ML7284 NON-SPRING RETURN DIRECT COUPLED DAMPER ACTUATOR
63-2504—2
6
12°
82°
M7877
COMMON
COMMON
NO
NO
NC
NC
WHT/RED
WHT/BLU
WHT/YEL
BLACK/RED
BLACK/BLU
BLACK/YEL
INTERNAL
AUXILIARY
SWITCH
3A 24VAC
SWITCHES SHOWN AT ACTUATOR CLOSED POSITION
Fig. 6. ML7284 Actuator wiring for auxiliary switches.
Switches shown at actuator closed
(counterclockwise) position.
L1
(HOT)
L2
1
1
RED
BLACK
RED
BLACK
ML7284
ML7284
M7616A
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
PROPORTIONING
CONTROLLER
PROPORTIONING
CONTROLLER
BROWN
WHITE
BROWN
WHITE
FEEDBACK
INPUT
FEEDBACK
INPUT
Fig. 7. Common transformer with two
controller outputs and two actuators.
M7621A
MOUNTING
BRACKET
TO JUNCTION
BOX (UP TO
3 FT AWAY)
30
30
0
60
60
90
12
12
REVERSE
DIRECT
Fig. 4. ML7284 Actuator typical mechanical connection.
M7623A
ML7284
MODULATING
CONTROL
SOURCE
BROWN
WHITE
BLACK
RED
24 VAC
FEEDBACK
INPUT
T1
T2
METER
L1
(HOT)
L2
1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
Fig. 5. ML7284 typical wiring diagram.