WEB-600E AND CP-600E NETWORK CONTROLLERS

5

62-0433—01

Removing and Replacing the Cover

You must remove the controller’s cover to install any option cards, or to install (or replace) the optional NiMH backup battery. The 

cover snaps onto the base with four plastic end tabs—two on each end.

Fig. 2. Press in four tabs on end to remove cover.

NOTE: If accessory modules are plugged into the con-

troller, you may need to slide them away from the 

unit to get to the end cover tabs.

• To remove the cover, press in the tabs on both ends of the 

unit, and carefully lift it off.

• To replace the cover, orient it so the cutout area for comm 

ports is correct, then push inwards to snap in place.

Board Layout

Figure 3 shows the location of LEDs, option slots, and other features of the WEB-600E controller with cover removed. For a side 

view of communications ports and other features, see Fig. 6.

Fig. 3. WEB-600E controller main board layout details.

The controller ships with onboard static RAM (SRAM) that can provide station backup during power loss, and also has two (2) 

open option card slots for a variety of available option cards. For details, see “About Expansion Options” on page 5 below, and 

also “About Backup Configurations” on page 13.

ABOUT EXPANSION OPTIONS

The controller provides for 

field-installable

 expansion using 

these types of options:

Option cards 

— Install on connectors on the controller’s 

base board. See “About Option Cards” on page 5.

Accessory modules 

— To “chain” on the controller’s 20-pin 

connector. See “About Accessory Modules” on page 7.

About Option Cards

The WEB-600E has two (2) available option slots for option 

cards designed for use with WEB controllers. Each slot has a 

30-pin connector. Installing an option card is recommended 

before mounting the unit. See “Installing an Option Card” on 

page 7.

COVER

PRESS

TABS IN

COVER

LIFTED 

AWAY 

M33915

COVER TABS

(2 EACH END)

EARTH GROUND

SPADE LUG 

NORMAL
SERIAL SHELL

OPTION 

SLOT 2

COM 1

COM 2 

SERIAL PORT LEDS ON BOTTOM BOARD, REMOVE COVER TO SEE:

LAN2

(SEC)

LAN1

(PRI)

BEAT

STATUS

STATUS LEDS (VISIBLE WITH COVER ON):

BRACKET FOR

OPTIONAL 

NIMH BACKUP 

BATTERY

OPTION SLOT

CONNECTORS

OPTION SLOT 1

20-PIN

CONNECTOR

(I/O AND

POWER

MODULES)  

MODE JUMPER

(FOR SERIAL 

SHELL ACCESS)  

SECONDARY

ETHERNET

(RJ-45) LAN2 

(TOP BOARD)

RS-232

(DB-9)

COM1

(BOTTOM  

BOARD)

BARREL POWER

CONNECTOR FOR

WALL MOUNTED 

POWER MODULE

(NPB-WPM-US)  

PRIMARY

ETHERNET

(RJ-45) LAN1 

(TOP BOARD)

RS-485

(3-POS.)

COM2

(BOTTOM

BOARD)  

NPM6E PROCESSOR

MODULE WITH

INTEGRAL SRAM  

M33918

Содержание CP-600E

Страница 1: ...kage contents for damaged or missing components If damaged notify the appropriate carrier at once and return any damaged components for immediate repair or replacement See Returning a Defective Unit on page 17 Included in this Package Material and Tools Required Included in this Package Included in this package you should find the following items a WEB 600E or a CP 600E controller This WEB 600E an...

Страница 2: ...powering the controller is 120 240Vac at 50 60 Hz if a NPB PWR UN H 24Vac at 50 60 Hz or 24Vdc if a NPB PWR H or from 100 240Vac at 50 60 Hz NPB WPM US Disconnect power before installation or servicing to prevent electrical shock or equipment damage Make all connections in accordance with national and local electrical codes Use copper conductors only To reduce the risk of fire or electrical shock ...

Страница 3: ...in the same enclosure This is especially important if the controller is mounted inside an enclosure with other heat producing equipment Do not mount the unit in an area with excessive moisture corrosive fumes or explosive vapors where vibration or shock is likely to occur in a location subject to electrical noise This includes the proximity of large electrical contactors electrical machinery weldi...

Страница 4: ...e controller 6 Repeat this for all accessories until all are mounted on the DIN rail and firmly connected to each other 7 To keep the final assembly together secure at both ends with DIN rail end clips provided by the DIN rail ven dor This also prevents the assembly from sliding on the DIN rail See Fig 1 WEB 600E IO 16 H MOUNTING ON DIN RAIL DIN RAIL END CLIP DIN RAIL END CLIP INSTALL DIN RAIL END...

Страница 5: ...About Expansion Options on page 5 below and also About Backup Configurations on page 13 ABOUT EXPANSION OPTIONS The controller provides for field installable expansion using these types of options Option cards Install on connectors on the controller s base board See About Option Cards on page 5 Accessory modules To chain on the controller s 20 pin connector See About Accessory Modules on page 7 Ab...

Страница 6: ...s adapter with a 2 position removable screw terminal connector plug Port operates as LON1 if only one LON option or LON2 in slot 2 if two LON cards NPB RS232 Single port RS 232 adapter with a DB 9M connector Supports baud rates up to 115200 If installed in option slot 1 port operates as COM3 If two 232 option cards ports are COM3 for Option slot 1 and COM4 for Option slot 2 NPB GPRS W NPB GPRS GSM...

Страница 7: ...et end plates and into the standoffs on the controller base board With a screwdriver hand tighten the screws For more details see NiMH Battery Installation and Maintenance on page 14 Otherwise place the two screws through the option card end plate and into the standoffs on the base board With a screwdriver hand tighten the screws 10 Replace the cover on the controller 11 Restore power to the contr...

Страница 8: ...sition power connector if NPB PWR UN H energize the AC circuit 120 240 Vac wired to that module if NPB WPM US plug in the power connector to the controller CAUTION Do not connect both the NPB WPM US and NPB PWR H NPB PWR UN H supplies at the same time or equipment damage may result Power consumption depends mainly on installed I O modules and may vary from Controller alone with or without installe...

Страница 9: ...unts as the last end module in the chain see Fig 1 WARNING A 120Vac or 240Vac circuit powers the NPB PWR UN H Disconnect power to this circuit before installation to prevent electrical shock or equipment damage Make all connections in accordance with national and local electrical codes Use copper conductors only Do not exceed the 30W capacity of NPB PWR UN H by the powered devices Fig 5 NPB PWR UN...

Страница 10: ... Ethernet connections are provided on the controller These RJ 45 connectors are labeled LAN1 PRI and LAN2 SEC Use a standard Ethernet patch cable for connecting to a hub or Ethernet switch The factory default IP address for LAN1 is 192 168 1 12n where the last numeral n in the address matches the last digit in the controller s serial number and the subnet mask is 255 255 255 0 By default LAN2 is d...

Страница 11: ...n the controller s RS 485 bias jumper pins this adds two onboard 3 3K ohm resistors into the controller s RS 485 circuit as follows from RS 485 to 5V from RS 485 to Ground NOTES In general only one device on an RS 485 trunk should be biased Otherwise undue loading of the circuit may result with fewer devices supported RS 485 bias resistors are different than termination resistors externally instal...

Страница 12: ...he NPM6E board aside Note the jumper block on the base board behind the RS 485 port see bottom of Fig 7 Fig 8 Install shorting blocks across both sides of jumper block to add RS 485 bias Installing short blocks to add RS 485 biasing 1 Locate the four jumper pins behind the RS 485 port with 2 pin shorting blocks installed on one pin each See Fig 8 2 To add biasing remove and replace both shorting b...

Страница 13: ...ler to continue operation without rebooting over short power outages or brownouts lasting several seconds or if also using SRAM up to 10 minutes For longer duration outages the battery allows the controller to perform a controlled shutdown safely backing up the station before shutting down Starting in the AX 3 6 nn maintenance build the controller can use both the NiMH backup battery and available...

Страница 14: ...pport Serial Ports LEDs for the two serial ports are located on the controller s bottom board on the opposite side of the RS 232 and RS 485 ports Labels COM1 and COM2 correspond to the software configuration of the COM ports LEDs show the transmit and receive activity for the serial ports and optional modem NOTE You must remove the cover to see these LEDs See Removing and Replacing the Cover on pa...

Страница 15: ...ge cycles the number of discharges and their depth and the ambient temperature of the battery during normal operation In most applications the NiMH battery should see relatively few discharges Therefore ambient temperature has more to do with the life expectancy of the battery than does any other factor If the controller is installed in a conditioned space this battery should provide dependable se...

Страница 16: ...les are installed and any I O points have voltage turn the devices off or dis connect power to them 3 Note positions of all communications and other wiring cables going to the controller as well as installed acces sory modules if they must be removed If necessary label connectors and accessory modules to avoid mis connection later after the controller is replaced 4 Unplug all Ethernet serial LON m...

Страница 17: ...ium Asia Pacific Pte Ltd 17 Changi Business Park Central 1 Honeywell Building Attn Mr Lim Hoon Chat Engineering Mgr Singapore 486073 Attn Return Department RA ____________ Australia Asia Pacific Sales Phone 61 4 1264 4234 Email mhodder tridium com CERTIFICATIONS Federal Communications Commission FCC This equipment generates uses and can radiate radio frequency energy and if not installed and used ...

Страница 18: ...ia Met EN 61326 1 2006 Class B Electo Magnetic Compaibility Emissions Generic Complies as listed below EN 55011 2007 A1 2007 Conducted Emissions Voltage Class B Pass Class B EN 55011 2007 A2 2007 Radiated Emissions Class B Pass Class B EN 61000 3 2 2006 Harmonic Current Emissions Pass EN 61000 3 3 2005 A1 2001 A2 2005 Voltage Fluctuations Flicker Pass EN 61000 4 2 1995 A1 1998 A2 2001 Electostatic...

Страница 19: ...EASUREMENTS BEFORE DRILLING ELECTRONIC AND PRINTED VERSIONS OF THIS DIN MOUNTING IS RECOMMENDED OVER TAB MOUNTING SEE FIG 1 WEB 600E NPB PWR H NPB PWR UN H OR IO 16 H NOTE DISTANCE BETWEEN CENTER OF TABS FROM ONE UNIT TO ANOTHER UNIT TIP IF MOUNTING ACCESSORY MODULES FUTURE REMOVAL REPLACEMENT OF THE CONTROLLER IS SIMPLIFIED IF YOU DO NOT INSTALL SCREWS IN THE ACCESSORY MODULE SIDE TABS OF THE CON...

Страница 20: ...l Inc 62 0433 01 M S 11 12 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any modificati...

Отзывы: