- 22 -
Continued
Instrument input range
Input type
Input
range
code
ºC ºF
Measurement accuracy:
±
0.1% of span typical(
±
1 digit for display)
K1
-200.0~200.0
-328.0~392.0
+/-0.1%FS
Below 0ºC : +/-0.2%FS
K2
0.0 ~ 1200.0
32.0~2192.0
+/-0.1%FS
K3 0.0~800.0
32.0~1472.0
+/-0.1%FS
K4 0.0~400.0
32.0~752.0
+/-0.1%FS
K(CA)
K5 0.0~1316.0
32.0~2400.0
+/-0.1%FS
J(IC) J 0.0~800.0
32.0~1472.0
+/-0.1%FS
R R
0.0~1600.0
32.0~2912.0
+/-0.1%FS
S S
0.0~1600.0
32.0~2912.0
+/-0.1%FS
B B
0.0~1800.0
32.0~3272.0
+/-0.1%FS
+/-4.0%FS at 0 to 260ºC
+/-0.15%FS at 260 to 800ºC
E(CRC) E 0.0~800.0
32.0~1472.0
+/-0.1%FS
T(CC)
T
-200.0~300.0
-328~572.0
+/-0.1%FS
+/-0.3%FS at –200 to -45ºC
N N
0.0~1300.0
32~2372
+/-0.1%FS
W1 W1
0.0~1200.0
32~2192
+/-0.1%FS
W2 W2
0.0~2300.0
32~4172
+/-0.1%FS
Thermo
couple
C C
0.0~2300.0
32~4172
+/-0.1%FS
* FS : Full Scale