background image

35 AND 70 LB-IN. NON-SPRING RETURN DIRECT COUPLED ACTUATORS

63-2209—8

8

IMPORTANT

Run an entire check of the operation after completing 

this procedure.

Fig. 9. Setscrew location for ML6161 and ML6174.

Wiring

CAUTION

Electrical Shock or Equipment Damage Hazard.

Can shock individuals or short equipment 

circuitry.

Disconnect all power supplies before installation.

Actuators with auxiliary switches can have more than 

one disconnect.

All wiring must comply with local electrical codes, ordinances 

and regulations. Voltage and frequency of the transformer 

used with the actuator must correspond with the 

characteristics of both the power supply and the actuator. 

Screw terminals are provided for easy hookup. See Fig. 11 

through 14 for typical wiring hookups.

Connecting Wiring to Conduit Cover Actuators (Fig. 
10)

1.

Remove the cover from the actuator by lifting the top 

and pivoting the cover to the rear of the actuator.

2.

Remove the conduit knockouts with a flat-bladed screw-

driver. Discard the knockouts.

3.

Install the conduit connector.

4.

Run the connecting wire through the conduit connector, 

strip the wire ends (if necessary) and connect to the 

CW, COM and CCW terminals using Fig. 11 through 14, 

Fig. 16 through 20, or the control manufacturer 

instructions.

5.

Apply power to the actuator.

6.

After operational checkout, replace the cover by 

reversing the procedure outlined in step 1.

Fig. 10. Conduit cover for ML6161C,D 

and ML6174C,D DCA.

Fig. 11. ML6161 or ML6174 used with T87F in 

heating-only or cooling-only application.

NOTE: See Fig. 12 for the 201052B Auxiliary Switch wiring.

Fig. 12. 201052B Auxiliary Switch wiring.

M10247

60

45

45

60

THIS SETSCREW 

CORRESPONDS WITH 

CLOSING IN THE 

CW DIRECTION

THIS SETSCREW 

CORRESPONDS WITH 

CLOSING IN THE 

CCW DIRECTION

COVER

M10075

CONDUIT 

KNOCKOUTS

M18019

EXTERNAL 

SWITCH

R

W

Y

T87F

R8222

RED    COM

BLUE   CW

WHITE   CCW

L1 

(HOT)

L2

1

1

2

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 

PROTECTION AS REQUIRED.

AUXILIARY SWITCHES ARE REQUIRED TO TURN OFF THE MOTOR 

AT EACH END OF THE STROKE.

ML6161, ML6174

M17350

SPDT

CONTROL

ON/OFF

CONTROL

RED    COM

BLUE   CW

WHITE   CCW

L1 

(HOT)

L2

1

1

4

2

3

2

3

4

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 

PROTECTION AS REQUIRED.

SET SWITCH TO CLOSE WHEN STROKE REACHES FULL CW POSITION.

SET SWITCH TO CLOSE WHEN STROKE REACHES FULL CCW POSITION.

ON-OFF CONTROL REQUIRES AN R8222 SPDT RELAY IN PLACE OF THE 

SPDT CONTROL.

ML6161, ML6174

201052B

Содержание ML6161 Series

Страница 1: ...spdt floating thermostats or two position control systems Two position control requires installation of the 201052B Auxiliary Switch FEATURES Selectable 45 60 or 90 stroke in both clockwise cw or counterclockwise ccw directions 0 to 30 minimum position adjustment cw or ccw direction on all models Magnetic coupling eliminates the need for mechanical stops Two field addable auxiliary switches Auxili...

Страница 2: ...58 kg Actuator Timing for 90 Stroke See Table 4 Mounting Mounts directly on 3 8 in to 1 2 in 10 to 13 mm round or square shaft Can be mounted with shaft in any position with two 1 4 in 6 mm 28 NF Allen screws Mini mum Shaft Length Required 1 3 4 in 45 mm Temperature Ratings Ambient 20 F to 125 F 18 C to 50 C Derated Timing to 20 F 29 C Shipping and Storage 20 F to 130 F 29 C to 54 C Humidity Ratin...

