TP970 SERIES CONVERTASTAT

®

 KITS 

Thermostat Cover Mounting 

1.   Remove caution card from cover. 
2.   Select correct window (vertical or horizontal/single, 

dual, or blank). 

3.   Peel release liner from window back (see Fig. 7)

NOTE:   Ensure window orientation is correct. 

When viewed from front of cover, setpoint 
and Day/Auto openings are on either the 
bottom (vertical thermostat) or the right 
(horizontal thermostat). The cover has 
slots which must mate with backplate 
mounting ears (see Fig. 5)

CAUTION 

Equipment Damage Hazard. 
Once assembled, disassembly can damage 
the window. 
Before installing window, remove card, check 
window selection and orientation to cover. The 
setpoint, Day/Auto openings and/or inserts must 
be down or to the right. 

4.   Mount cover. Hook two slots on cover bottom (right 

end for horizontal mounting) to backplate ears. 
Swing cover into place and back out (counterclock­
wise) setscrews with thermostat tool or 0.05-inch 
Allen wrench to secure. 

6 0

7 0 

80

9 0

6 0 

7 0 

8 0 

9 0 

SETSREW HOLES (4) 
(USE HOLES CLOSEST 
TO THE WALL) 

WINDOW 
(DUAL SHOWN, 
PARTIALLY 
INSTALLED) 

C7256 

Fig. 7. Assembly of Cover with 

Window Frame and Insert. 

CHECKOUT AND TESTING 

Equipment Required 

The following equipment is available from your 
Serviceline Supplier: 
— Gage 305965 or 40002576-001, 0 to 30 psi (0-210 kPa). 
— CCT729 Gage Adapter. 
— CCT735A Thermostat Tool. 

NOTE:  

Before making adjustments, set thermostat desired 
setpoint and let system operate long enough to 
stabilize. Ensure that the system is stable before 
checking calibration. All thermostats are accurately 
factory calibrated and should require only a 
calibration check to ensure correct operation. 

Throttling Range 

Thermostat throttling range (TR) is factory set at 4

°

(2.2 K) and should not require any change under normal 
operating conditions. If a change is necessary, use 
following procedures to reset throttling range to values 
specified on job drawings. 

NOTE:   Changing throttling range requires recalibration. 

1.   Remove cover and install 0 to 30 psi (0 to 210 kPa) 

gage (with gage adapter) in gage tap (Fig. 8)

2.   Slide throttling range adjustment to desired

position on throttling range scale. 

3.   Mechanically check TR by moving setpoint adjust­

ment until branch line pressure is 3 psi (21 kPa); 
note setpoint indicator setting. 

4.   Move setpoint adjustment until branch line 

pressure is 13 psi (90 kPa) and note setpoint 
indicator setting. The difference in setpoint 
indicator settings is the actual throttling range. 

NOTE:   The ambient temperature ±1/2 of the 

throttling range must not exceed minimum 
or maximum thermostat setpoints. 

RESULT: With a 6

°

F (3.3 K) throttling range and an 

ambient temperature of 62

°

F (16

°

C), this 

procedure will not work for a TP970A 
which has a 60

°

F (15

°

C) minimum 

setpoint. 

5.   Recalibrate using procedures in Recalibration

section. 

DA 

DA 

60 

70 

80 

90 

SETPOINT DIAL 
(NITE/WINTER) 

THERMOMETER 
CALIBRATION 
BOBBIN 

SETPOINT 
INDICATOR 
(NITE/WINTER) 

SETPOINT INDICATOR 

CALIBRATION SCREW 
(DAY/SUMMER) 

DAY/AUTO LEVER 
(TP971 ONLY) 

SETPOINT  ADJUSTMENT 

SCALEPLATE 

THROTTLING 
RANGE SCALE 
(DAY/SUMMER) 

THROTTLING 
PLATE (2) 

GAUGE TAP 

NOTE: NOT ALL ADJUSTMENTS 
ARE ON ALL THERMOSTATS. 

TEMPERATURE  INDICATOR 

SETPOINT LIMIT STOPS 

CALIBRATION SCREW 
(NITE/WINTER) 

SETPOINT LOCK SCREW 

THROTTLING RANGE 
ADJUSTMENT 
(NITE/WINTER) 

DA 

MIN 

10 

M17442 

Fig. 8. TP971 and TP972 Controls and Indicators, 

Front View with Cover Removed. 

Setpoint Limit Adjustment 

To set minimum or maximum setpoint limits: 

1.   Loosen setpoint lockscrew (Fig. 8)
2.   Move each stop to desired position. 
3.   Tighten setpoint lockscrew. 
4.   Check positioning of stops by changing setpoint. 

85-0210EF—1

 

 

Содержание CONVERTASTAT TP970A2145

Страница 1: ...mponents needed to create a cover to meet building requirements are included INSTALLATION When the old mounting plate is removed retain the screws to use for mounting the adapter plate Cut the existing tubes as close as possible to the thermostat Do not remove the antikink springs from cut tubes Do not allow tubes to slip inside the wall after removing the old thermostat Remove Johnson Thermostat ...

Страница 2: ...3 3011 T27 301 T27 3011 2214 121c 2214 131c 2216 126 2216 136 2216 526d TP971A2183 Same as TP971A2102 except plastic cover is beige T4506 6203c T4506 6204c 2214 521d TP972A2192 Single temp two pipe proportioning 60 to 90 F 16 to 32 C range RA Summer 13 psi 90 kPa or 9 psi 62 kPa unit vent DA Winter 18 psi 124 kPa changeover field adjustable T4756 205 T4756 206 T4756 217 T4756 6205 T4756 6206 T4756...

Страница 3: ...s and separate see Fig 5 e Align and attach backplate and adapter plate to mounting screw holes using screws retained from stripping adapter plate threads f Proceed to Step 7 NOTE When adapting to a Johnson thermostat if wall holes are out of alignment with adapter plate holes use any available hole for an additional wall anchor HOLES 10 CODED PER MANUFACTURER J JOHNSON P POWERS R ROBERTSHAW TUBIN...

Страница 4: ...at 4 F 2 2 K and should not require any change under normal operating conditions If a change is necessary use following procedures to reset throttling range to values specified on job drawings NOTE Changing throttling range requires recalibration 1 Remove cover and install 0 to 30 psi 0 to 210 kPa gage with gage adapter in gage tap Fig 8 2 Slide throttling range adjustment to desired position on t...

Страница 5: ...reads approximately 10F 5 5C degrees above space temperature and set night setpoint dial below space temperature The gage should indicate main air pressure Push day auto lever to day left position it should stay there and BLP should go to 0 psi 0 kPa TP972 Turn setpoint adjustment until setpoint indicator reads approximately 10F 5 5C degrees above space temperature BLP should go to 0 psi 0 kPa 4 S...

Страница 6: ...Pa 4 Turn calibration screw in opposite direction until gage indicates 8 1 psi 56 7 kPa The thermostat is now calibrated 5 Remove gage and replace cover TP971 1 Remove cover and install a 30 psi 210 kPa gage into gage tap 2 Turn setpoint adjustment until setpoint indicator reads indicated temperature 3 With 13 psi 90 kPa day main air pressure turn day left calibration screw Fig 8 until gage indica...

Страница 7: ... notice explique comment retirer le thermostat selon le fabricant et installer le nouveau thermostat de série TP970 Une fois l ancienne plaque de montage retirée conserver les vis qui serviront à l installation de la plaque d adaptation Couper le tuyau existant aussi près que possible du thermostat Ne pas retirer des tuyaux le ressort antitortillement Ne pas laisser les tuyaux glisser à l intérieu...

Страница 8: ...e TP971A2102 mais avec couvercle de plastique beige T4506 6203c T4506 6204c 2214 521d TP972A2192 Une seule temp deux canalisations à action proportionnelle gamme de 60 à 90 F 16 à 32 C action inverse en été à 13 psi 90 kPa ou 9 psi 62 kPa ventilo convecteur action directe en hiver inversion à 18 psi 124 kPa réglable sur place T4756 205 T4756 206 T4756 217 T4756 6205 T4756 6206 T4756 6217 TH192 208...

Страница 9: ... plaque d adaptation et les fixer aux ouvertures des vis de montage à l aide des vis qui ont servi à aléser les filets de la plaque d adaptation f Passer à l étape 7 REMARQUE Lors du remplacement d un thermostat Johnson si les trous dans le mur ne corre spondent pas aux ouvertures de la plaque d adaptation utiliser n importe quel autre trou pour insérer une cheville additionnelle TROU DE GUIDAGE 2...

Страница 10: ...couvercle et installer un manomètre de 0 à 30 psi 0 à 210 kPa dans la prise de manomètre Fig 8 2 Faire glisser le curseur de la bande proportionnelle à la valeur désirée 3 Vérifier mécaniquement la bande proportionnelle en déplaçant le réglage du point de consigne jusqu à ce que la pression de la canalisation princi pale soit de 3 psi 21 kPa Prendre note du point de consigne 4 Déplacer ensuite le ...

Страница 11: ...uto à la position jour à gauche il devrait rester en position et la pression de la canalisation secondaire devrait passer à 0 psi 0 kPa TP972 Faire tourner le réglage du point de consigne jusqu à ce que l indicateur marque environ 10 F 5 5 C au dessus de la température ambiante La pression de la canalisation secondaire devrait passer à 0 psi 0 kPa B M S DU COUVERCLE DU FILTRE FILTRE DES ÉTAGES DU ...

Страница 12: ...opposé jusqu à ce que le manomètre indique 8 psi 1 psi 56 kPa 7 psi Le thermostat est maintenant étalonné 5 Retirer le manomètre et remettre le couvercle TP971 1 Retirer le couvercle et installer un manomètre de 30 psi 210 kPa dans la prise de manomètre 2 Faire tourner le réglage du point de consigne jusqu à ce que l indicateur du point de consigne marque la température indiquée 3 Avec une pressio...

Отзывы: