Calibration
4. Calibration
4.1 Calibration
Overview
Calibration consists of the following functions:
Cell Calibration Trim Value and Reset
– may be reset to the Factory Default of
1.000.
(go to Step 1)
Cell Calibration
– can only be selected when online PV is displayed.
(go to Step 2)
Temperature Calibration Offset Value and Reset
– may be reset to the
Factory Default of 0.0.
(go to Step 3)
Temperature Calibration
– can only be selected when online PV is displayed.
(go to Step 4)
NOTE: Display returns to On-line PV after each step
ATTENTION:
In Table 4-1, under the
Press
column:
Hold
means to hold the button down until the display changes.
Momentarily
means to press and release the indicated button.
Table 4-1 Calibration Procedure
Step
Operation
Press
Display
1
Cell Calibration
Trim Reset
CCal
Momentarily
Ctr (1 second)
Then "Cal Trim Value" i.e. 1.250
Hold
(10
seconds)
Display will show "1.000".
Cell Cal Trim is reset.
continued MODE
Momentarily
Display will change to online PV.
18
DirectLine® DL423 Sensor Module User Manual
9/11