Application Manual
35
Binding the evotouch controller to the HM80 mixing valve controller
4.6
Binding procedure
4.6.1
Follow the guided or expert configuration until the
f
following screen appears.
Press both buttons (1) and (2) at the HM80 for approx.
f
4 seconds until the LED (3) flashes regularly.
3
1
2
Position the
f
evotouch controller as close as possible
to the HM80 mixing valve controller.
Press the BIND button on the
f
evotouch controller
to send the bind signal to the HM80 mixing valve
controller.
The LED (3) of the HM80 is switched OFF to confirm a
successful binding.
i
Binding is terminated automatically after 3 minutes.