SELF DIAGNOSTICS

The system contains complete self diagnostics, which is

executed automatically every time the power is turned on.

This function checks returns an error byte to system RAM. If

the error message equals 8, it will not be cleared until a new

self diagnostic procedure is activated after a power up. The

other codes are reset when the causes have vanished.
For AQS51/61-KAM the tests comprise checking internal

voltage regulators and output values. In addition, constantly

during operation, the sensor probes are checked against

failure by checking the valid dynamic measurement ranges.

Error Code and Actions

Error Code

Suggested Action

4

Indicate problems with the power

supply.

Check power supply voltage.

8

Indicates problem with OUT1.

Could be too high an output load

connected to the output. Check OUT1

with a voltmeter and compare the

output with the LCD reading (for

AQS61-KAM).

Disconnect the output wiring

 to

check if the external load is too high

and causes the error indication. To start

the internal output diagnostic, switch

the power off and restart the unit.

32

Sensor out of range.

Occurs during over exposure of CO

2

sensor, in which case the error code

will automatically reset when the

measurement values return to normal.

Could also indicate the need of zero

point calibration. If the CO

2

 reading is

correct  and the error code remains, the

temperature sensor must be broken.

NOTE:

If several errors are detected at the same time,

the different error code numbers will be added

together into one single error code.

Содержание AQS51-KAM

Страница 1: ...s analog output configuration the software program STRATEGY is available which is part of the User Interface Program Software package AQS USP22 used for re calibration change of the measurement range or other service or set up purposes The switching setpoint and differential of the relay output for CO2 limit monitoring or plant system ON OFF control can be adjusted within the measurement range Thi...

Страница 2: ...D indication Yellow Maintenance required Red Relay activated Power up time 1 min Ambient operating limits Temperature 0 50 C General Humidity 0 95 rh non condensing Operating principle Non dispersive infrared NDIR Gas sampling mode Diffusion and 3 mm gas inlet push on barb Response time 2 min diffusion or 10 sec 0 2 ltr min gas flow Measurement range 0 3000 ppm Converting range 0 2000 ppm 0 10 Vdc...

Страница 3: ...using the PC software STRATEGY Version 3 Digital relay output Single pole double throw SPDT switching potential free contact Factory adjusted switching setpoint and differential 1A 50 Vac 50VA or 1 A 24 Vdc 30 W Relay activated 1000 ppm Relay deactivated 900 ppm Sensor housing 84 x 142 x 46 mm Dimensions Sampling probe 203 mm Zigzag traces accessible after removing the cover Shortage with a screwd...

Страница 4: ...ions to provide different ventilation control strategies All sensor measurements can be addressed to these functions and mixed together by this software to form two independent and intelligent P I controllers The relay output contact CM NO is closed if the CO2 level exceeds the factory adjusted limit of 1000ppm and the contact CM NC is closed if the CO2 level is equal or below 900ppm These paramet...

Страница 5: ...Pos 7 cable entry bushings To make a hole insert a screwdriver into the groove and hit firmly Mount for each cable a cable entry bushing into the aspiration box and seal properly 7 Mounting the aspiration box to the sampling probe is performed by a snap in bayonet fitting Pos 10 Insert first the temperature sensor placed on the end of a 150mm long soldered on lead Fig 3 Pos 2 into the air inlet to...

Страница 6: ...G0 permitting a 3 wire configuration A single transformer may be used for the entire system Situations can occur where different transformers must be used NOTE2 AQS51 61 can supply both a voltage or a current output for OUT1 OUT2 To change between voltage and current output mode the hardware jumpers have to be set in accordance There is one jumper for AN1 and one for AN2 so that one output can be ...

Страница 7: ...2 Error code 3 CO2 concentration in ppm 4 Temperature in C 5 OUT1 value full scale 6 OUT2 value full scale To access the maintenance level short at level 5 OUT1 value ENTER MENU ENTER in sequence The maintenance mode is restricted to competent trained service personnel only For detailed information see the Service Checkout Instruction EN2B 0461GE02 LED Signals The standard sensor has two different...

Страница 8: ...sor probes are checked against failure by checking the valid dynamic measurement ranges Error Code and Actions Error Code Suggested Action 4 Indicate problems with the power supply Check power supply voltage 8 Indicates problem with OUT1 Could be too high an output load connected to the output Check OUT1 with a voltmeter and compare the output with the LCD reading for AQS61 KAM Disconnect the outp...

Отзывы: