WEB-600E AND CP-600E NETWORK CONTROLLERS

62-0433—01

8

WIRING DETAILS

See Fig. 3 to locate connectors and components on the 

controller. 

Make connections to the controller in the following order:

1.

Install any option card (LON, RS-485, RS-232, etc.) 

and/or approved MiniPCI card in the available option 

slots. See “Installing an Option Card” on page 7 for a 

procedure. For complete details, refer to the document 

that shipped with the option card.

If installing the optional NiMH battery, do that after 

inserting option card(s). See “NiMH Battery Installation 

and Maintenance” on page 14.

2.

Connect supplied grounding wire from the earth ground 

lug on the controller, as well ground wire for each acces-

sory module, to a nearby earth grounding point. See 

“Grounding” on page 8.

3.

Prepare power wiring (leave unit powered off). See 

“Power Wiring” on page 8.

4.

Connect communications cables. See “Communications 

Wiring” on page 10 for ports on the controller. For ports 

on any installed option card (485-PWR, LON, RS-485, 

modem) see the option’s specific mounting and wiring 

guide for details.

5.

If I/O accessory modules are installed, connect I/O wir-

ing. Refer to the appropriate mounting and wiring guide 

for details.

6.

Apply power to the unit. See “Power Up and Initial 

Checkout” on page 13.

Grounding

An earth ground spade lug (0.187") is provided on the 

controller base for connection to earth ground. For maximum 

protection from electrostatic discharge or other forms of EMI, 

connect the supplied earth grounding wire to this lug and a 

nearby earth ground. Keep this wire as short as possible, see 

Fig. 4.

Also connect the earth ground spade lug of each accessory 

module to ground in the same manner.

Power Wiring

The controller must be powered by an approved 15 Vdc power 

source. This can be either

a

 DIN-mountable module: the NPB-

PWR-H, a 24Vac/dc-powered module, or the NPB-PWR-UN-

H, a line-powered 120–240Vac module. Or, an external Class 

2 wall mount AC adapter (NPB-WPM-US) can be used for 

controller power.

The controller does not include an on/off switch. To apply 

power, you either:

• if NPB-PWR-H, plug in its 2-position power connector.

• if NPB-PWR-UN-H, energize the AC circuit (120–240 Vac) 

wired to that module.

• if NPB-WPM-US, plug in the power connector to the 

controller.

CAUTION

Do not connect both the NPB-WPM-US and NPB-

PWR-H / NPB-PWR-UN-H supplies at the same 

time, or equipment damage may result.

Power consumption depends mainly on installed I/O modules, 

and may vary from:

• Controller alone (with 

or

 without installed option cards): 

approximately 7.5 VA (AC) or 7.5 W (DC).

• Controller (with 

or

 without installed option cards), plus four 

(4) IO-16-H modules: up to 20 VA (AC) or 20 W (DC).

If desired, you can use the wall mount NPB-WPM-US in your 

office (to initially commission the controller), and then install 

the controller at the job using either a NPB-PWR-H or NPB-

PWR-UN-H module. The following sections provide more 

details:

• “NPB-PWR-H” on page 8 (24Vac/dc-powered in-line 

module)

• “NPB-PWR-UN-H” on page 9 (Universal 120V–240Vac-

powered in-line module)

• “NPB-WPM-US (Wall Mount AC Adapter)” on page 10

NPB-PWR-H

Use the NPB-PWR-H module to power the controller (and if 

installed, IO-16-H modules) from a dedicated Class 2, 24Vac 

transformer, or from a 24Vdc power supply. 

NOTE: If there is no optional NiMH backup battery, using 

the NPB-PWR-H allows a higher operating tem-

perature. See “Environmental Requirements” on 

page 3.

IO-34-H

DIN-mountable, combined 34 points I/O with 24V 

isolated power module, used to provide I/O points as 

well as power the controller from a dedicated, 

external, Class-2, 24Vac transformer or a 24Vdc 

power supply.

Only one IO-34-H module per controller.

This module provides these I/O points:

16 - Universal Inputs (UIs).

10 - Digital Outputs (DOs), SPST-relay type.

8 - Analog Outputs (AOs), 0–10Vdc type.

