OPERATOR MANUAL // SECTION 1: INTRODUCTION
HONEYWELL
11
1.6.4
Physical Description
The Detector’s electronics and sensors are mounted inside a
module which is housed in a water-tight and explosion-proof
enclosure with the following ratings: Class I Div. 1, 2, Groups B, C,
D; Class II, Div. 1 & 2, Groups E, F, G and Class III; NEMA 3 & 4;
tamper-resistant with integral dual 3/4 inch NPT conduit openings;
copper-free aluminum (less than 0.4%) with a red powder-coated
epoxy finish and a reflector assembly. The Detector’s housing “O”
ring material is Dupont Viton that is not affected by paint solvents.
The Detector weighs approximately 3.5 pounds. For dimensions,
see Figures 1 and 2.
1.6.5
Field of View
The Detector’s field-of-view is ninety (90) degrees (+ 45 º horizontal
and vertical).
1.6.6
Environment Range
The Detector humidity range is 10% to 90% (RH), non-condensing.
The operating and storage temperature range of the Detector is –
40
o
F to +185
o
F (-40
o
C to +85
o
C).
1.6.7
Location
For proper installation, each Detector should be located within the
detection distance ordered from the factory (i.e., 15 feet for the
FS10-R15, -RN15, -A15, -AN15; 30 feet for the FS10-R30, -RN30, -
A30, -AN30, and 45 feet for the FS10-R45, -RN45, -A45, -AN45) of
the fire threat area and have a clear view of the area being
monitored.
1.6.8
Self-Test
The Detector activates an ACCTTL
TM
(Automatic Computer
Controlled Through The Lens Test) for checking the Detector’s
window lens for contamination. If the Detector’s lens needs
cleaning, the Detector’s LED blinks three times in a burst, every 10
seconds.
1.6.9
Warranty
Honeywell Analytics warrants the Flame Detector against any
defects in material and workmanship for a period of two (2) years
from shipment date.