HVAC400X – APPLICATION MANUAL
119
EN2B-0417GE51 R0719
10.5.5
Analog Outputs
P3.5.4.1.1 AO1 FUNCTION (ID 10050)
You can use this parameter to select a function or a signal that is connected to the analog output.
Table 69. P3.5.4.1.1 AO1 FUNCTION (ID 10050)
Selection number Selection name
Description
0
Test 0% (not used)
The analog output is set to 0% or 20% so that it agrees with parameter
P3.5.4.1.3.
1
TEST 100%
The analog output is set to 100% of the signal (10V / 20mA).
2
Output frequency
The actual output frequency from 0 to Maximum frequency reference.
3
Frequency reference
The actual frequency reference from 0 to Maximum frequency
reference.
4
Motor speed
The actual motor speed from 0 to Motor nominal speed.
5
Motor current
The output current of the drive from 0 to Motor nominal current.
6
Motor torque
The actual motor torque from 0 to motor nominal torque (100%).
7
Motor power
The actual motor power from 0 to Motor nominal power (100%).
8
Motor voltage
The actual motor voltage from 0 to Motor nominal voltage.
9
-link voltage
The actual DC-link voltage 0…1000V.
10
PID1 output
The output of the PID controller 1 (0…100%).
11
PID2 output
The output of the PID controller 2 (0…100%).
12
Process Data In 1
Process Data In 1: 0…10000 (this agrees with 0…100.00%).
13
Process Data In 2
Process Data In 2: 0…10000 (this agrees with 0…100.00%).
14
Process Data In 3
Process Data In 3: 0…10000 (this agrees with 0…100.00%).
15
Process Data In 4
Process Data In 4: 0…10000 (this agrees with 0…100.00%).
16
Process Data In 5
Process Data In 5: 0…10000 (this agrees with 0…100.00%).
17
Process Data In 6
Process Data In 6: 0…10000 (this agrees with 0…100.00%).
18
Process Data In 7
Process Data In 7: 0…10000 (this agrees with 0…100.00%).
19
Process Data In 8
Process Data In 8: 0…10000 (this agrees with 0…100.00%).
NOTE:
For ProcessDataIn, use a value without a decimal separator, e.g., 5000 =50.00%.
P3.5.4.1.2 AO1 FILTER TIME (ID 10051)
You can use this parameter to set the filtering time for the analog signal.
The filtering function is disabled when the filtering time is 0.
P3.5.4.1.3 AO1 MINIMUM (ID 10052)
You can use this parameter to change the range of the analog output signal.
For example, if '4mA' is selected, the range of analog output signal is 4…20mA.
Select the signal type (current/voltage) using the dip switches.
P3.5.4.1.4 AO1 MINIMUM SCALE (ID 10053)
You can use this parameter to scale the analog output signal.
The scaling values (min and max) are given in the process unit that is specified by the selection of the AO function.