Configuration
9/11
DirectLine® DL423 Sensor Module User Manual
13
Noise Suppression Frequency Selection
– Selection of 50 Hz or 60 Hz
(default).
Defaults to 60 Hz at unit reset.
Output Configuration
– The following Output Configuration functions can be
selected:
0% Range
0 % Range values can be adjusted within a range
0.00 (default) to Max PV in 0.50 increments.
100% Range
100 % Range values can be adjusted within a range
0.00 to Max PV (default) in 0.50 PV increments.
0% Calibration
Output current can be typically adjusted to within a
range of 3.80 mA to 4.40 mA.
100% Calibration
Output current can be typically adjusted to within a
range of 19.60 mA to 20.40 mA.
Table 3-1 provides steps and entry information for the complete configuration
sequence.