Wiring is covered in the 

IO-34-H Installation and 

Configuration Guide

.

a

A wall mount AC adapter (NPB-WPM-US) is also available; however, it is not an accessory module that mounts on the 20-pin 

connector of the controller.

Table 2. Accessory Modules

a

 Compatible with the WEB-600E Controller. (Continued)

Model

Description

Notes

a

A fourth power option is available: a IO-34-H accessory 

module, which is a combination of the NPB-PWR-H module 

and two IO-16-H modules (plus two extra relays). Refer to its 

mounting and wiring document for more details. For a listing 

of modules, see “About Accessory Modules” on page 7.

Содержание CP-600E

Страница 1: ...kage contents for damaged or missing components If damaged notify the appropriate carrier at once and return any damaged components for immediate repair or replacement See Returning a Defective Unit on page 17 Included in this Package Material and Tools Required Included in this Package Included in this package you should find the following items a WEB 600E or a CP 600E controller This WEB 600E an...

Страница 2: ...powering the controller is 120 240Vac at 50 60 Hz if a NPB PWR UN H 24Vac at 50 60 Hz or 24Vdc if a NPB PWR H or from 100 240Vac at 50 60 Hz NPB WPM US Disconnect power before installation or servicing to prevent electrical shock or equipment damage Make all connections in accordance with national and local electrical codes Use copper conductors only To reduce the risk of fire or electrical shock ...

Страница 3: ...in the same enclosure This is especially important if the controller is mounted inside an enclosure with other heat producing equipment Do not mount the unit in an area with excessive moisture corrosive fumes or explosive vapors where vibration or shock is likely to occur in a location subject to electrical noise This includes the proximity of large electrical contactors electrical machinery weldi...

Страница 4: ...e controller 6 Repeat this for all accessories until all are mounted on the DIN rail and firmly connected to each other 7 To keep the final assembly together secure at both ends with DIN rail end clips provided by the DIN rail ven dor This also prevents the assembly from sliding on the DIN rail See Fig 1 WEB 600E IO 16 H MOUNTING ON DIN RAIL DIN RAIL END CLIP DIN RAIL END CLIP INSTALL DIN RAIL END...

Страница 5: ...About Expansion Options on page 5 below and also About Backup Configurations on page 13 ABOUT EXPANSION OPTIONS The controller provides for field installable expansion using these types of options Option cards Install on connectors on the controller s base board See About Option Cards on page 5 Accessory modules To chain on the controller s 20 pin connector See About Accessory Modules on page 7 Ab...

Страница 6: ...s adapter with a 2 position removable screw terminal connector plug Port operates as LON1 if only one LON option or LON2 in slot 2 if two LON cards NPB RS232 Single port RS 232 adapter with a DB 9M connector Supports baud rates up to 115200 If installed in option slot 1 port operates as COM3 If two 232 option cards ports are COM3 for Option slot 1 and COM4 for Option slot 2 NPB GPRS W NPB GPRS GSM...

Страница 7: ...et end plates and into the standoffs on the controller base board With a screwdriver hand tighten the screws For more details see NiMH Battery Installation and Maintenance on page 14 Otherwise place the two screws through the option card end plate and into the standoffs on the base board With a screwdriver hand tighten the screws 10 Replace the cover on the controller 11 Restore power to the contr...

Страница 8: ...sition power connector if NPB PWR UN H energize the AC circuit 120 240 Vac wired to that module if NPB WPM US plug in the power connector to the controller CAUTION Do not connect both the NPB WPM US and NPB PWR H NPB PWR UN H supplies at the same time or equipment damage may result Power consumption depends mainly on installed I O modules and may vary from Controller alone with or without installe...

Страница 9: ...unts as the last end module in the chain see Fig 1 WARNING A 120Vac or 240Vac circuit powers the NPB PWR UN H Disconnect power to this circuit before installation to prevent electrical shock or equipment damage Make all connections in accordance with national and local electrical codes Use copper conductors only Do not exceed the 30W capacity of NPB PWR UN H by the powered devices Fig 5 NPB PWR UN...

