50461/GTEX MMC/1111
UTImeter Gtex MMC
11
5. Recommendation for safe use
1. This Operation and Service Manual is a guide in order to help the user to operate the instrument to our
best knowledge.
2. Nevertheless the maker disclaims all responsibility and liability for damage resulting from the use of the
equipment regardless of the cause of the damage.
3.
Attention is drawn to the possible hazard due to electrostatic charges which may be present in
the tank.
This may happen in particular with static accumulator liquids, i.e. liquids which have low
conductivity of 50 picoSiemens/metre (pS/m) or less.
4.
It is very important that the instrument is grounded to the tank before the probe is introduced into
the tank and remains grounded until after complete withdrawal from the tank.
4.1. If the instrument is installed with the quick connect coupler, grounding is effected through the quick
connect coupler and the mating nipple of the valve provided that these parts are kept clean and free
from corrosion in order to guarantee electrical conductivity. If a grease is used for this purpose, it
must be one which contains graphite.*
4.2. If the instrument is not connected to the mating deck valve *, the instrument has to be also* earthed
by means of the grounding cable and clamp.
*
WITH MMC APDAPTORS THE USE OF THE GROUNDING CABLE IS MANDATORY
.
5.
It is anticipated that the user will have specific operating methods laid down to ensure safety
when using this type of apparatus. In this case the user's instructions shall be strictly observed.
6.
In the absence of such instructions the following should be noted:
6.1. If a metal sounding pipe is fitted beneath the deck valve or tank is inerted, then ullaging, etc. is
permissible at any time with no restriction.
6.2. If there is no sounding tube or tank is not inerted, the following precautions shall be taken:
6.2.1. If the cargo is not a static accumulator liquid, i.e. its conductivity is more than 50 pS/m, then
ullaging is permitted provided that the instrument is properly grounded and earthed before
the probe is inserted into the tank and remains earthed until the probe has been removed
from the tank.
6.2.2. If the cargo is a static accumulator liquid, i.e. its conductivity is less than 50 pS/m, then
ullaging is permitted provided that:
6.2.2.1. The instrument is properly grounded and earthed before the probe is inserted into
the tank and remains earthed until the probe has been removed from the tank.
6.2.2.2. The apparatus is not introduced into a tank until at least 30 minutes have elapsed
after completion of any loading operation or stopping the injection of inert gas.
6.3. For further guidance refer to International Safety Guide for Oil Tankers and Terminals (ISGOTT),
ISBN 1 85609 291 7, Fith Edition 2006, or consult the appropriate Legislative Authority for the
installation.
7.
Warning:
change of battery must be carried out in safe area only (non flammable atmosphere).
8.
This product and his use is / may be related to international, national, local or company
regulations or standards. It is the customer / user responsibility to ensure that the way to use the
device complies with such applicable regulations or standards.
9.
This device is a portable product. It must not be permanently installed on the tank and must be
disconnected after use and stored in a safe and dry area.
Содержание HERMetic UTImeter Gtex
Страница 10: ...50461 GTEX MMC 1111 UTImeter Gtex MMC 10 ...
Страница 54: ...50461 GTEX MMC 1111 UTImeter Gtex MMC 54 Figure 13 2 display unit assembly TS 10210 details ...
Страница 57: ...50461 GTEX MMC 1111 UTImeter Gtex MMC 57 Figure 13 5 load details ...
Страница 63: ......
Страница 64: ......