actuator is designed with removable hub inserts to accommodate specific damper shaft sizes Proper insert selection is necessary to avoid excessive strain on the output gear Most ML7284 Actuators are shipped with a 1 2 in hub insert For field use three hub insert sizes are available See the Accessories listing in the Specifications section Shaf...

Страница 5: ...cket on the damper housing 4 Remove the mounting bracket and actuator 5 Drill or center punch the starting holes for the mounting bracket screws or use no 10 self tapping sheet metal screws not provided 6 Place the actuator and mounting bracket back into position over the damper shaft and install the mounting bracket screws 7 Move damper shaft either fully cw or ccw 8 Fully depress and hold diseng...

Страница 6: ...R SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PROPORTIONING CONTROLLER PROPORTIONING CONTROLLER BROWN WHITE BROWN WHITE FEEDBACK INPUT FEEDBACK INPUT Fig 7 Common transformer with two controller outputs and two actuators M7621A MOUNTING BRACKET TO JUNCTION BOX UP TO 3 FT AWAY 30 30 0 60 60 90 12 1 2 REVERSE DIRECT Fig 4 ML7284 Actuator typical mechanical connection M7623A M...

Страница 7: ...pdt auxiliary switches that are factory set to make common to normally open at 12 and 82 rotation from the closed counter clockwise stop See Fig 6 OPERATION The ML7284 Non Spring Return Direct Coupled Damper Actuator is designed to be used in ventilating and air condi tioning installations to operate dampers ventilation flaps and louvers requiring up to 150 lb in torque The ML7284 Non Spring Retur...

Страница 8: ...eywell Inc 1985 Douglas Drive North Golden Valley MN 55422 TROUBLESHOOTING If the actuator does not operate properly during the checkout perform the following troubleshooting steps Perform these steps before replacing the actuator 1 Check actuator label to verify proper power and control signal requirements for the application 2 Check for presence of 24 Vac at the black T1 and red T2 leads when th...

Отзывы: