HVAC400X – APPLICATION MANUAL
EN2B-0417GE51 R0719
72
7
I/O AND HARDWARE MENU
In this menu, there are different settings that are related to the options.
7.1
Basic I/O
In the Basic I/O menu, you can monitor the statuses of the inputs and the outputs.
Table 55. The basic I/O parameters in the I/O and Hardware menu
Index
Parameter
Min
Max
Unit
Default
ID
Description
V5.1.1
Digital Input 1
0
1
0
2502
Status of the digital input signal.
V5.1.2
Digital Input 2
0
1
0
2503
Status of the digital input signal.
V5.1.3
Digital Input 3
0
1
0
2504
Status of the digital input signal.
V5.1.4
Digital Input 4
0
1
0
2505
Status of the digital input signal.
V5.1.5
Digital Input 5
0
1
0
2506
Status of the digital input signal.
V5.1.6
Digital Input 6
0
1
0
2507
Status of the digital input signal.
V5.1.7
Analog input 1 Mode
1
3
3
2508
Shows the mode that is set for the
analog input signal. The selection is
made using a DIP switch on the control
board.
1 = 0...20mA
3 = 0...10V
V5.1.8
Analog input 1
0
100
%
0.00
2509
Status of the analog input signal 1
V5.1.9
Analog input 2 Mode
1
3
3
2510
Shows the mode that is set for the
analog input signal. The selection is
made using a DIP switch on the control
board.
1 = 0...20mA
3 = 0...10V
V5.1.10 Analog input 2
0
100
%
0.00
2511
Status of the analog input signal 2
V5.1.11 Analog output 1 Mode
1
3
1
2512
Shows the mode that is set for the
analog input signal. The selection is
made using a DIP switch on the control
board.
1 = 0...20mA
3 = 0...10V
V5.1.12 Analog output 1
0
100
%
0.00
2513
Status of analog output signal 1.
V5.1.13 Relay Output 1
0
1
0
2514
Status of relay output signal 1.
V5.1.14 Relay Output 2
0
1
0
2515
Status of relay output signal.
V5.1.16 Thermistor
0
1
0
2516
Status of the thermistor.