background image

TP970 SERIES CONVERTASTAT

®

 KITS 

Remove Powers Thermostat 

1.   Loosen screws on each side to remove cover. 
2.   Pull thermostat from the mounting plate. 
3.   Cut tubes near connector and temporarily plug 

main line to conserve air. 

4.   Remove old mounting plate and retain screws. 

MCC POWERS 

10 

20 

30

15 

25 

25

20 

C2314 

Fig. 3. Powers Thermostat. 

Install New Thermostat 

1.   Feed tubes through large adapter plate hole 

(see Fig. 4)

2.   Match adapter plate holes to wall screw holes. 
3.   Mount adapter plate using screws retained from 

old mounting plate removal. Do not over-tighten 
screws. 

NOTE:   If any wall screw holes coincide with 

noncoded adapter plate holes (see 
Fig. 4), proceed as follows. (If not, 
continue with Step 4.): 
a.  With adapter plate away from the wall, 

ream out or strip threaded holes by 
tightening screws retained when 
removing the old mounting plate. 
Tighten with enough force so that the 
screws move freely. 

b.  Remove and retain screws. If wall 

screw holes are larger than #6, 
enlarge adapter plate holes to allow 
enough clearance for screws. 

c.  After removing temporary plug, push 

tubes onto thermostat backplate (main 
tube has air blowing out and must be 
connected to the M barb connection on 
backplate rear). 

d.  To remove thermostat cover, slowly 

drive screws clockwise until cover is 
free. To remove thermostat from 
backplate, spread retaining clips and 
separate (see Fig. 5)

e.  Align and attach backplate and adapter 

plate to mounting screw holes using 
screws retained from stripping adapter 
plate threads. 

f.   Proceed to Step 7. 

NOTE:   When adapting to a Johnson thermostat, 

if wall holes are out of alignment with 
adapter plate holes, use any available 
hole for an additional wall anchor. 

HOLES (10) CODED 
PER MANUFACTURER 
(J = JOHNSON, P = POWERS, 
R = ROBERTSHAW) 

TUBING 

PILOT HOLE (2) 
FOR #6 SELF-TAPPING 
SCREW (PROVIDED) 

M17414 

Fig. 4. Adapter Plate Installation. 

4.   To remove thermostat cover, drive screws 

clockwise until cover is free. To remove thermostat 
from backplate, spread retaining clips (Fig. 4) and 
separate. 

5.   After removing temporary plug, push tubes onto 

thermostat backplate (mainline tube has air 
blowing out and must be connected to the M barb 
connection on rear of backplate). 

6.   Attach backplate to adapter plate with thread­

forming screws provided with thermostat. Do not 
over-tighten screws. 

7.   Press thermostat onto backplate until it is fully 

seated and backplate clips have engaged 
(see Fig. 5)

8.   Remove shipping stops (see Fig. 6)
9.   Mount cover (see Thermostat Cover Mounting 

section). 

SET 
SCREWS 

RETAINING 
CLIPS 

AIR TUBING 
CONNECTIONS 
(3) 

COVER 
MOUNTING 

M17415

EARS 

Fig. 5. Backplate. 

QUICK-MOUNT STAT 
SETSCREWS 

THROTTLING RANGE 
SETTING INDICATOR 

C7257 

TEMPERATURE 
INDICATOR 

CALIBRATION SCREW 

SETPOINT 
LOCK 
SCREW 

STOPS-TEMPERATURE SETTING 

SETPOINT 
INDICATOR 

SHIPPING STOP (2) 
(REMOVE WHEN 
INSTALLING) 

60 

70 

80 

90 

SETPOINT ADJUSTMENT 

Fig. 6. TP970 Series Thermostat 

with Cover Removed. 

3  

85-0210EF—1 

Содержание CONVERTASTAT TP970A2145

Страница 1: ...mponents needed to create a cover to meet building requirements are included INSTALLATION When the old mounting plate is removed retain the screws to use for mounting the adapter plate Cut the existing tubes as close as possible to the thermostat Do not remove the antikink springs from cut tubes Do not allow tubes to slip inside the wall after removing the old thermostat Remove Johnson Thermostat ...

Страница 2: ...3 3011 T27 301 T27 3011 2214 121c 2214 131c 2216 126 2216 136 2216 526d TP971A2183 Same as TP971A2102 except plastic cover is beige T4506 6203c T4506 6204c 2214 521d TP972A2192 Single temp two pipe proportioning 60 to 90 F 16 to 32 C range RA Summer 13 psi 90 kPa or 9 psi 62 kPa unit vent DA Winter 18 psi 124 kPa changeover field adjustable T4756 205 T4756 206 T4756 217 T4756 6205 T4756 6206 T4756...

Страница 3: ...s and separate see Fig 5 e Align and attach backplate and adapter plate to mounting screw holes using screws retained from stripping adapter plate threads f Proceed to Step 7 NOTE When adapting to a Johnson thermostat if wall holes are out of alignment with adapter plate holes use any available hole for an additional wall anchor HOLES 10 CODED PER MANUFACTURER J JOHNSON P POWERS R ROBERTSHAW TUBIN...

Страница 4: ...at 4 F 2 2 K and should not require any change under normal operating conditions If a change is necessary use following procedures to reset throttling range to values specified on job drawings NOTE Changing throttling range requires recalibration 1 Remove cover and install 0 to 30 psi 0 to 210 kPa gage with gage adapter in gage tap Fig 8 2 Slide throttling range adjustment to desired position on t...

Страница 5: ...reads approximately 10F 5 5C degrees above space temperature and set night setpoint dial below space temperature The gage should indicate main air pressure Push day auto lever to day left position it should stay there and BLP should go to 0 psi 0 kPa TP972 Turn setpoint adjustment until setpoint indicator reads approximately 10F 5 5C degrees above space temperature BLP should go to 0 psi 0 kPa 4 S...

Страница 6: ...Pa 4 Turn calibration screw in opposite direction until gage indicates 8 1 psi 56 7 kPa The thermostat is now calibrated 5 Remove gage and replace cover TP971 1 Remove cover and install a 30 psi 210 kPa gage into gage tap 2 Turn setpoint adjustment until setpoint indicator reads indicated temperature 3 With 13 psi 90 kPa day main air pressure turn day left calibration screw Fig 8 until gage indica...

Страница 7: ... notice explique comment retirer le thermostat selon le fabricant et installer le nouveau thermostat de série TP970 Une fois l ancienne plaque de montage retirée conserver les vis qui serviront à l installation de la plaque d adaptation Couper le tuyau existant aussi près que possible du thermostat Ne pas retirer des tuyaux le ressort antitortillement Ne pas laisser les tuyaux glisser à l intérieu...

Страница 8: ...e TP971A2102 mais avec couvercle de plastique beige T4506 6203c T4506 6204c 2214 521d TP972A2192 Une seule temp deux canalisations à action proportionnelle gamme de 60 à 90 F 16 à 32 C action inverse en été à 13 psi 90 kPa ou 9 psi 62 kPa ventilo convecteur action directe en hiver inversion à 18 psi 124 kPa réglable sur place T4756 205 T4756 206 T4756 217 T4756 6205 T4756 6206 T4756 6217 TH192 208...

Страница 9: ... plaque d adaptation et les fixer aux ouvertures des vis de montage à l aide des vis qui ont servi à aléser les filets de la plaque d adaptation f Passer à l étape 7 REMARQUE Lors du remplacement d un thermostat Johnson si les trous dans le mur ne corre spondent pas aux ouvertures de la plaque d adaptation utiliser n importe quel autre trou pour insérer une cheville additionnelle TROU DE GUIDAGE 2...

Страница 10: ...couvercle et installer un manomètre de 0 à 30 psi 0 à 210 kPa dans la prise de manomètre Fig 8 2 Faire glisser le curseur de la bande proportionnelle à la valeur désirée 3 Vérifier mécaniquement la bande proportionnelle en déplaçant le réglage du point de consigne jusqu à ce que la pression de la canalisation princi pale soit de 3 psi 21 kPa Prendre note du point de consigne 4 Déplacer ensuite le ...

Страница 11: ...uto à la position jour à gauche il devrait rester en position et la pression de la canalisation secondaire devrait passer à 0 psi 0 kPa TP972 Faire tourner le réglage du point de consigne jusqu à ce que l indicateur marque environ 10 F 5 5 C au dessus de la température ambiante La pression de la canalisation secondaire devrait passer à 0 psi 0 kPa B M S DU COUVERCLE DU FILTRE FILTRE DES ÉTAGES DU ...

Страница 12: ...opposé jusqu à ce que le manomètre indique 8 psi 1 psi 56 kPa 7 psi Le thermostat est maintenant étalonné 5 Retirer le manomètre et remettre le couvercle TP971 1 Retirer le couvercle et installer un manomètre de 30 psi 210 kPa dans la prise de manomètre 2 Faire tourner le réglage du point de consigne jusqu à ce que l indicateur du point de consigne marque la température indiquée 3 Avec une pressio...