Preconfiguration checklist
gtap.genetec.com | Honeywell Galaxy Control Panel Integration Guide 5.2
16
EN.550.007-V5.2.C4(3) | Last updated: March 11, 2014
For more information about configuring the communication mode, see “56.6.1 Mode” in
the
Honeywell Galaxy Dimension Installer Manual
.
2
Set the alarm signalling
Format
as
SIA
, and the
SIA level
to level 4.
SIA level 4 allows Security Center to control the Galaxy Dimension control panel.
For more information about programming the SIA format, see “56.1.2 = SIA (Security
Industries Association)” in the
Honeywell Galaxy Dimension Installer Manual
.
3
Create the
Account Number (Account No.).
The account number must be a unique number that identifies the site. It can have up to six
digits.
Best practice:
Do not start the account number with a zero.
For more information about creating an account number, see “56.6.3 Account No.” in the
Honeywell Galaxy Dimension Installer Manual
.
4
Configure the
Comms Setup
.
The RS-232 port serial communication settings must match the settings of the Security
Center serial COM port used to communicate with the intrusion detection unit. See
For more information about configuring the communications setup on the control panel,
see “56.6.4 Comms Setup” in the
Honeywell Galaxy Dimension Installer Manual
.