Страница 10: ... Ethernet connections are provided on the controller These RJ 45 connectors are labeled LAN1 PRI and LAN2 SEC Use a standard Ethernet patch cable for connecting to a hub or Ethernet switch The factory default IP address for LAN1 is 192 168 1 12n where the last numeral n in the address matches the last digit in the controller s serial number and the subnet mask is 255 255 255 0 By default LAN2 is d...

Страница 11: ...n the controller s RS 485 bias jumper pins this adds two onboard 3 3K ohm resistors into the controller s RS 485 circuit as follows from RS 485 to 5V from RS 485 to Ground NOTES In general only one device on an RS 485 trunk should be biased Otherwise undue loading of the circuit may result with fewer devices supported RS 485 bias resistors are different than termination resistors externally instal...

Страница 12: ...he NPM6E board aside Note the jumper block on the base board behind the RS 485 port see bottom of Fig 7 Fig 8 Install shorting blocks across both sides of jumper block to add RS 485 bias Installing short blocks to add RS 485 biasing 1 Locate the four jumper pins behind the RS 485 port with 2 pin shorting blocks installed on one pin each See Fig 8 2 To add biasing remove and replace both shorting b...

Страница 13: ...ler to continue operation without rebooting over short power outages or brownouts lasting several seconds or if also using SRAM up to 10 minutes For longer duration outages the battery allows the controller to perform a controlled shutdown safely backing up the station before shutting down Starting in the AX 3 6 nn maintenance build the controller can use both the NiMH backup battery and available...

Страница 14: ...pport Serial Ports LEDs for the two serial ports are located on the controller s bottom board on the opposite side of the RS 232 and RS 485 ports Labels COM1 and COM2 correspond to the software configuration of the COM ports LEDs show the transmit and receive activity for the serial ports and optional modem NOTE You must remove the cover to see these LEDs See Removing and Replacing the Cover on pa...

Страница 15: ...ge cycles the number of discharges and their depth and the ambient temperature of the battery during normal operation In most applications the NiMH battery should see relatively few discharges Therefore ambient temperature has more to do with the life expectancy of the battery than does any other factor If the controller is installed in a conditioned space this battery should provide dependable se...

Страница 16: ...les are installed and any I O points have voltage turn the devices off or dis connect power to them 3 Note positions of all communications and other wiring cables going to the controller as well as installed acces sory modules if they must be removed If necessary label connectors and accessory modules to avoid mis connection later after the controller is replaced 4 Unplug all Ethernet serial LON m...

Страница 17: ...ium Asia Pacific Pte Ltd 17 Changi Business Park Central 1 Honeywell Building Attn Mr Lim Hoon Chat Engineering Mgr Singapore 486073 Attn Return Department RA ____________ Australia Asia Pacific Sales Phone 61 4 1264 4234 Email mhodder tridium com CERTIFICATIONS Federal Communications Commission FCC This equipment generates uses and can radiate radio frequency energy and if not installed and used ...

Страница 18: ...ia Met EN 61326 1 2006 Class B Electo Magnetic Compaibility Emissions Generic Complies as listed below EN 55011 2007 A1 2007 Conducted Emissions Voltage Class B Pass Class B EN 55011 2007 A2 2007 Radiated Emissions Class B Pass Class B EN 61000 3 2 2006 Harmonic Current Emissions Pass EN 61000 3 3 2005 A1 2001 A2 2005 Voltage Fluctuations Flicker Pass EN 61000 4 2 1995 A1 1998 A2 2001 Electostatic...

Страница 19: ...EASUREMENTS BEFORE DRILLING ELECTRONIC AND PRINTED VERSIONS OF THIS DIN MOUNTING IS RECOMMENDED OVER TAB MOUNTING SEE FIG 1 WEB 600E NPB PWR H NPB PWR UN H OR IO 16 H NOTE DISTANCE BETWEEN CENTER OF TABS FROM ONE UNIT TO ANOTHER UNIT TIP IF MOUNTING ACCESSORY MODULES FUTURE REMOVAL REPLACEMENT OF THE CONTROLLER IS SIMPLIFIED IF YOU DO NOT INSTALL SCREWS IN THE ACCESSORY MODULE SIDE TABS OF THE CON...

Страница 20: ...l Inc 62 0433 01 M S 11 12 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modificati...

Отзывы: