HVAC400X – APPLICATION MANUAL
EN2B-0417GE51 R0719
52
The Digital Outputs of the Expander Slots C, D, and E
Shows only the parameters for the outputs on option boards in slots C, D and E. Make the selections as in Basic
RO1 Function (P3.5.3.2.1).
If there are no digital outputs in slots C, D, or E, this group or these parameters are not visible.
Table 21. Standard I/O board analog output settings
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.5.4.1.1
AO1 function
0
20
2
10050
0 = TEST 0% (Not used).
1 = TEST 100%.
2 = Output freq (0 - fmax).
3 = Freq reference (0 - fmax).
4 = Motor speed (0 - Motor
nominal speed).
5 = Output current (0 - InMotor).
6 = Motor torque (0 - TnMotor).
7 = Motor power (0 - PnMotor).
8 = Motor voltage (0 - UnMotor).
9 = DC link voltage (0 - 1000V).
10 = PID1 output (0-100%).
11 = PID2 output (0-100%).
12 = ProcessDataIn1 (0-100%).
13 = ProcessDataIn2 (0-100%).
14 = ProcessDataIn3 (0-100%).
15 = ProcessDataIn4 (0-100%).
16 = ProcessDataIn5 (0-100%).
17 = ProcessDataIn6 (0-100%).
18 = ProcessDataIn7 (0-100%).
19 = ProcessDataIn8 (0-100%).
20 = PID Feedback (0-100%).
P3.5.4.1.2
AO1 filter time
0.0
300.0
s
1.0
10051
0 = No filtering.
P3.5.4.1.3
AO1 minimum signal
0
1
0
10052
0 = 0 mA / 0V.
1 = 4 mA / 2V.
P3.5.4.1.4
AO1 minimum scale
Varies
Varies
Varies
0.0
10053
P3.5.4.1.5
AO1 maximum scale
Varies
Varies
Varies
0.0
10054