Страница 3: ...Linkage 61 Floating Control 71 4 20 mA 2 10 Vdc Control 61 35 lb in 4 Nm Non Spring Return 74 70 lb in 8 Nm Non Spring Return A Includes output for feedback potentiometer B Standard includes minimum position setscrews C Includes output for feedback potentiometer and cover with conduit connections D Includes cover with conduit connections E Standard with European ratings 1 Standard 2 Includes declu...

Страница 4: ...IRECT COUPLED ACTUATORS 63 2209 8 4 Fig 1B Approximate dimensions of ML6161C D and ML6174C D DCA in in mm M18018 5 7 8 149 1 13 16 46 1 25 3 5 8 92 1 13 16 46 3 IN 76 MM MINIMUM SPACING REQUIRED FOR REMOVING CONDUIT COVER 3 3 4 95 7 8 22 ...

Страница 5: ... designed to open a damper or valve by driving the shaft in either the clockwise cw or counterclockwise ccw direction The actuator has a mounting tab on the bottom that secures it to a damper box or valve linkage When mounted correctly this tab allows the actuator to float without rotating relative to the shaft The tab is sized for 1 4 in screw or pin not included CAUTION Equipment Damage Hazard T...

Страница 6: ...gle of the damper opening is either 45 or 60 close the actuator using the manual declutch a Disengage the hub using the declutch lever see Manual Operation Declutch section b Rotate the hub until the actuator gear train passes the proper 45 or 60 setting Do not insert the pin until after the actuator passes this point c Release the declutch lever NOTE Dampers with 90 stroke do not require the rang...

Страница 7: ...ng 7 If resistance is met before the setscrew is fully inserted stop and review the initial setup procedures as detailed in steps 1 through 3 8 Determine the angle of minimum position required for the application With the setscrew fully inserted the minimum position is 30 With the setscrew fully out the minimum position is 0 9 Using the conversion of approximately 1 7 angular degrees per turn of t...

Страница 8: ... ends if necessary and connect to the CW COM and CCW terminals using Fig 11 through 14 Fig 16 through 20 or the control manufacturer instructions 5 Apply power to the actuator 6 After operational checkout replace the cover by reversing the procedure outlined in step 1 Fig 10 Conduit cover for ML6161C D and ML6174C D DCA Fig 11 ML6161 or ML6174 used with T87F in heating only or cooling only applica...

Страница 9: ...or body and the bracket is aligned over the screw hole 4 Insert the screw provided into the hole and fasten securely IMPORTANT Failure to follow the calibration procedures can result in improper resistance values at desired stroke Fig 15 ML6161A C ML6174A C with field addable potentiometer To Calibrate the 200976A C IMPORTANT Remove the range stop pins and minimum position setscrews prior to calib...

Страница 10: ...all thermostats The T641 is a mercury bulb floating control type thermostat designed for use with the seven minute model on pressure dependent systems see Fig 16 and 17 The T6984 is an electronic floating control thermostat designed for use with the 90 second and seven minute models see Fig 18 Fig 16 T641A controlling ML6161 or M6174 Actuator Fig 17 Minimum position set with auxiliary switch conta...

Страница 11: ...llel Make certain the total connected load does not exceed the current capacity of the input signal source CURRENT INPUT 4 TO 20 MA When using a current controller such as the W7600 wire the ML7161 ML7174 voltage input terminals Vdc and in parallel Use a bridging resistor in parallel with the 4 to 20 mA signal See Fig 20 for resistor values NOTE The actuator has 45 000 ohm impedance Fig 19 Spdt co...

Страница 12: ...of the thermostat higher to determine if the wiring is correct 4 If no movement is observed check for the presence of 24 volts 5 If using the T641 Thermostat check that 24 volts are present between terminals C and Y during a call for cooling With proper wiring and 24 volts present the actuator should operate correctly 6 If not replace the actuator ML7161 ML7174 Check input impedance on the actuato...

Отзывы: