Honeywell ML7284 Скачать руководство пользователя страница 2

ML7284 NON-SPRING RETURN DIRECT COUPLED DAMPER ACTUATOR

63-2504—2

2

SPECIFICATIONS

Models:

ML7284: Non-Spring Return Direct Coupled Damper Actuators.
ML7284A: High Torque (150 lb-in.) Direct Coupled Damper

Actuator without auxiliary switches or time-out function.

ML7284C: High Torque (150 lb-in.) Direct Coupled Damper

Actuator with two low voltage rated auxiliary switches
and without time-out function.

ML7284D: High Torque (150 lb-in.) Direct Coupled Damper

Actuator without auxiliary switches and with time-out
function.

ML7284F: High Torque (150 lb-in.) Direct Coupled Damper

Actuator with two low voltage auxiliary switches and
with time-out function.

Electrical Ratings:

Power Input: 24 Vac 

±

 20%, 50/60 Hz.

Power Consumption:

ML7284A-C: 6.0 VA at 24 Vac.
ML7284D,F: 6.5 VA at 24 Vac.

Auxiliary Switch Ratings: 24 Vac, 3 AFL, 18 ALR, 1A Pilot

Duty.

Cable Ratings:

Control: Standard models include nonplenum UL/CSA

rated, 30V, 60

°

C, 20 gauge cable.

Auxiliary Switch: UL/CSA rated 300V 90

°

C, 18 gauge.

Torque Ratings at Rated Voltages:

Lift and Hold Minimum: 150 lb-in. (17 N•m).
Breakaway Minimum: 150 lb-in. (17 N•m).
Stall Minimum: 150 lb-in. (17 N•m).
Stall Maximum: 250 lb-in. (28.3 N•m).

Torque Deratings at 24 

±

20% Vac:

150 lb-in. from -20

°

F to 95

°

F (-29

°

C to +35

°

C).

133 lb-in. from 95

°

F to 140

°

F (35

°

C to 60

°

C).

150 lb-in. from -40

°

F to -20

°

F (-29

°

C to -34

°

C) at 24 Vac

+20% only.

Actuator Stroke:
95

°

 Nominal 

±

 3

°

, mechanically limited.

Actuator Timing at 90

°

 Stroke:

92 

±

 2 seconds synchronous at 60 Hz from -4

°

F to 140

°

F.

110 

±

 2 seconds synchronous at 50 Hz from -4

°

F to 140

°

F.

Non synchronous below -4

°

F.

Ambient Temperature  Range:
-40

°

F to +140

°

F (-40

°

C to +60

°

C).

Storage Temperature:
-30

°

F to 150

°

F (-40

°

C to 65

°

C).

Humidity:
5 to 95 percent relative humidity, noncondensing.

Mounting:
Mounts directly on 3/8 in. to 3/4 in. (12 to 19 mm) round or
square damper shaft. Minimum shaft length required:

2.5 in. (64 mm) when the shaft attachment is made on
the side of the actuator opposite the duct;

0.65 in. (16 mm) when the hub is mounted on the shaft
before the actuator is installed.

Most actuators are shipped with specifically sized hubs.
Some models contain an assembly with assorted hub inserts.
Mounting bracket is included with most models.

Dimensions:
See Fig. 1.

Device Weight:
3.0 lb (1.36 kg).

Noise Rating:
45 dBA maximum at 1 meter.

Position Indicator:
Mounted on actuator hub.

Actuator Design Life:
Full Stroke Cycles: 100,000.

Repositions:
2,000,000 minimum.

Control Input Specifications:
2 to 10 Vdc, 0 to 10 Vdc, or 4 to 20 mA.

Input Impedance:
100K ohms.

Feedback Signal:
2-10 Vdc.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number, or specify:

1. Model number.

2. Application.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Logistics

Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 (612) 951-1000

In Canada—Honeywell Limited/Honeywell Limitée, 155 Gordon Baker Road, North York, Ontario M2H 2C9. International Sales
and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan,
Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

Содержание ML7284

Страница 1: ... 90 low leakage dampers Manual clutch allows for manual adjustment 92 second synchronous timing can eliminate need for feedback position indication in closed loop tempera ture control applications Removable splined output hub permits premounting of hub on damper shaft providing installation flexibility Includes standard reverse direct acting rotation switch on the outside cover Designed for both s...

Страница 2: ...torage Temperature 30 F to 150 F 40 C to 65 C Humidity 5 to 95 percent relative humidity noncondensing Mounting Mounts directly on 3 8 in to 3 4 in 12 to 19 mm round or square damper shaft Minimum shaft length required 2 5 in 64 mm when the shaft attachment is made on the side of the actuator opposite the duct 0 65 in 16 mm when the hub is mounted on the shaft before the actuator is installed Most...

Страница 3: ...tor and mounting bracket in in mm 9 32 7 3 PLACES 1 17 32 39 3 3 32 79 4 102 7 16 11 1 1 4 32 7 11 16 196 8 7 16 215 36 914 1 2 12 5 8 17 13 32 10 1 2 13 3 4 19 7 8 22 1 25 3 5 32 80 1 2 13 1 2 13 1 11 16 43 2 1 2 63 3 5 16 84 4 1 2 114 5 127 6 152 1 4 6 1 1 REMOVABLE RETAINING RING FOR REMOVAL OF HUB SLEEVE M7618B 1 4 6 1 8 3 2 51 15 16 24 1 29 32 48 ...

Страница 4: ...ion The ML7284 Non Spring Return Direct Coupled Damper Actuator is designed with removable hub inserts to accommodate specific damper shaft sizes Proper insert selection is necessary to avoid excessive strain on the output gear Most ML7284 Actuators are shipped with a 1 2 in hub insert For field use three hub insert sizes are available See the Accessories listing in the Specifications section Shaf...

Страница 5: ...cket on the damper housing 4 Remove the mounting bracket and actuator 5 Drill or center punch the starting holes for the mounting bracket screws or use no 10 self tapping sheet metal screws not provided 6 Place the actuator and mounting bracket back into position over the damper shaft and install the mounting bracket screws 7 Move damper shaft either fully cw or ccw 8 Fully depress and hold diseng...

Страница 6: ...R SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED PROPORTIONING CONTROLLER PROPORTIONING CONTROLLER BROWN WHITE BROWN WHITE FEEDBACK INPUT FEEDBACK INPUT Fig 7 Common transformer with two controller outputs and two actuators M7621A MOUNTING BRACKET TO JUNCTION BOX UP TO 3 FT AWAY 30 30 0 60 60 90 12 1 2 REVERSE DIRECT Fig 4 ML7284 Actuator typical mechanical connection M7623A M...

Страница 7: ...pdt auxiliary switches that are factory set to make common to normally open at 12 and 82 rotation from the closed counter clockwise stop See Fig 6 OPERATION The ML7284 Non Spring Return Direct Coupled Damper Actuator is designed to be used in ventilating and air condi tioning installations to operate dampers ventilation flaps and louvers requiring up to 150 lb in torque The ML7284 Non Spring Retur...

Страница 8: ...eywell Inc 1985 Douglas Drive North Golden Valley MN 55422 TROUBLESHOOTING If the actuator does not operate properly during the checkout perform the following troubleshooting steps Perform these steps before replacing the actuator 1 Check actuator label to verify proper power and control signal requirements for the application 2 Check for presence of 24 Vac at the black T1 and red T2 leads when th...

Отзывы: