Operation
2/04
DirectLine® DL421 Sensor Module User Manual
25
5.2 Diagnostic Error Messages
When a diagnostic error or status condition occurs, the Online Display alternates
between measured pH and a text message.
Table 5-3 Online Diagnostic Errors
What you see
What it is
What to do
CNFG
Data error detected.
Reset unit or cycle power.
Second occurrence will show
FALT.
FALT
Unit electronics are defective.
Replace electronics module.
These errors may occur when online pH or temperature is displayed.
P HI
Measured pH is > 14.00 pH
Bring process within limits
P LO
Measured pH is < 0.00 pH
Bring process within limits
PRBE
Probe is defective, removed from process, or not
connected.
Forces the output to burnout level (greater than
21.8 mA).
Check probe, connection and
presence of sample.
When the source of the error is
removed, the error will clear and
the output will return to normal
operation.
T HI
Measured temperature is > 110
°
C
Bring process within limits
T LO
Measured temperature is <
−
10
°
C
Bring process within limits
These errors may occur during probe calibration and abort the calibration process.
FAIL
These error messages are preceded by the
message “FAIL”
BFRS
The Slope buffer is less than 2 pH from
Zero (Standardization) buffer.
SRNG
The Slope calibration failed due to a
calculated Percent Theoretical Slope value
outside the range of 80.0 % to 105.0 %.
STBL
The Zero (Standardization) or Slope
calibration failed due to measured pH
instability.
TRNG
The Zero (Standardization) or Slope
calibration failed due to solution
temperature outside the range of 0
°
C to 50
°
C. (Auto Buffer Recognition calibration
only)
ZRNG
The Zero (Standardization) calibration
failed due to a calculated Zero Offset value
outside the range of –2.00 pH to 2.00 pH.
Press Mode to return to online
display.
Содержание DirectLine DL421
Страница 34: ...Spare Parts 28 DirectLine DL421 Sensor Module User Manual 2 04 ...
Страница 35: ...Spare Parts 2 04 DirectLine DL421 Sensor Module User Manual 29 ...
Страница 37: ...Appendix CE Mark Applications 2 04 DirectLine DL421 Sensor Module User Manual 31 ...
Страница 39: ...2 04 DirectLine DL421 Sensor Module User Manual 33 ...