Lynx Plus Series Installation and Setup Guide
- 9 -
Connecting/Configuring Communication Modules
General
This Lynx Plus Series control supports central station reporting via the internet using wireless (GSM) and
hardwire (IP) communications modules. It also supports upload/download programming capability via the
Internet or a Private local area network (Intranet). This allows site maintenance independent of central
station monitoring, and modification to sites globally via the Internet or through a private LAN. Refer to the
instructions provided with the LRR/IP Communications Device being installed for additional information
regarding its installation, programming, and registration. The control is compatible with the following
AlarmNet Communications Modules:
•
7847i-L Internet Communications Module
•
GSMVLP GSM Communications Module with 2-Way Voice
Connecting Long Range Radio and Internet Communication Devices
Connect and configure the communications device (refer to the Installation Instructions for device that you
are installing for additional information).
LRR/IP Communications Device 24-Hour Standby Power
If you are installing the AlarmNet 7847i-L, and require 24-hour standby, you must install the Super High
Capacity battery P/N WALYNX-RCHB-SHA in the control.
Configuring Long Range Radio and Internet Communication Devices
1. Enable the communications device in programming field
✼
55 and configure alarm reporting and module
supervision in programming field
✼
77.
2. Program the device as required using the 7720P programmer (refer to the Installation Instruction for the
device that you are installing). Note that the device address must be set to 3.
The device must be registered before downloading or alarm reporting can take place.
LRR Communications Device Diagnostic Mode
This mode provides a method to verify the LRR signal strength.
1. Enter the Installer Code (4112) + 899. The system will initially display “Entering programming mode”.
2. The LRR Communications Module’s Signal Level (Primary Site Received Signal Strength Indication
[PriRSSI]) will be displayed in dBm. The system will also display GPRS connection and registration
indications (refer to the example that follows).
3. If “FAIL” or “POOR” signal levels are displayed during the test, the control should be relocated to find a
location that provides better signal strength.
If a ‘searching for coverage’ message is displayed or the radio is not connected and no signal indication
is displayed, the installer should check radio programming, panel programming, etc., before entering this
mode again.
Signal strength may vary
4. The Lynx Plus will automatically exit this mode after approximately 1-minute or if any key is pressed.
The system will display “Exiting programming mode” when the test is complete.