Revision 6
HC900 Process & Safety Controller User and Installation Manual
181
21 April 2017
Number
of Red
Strobes
Possible Causes
Lead and/or Reserve Controller
Action(s)
User Action
Honeywell OI
Indication
HCDesigner/HC
Utilities Indication
8 or 9
If 8 flashes, the S1
serial port is reporting a
diagnostic.
If 9 flashes, the S2
serial port is reporting a
diagnostic.
Possible causes are:
If the port is
configured as a
Modbus or ELN
slave, the data link
layer is reporting
that at least 75% of
the last characters
received have had
a failure reported by
the UART or at
least 75% of the
last messages
received have
been invalid.
If the port is
configured as a
Modbus Master, at
least 75% of the
last requests to a
particular slave
resulted in no
response or a reply
that failed the data
link protocol.
1.
ASYS and FSYS blocks’ HW
OK pins are turned off.
2. If configured as a Modbus
master:
ASYS and FSYS blocks’
Modbus Master Fail pins are
turned on.
Slave and read blocks
associated with the slaves
experiencing the failure have
their read pins frozen to the last
value read.
Slave blocks associated with
the slaves experiencing the
failure have their BAD COMM
and NO SCAN pins turned on.
IN SCAN STATUS is set to
NO for all slaves experiencing
the failure.
COMM STATUS is set to BAD
for all slaves experiencing the
failure.
The slaves with the data link
errors have a non-zero data
link error count.
The slaves experiencing the
failure are moved to the
background scan rate.
1. Check baud rate
2. Check connectors
3. Check cable polarity
4. Isolate cabling from electrical
interference
5. If RS-232 to RS-485 converter is
used, check its power, switch/jumper
settings, and polarity.
6. If configured as a Modbus master,
use the slave status screens to
determine which slaves are
experiencing the problem. For those
slaves check:
Power
Connections
address
baud rate
parity
number of stop bits
for electrical interference
grounding
termination resistor (if at end
of link)
9. The diagnostic is cleared by
clearing the port’s statistics.
2
The UART failed its
power-up tests
See above
Replace CPU module
10
Ethernet port tests
failed during power-up.
1. E1 or E2 port diagnostic is set to
FAILED.
2.
ASYS block’s HW OK pin is
turned off.
Replace CPU module.
If the lead’s status
LED is indicating
the failure, see
NETWORK
PORT E1
or
NETWORK
PORT E2
in the
“Lead CPU
Diagnostics”
display.
If the reserve’s
status LED is
indicating the
failure, see
NETWORK
PORT E1
or
NETWORK
PORT E2
in the
“Reserve CPU
Diagnostics”
display.
If the lead’s status
LED is indicating
the failure, see
Lead Port E1:
Network Port
Diagnostics
or
Lead Port E2:
Network Port
Diagnostics
in
the “Lead
Diagnostics
Overview” dialog
box.
If the reserve’s
status LED is
indicating the
failure,
Lead Port
E1: Network Port
Diagnostics
or
Lead Port E2:
Network Port
Diagnostics
in
the “Reserve
Diagnostics
Overview” dialog
box.
Содержание HC900
Страница 5: ...Revision 6 HC900 Process Safety Controller User and Installation Manual v 21 April 2017 ...
Страница 6: ......
Страница 30: ......
Страница 128: ...114 HC900 Process Safety Controller User and Installation Manual Revision 6 21 April 2017 Figure 61 DC Output Jumpers ...
Страница 140: ......
Страница 186: ......
Страница 269: ...Revision 6 HC900 Process Safety Controller User and Installation Manual 255 21 April 2017 Declaration of Conformity ...
Страница 270: ...256 HC900 Process Safety Controller User and Installation Manual Revision 6 21 April 2017 ATEX Certification ...