AQS51/61-KAM  COMBINED CO

2

-/TEMPERATURE DUCT SENSOR/CONTROLLER

EN0B-1023 GE02R0700

2

MODELS

Type

Order Number

CO

2

 and Temperature Duct

Sensor without LCD display

AQS51-KAM

CO

2

 and Temperature Duct

Sensor with 4-digit LCD display

AQS61-KAM

ACCESSORIES

Description

Order Number

Service Software; 3.5” Diskette

(for changing the sensing range, the

parametrization and the post calibration)

AQS-USP22

Testset

(consists of a portable gas generator for

zero-position calibration, pump, packing,

3m tube, battery and transformer)

AQS-F0005

RS Cable with built-in electronics and

adapters

AQS3/4 or

AQS31/41

TECHNICAL DATA

Power supply

24Vac 

±

 20%; 50/60Hz or 24Vdc 

±

 20%

Power consumption

2W

Sensor life expectancy

>

15 years

Maintenance interval

5 years

Self diagnostics

Complete power/sensor/analog outputs internal test

Status LED indication

Yellow = Maintenance required; Red = Relay activated

Power-up time

1 min

Ambient operating limits
- Temperature

0...50

°

C

General

- Humidity

0...95%rh (non condensing)

Operating principle

Non-dispersive infrared (NDIR)

Gas sampling mode

Diffusion and 

3 mm gas inlet push-on barb

Response time

2 min (diffusion) or 10 sec (0.2 ltr/min gas flow)

Measurement range

0...3000 ppm

Converting range

0...2000 ppm = 0...10 Vdc (factory setting)

or 2...10 Vdc / 0...20 mA / 4...20 mA

Accuracy

±

1% of measurement range, 

±

5% of reading

Pressure dependence

+

1.58% of reading per kPa deviation from normal pressure

100 kPa

CO

2

 - Measurement

Annual zero drift

<

 

±

1% of measurement range

Operating principle

Thermistor

Measurement range

10...60

°

C

Converting range

0...50 

°

C = 0...10 Vdc (factory setting) or 2...10 Vdc / 0...20

mA / 4...20 mA

Temperature

Measurement

Accuracy

±

0.2 K

Settings and configuration with

Service Software AQS-USP22
- Throttling range CO

2

100...800 ppm

- Throttling range temperature

1...10 K

P

++++

I control

- Reset time adjustment ranges

2...500 sec (factory setting: 300 sec)

Содержание AQS51-KAM

Страница 1: ...s analog output configuration the software program STRATEGY is available which is part of the User Interface Program Software package AQS USP22 used for re calibration change of the measurement range or other service or set up purposes The switching setpoint and differential of the relay output for CO2 limit monitoring or plant system ON OFF control can be adjusted within the measurement range Thi...

Страница 2: ...D indication Yellow Maintenance required Red Relay activated Power up time 1 min Ambient operating limits Temperature 0 50 C General Humidity 0 95 rh non condensing Operating principle Non dispersive infrared NDIR Gas sampling mode Diffusion and 3 mm gas inlet push on barb Response time 2 min diffusion or 10 sec 0 2 ltr min gas flow Measurement range 0 3000 ppm Converting range 0 2000 ppm 0 10 Vdc...

Страница 3: ...using the PC software STRATEGY Version 3 Digital relay output Single pole double throw SPDT switching potential free contact Factory adjusted switching setpoint and differential 1A 50 Vac 50VA or 1 A 24 Vdc 30 W Relay activated 1000 ppm Relay deactivated 900 ppm Sensor housing 84 x 142 x 46 mm Dimensions Sampling probe 203 mm Zigzag traces accessible after removing the cover Shortage with a screwd...

Страница 4: ...ions to provide different ventilation control strategies All sensor measurements can be addressed to these functions and mixed together by this software to form two independent and intelligent P I controllers The relay output contact CM NO is closed if the CO2 level exceeds the factory adjusted limit of 1000ppm and the contact CM NC is closed if the CO2 level is equal or below 900ppm These paramet...

Страница 5: ...Pos 7 cable entry bushings To make a hole insert a screwdriver into the groove and hit firmly Mount for each cable a cable entry bushing into the aspiration box and seal properly 7 Mounting the aspiration box to the sampling probe is performed by a snap in bayonet fitting Pos 10 Insert first the temperature sensor placed on the end of a 150mm long soldered on lead Fig 3 Pos 2 into the air inlet to...

Страница 6: ...G0 permitting a 3 wire configuration A single transformer may be used for the entire system Situations can occur where different transformers must be used NOTE2 AQS51 61 can supply both a voltage or a current output for OUT1 OUT2 To change between voltage and current output mode the hardware jumpers have to be set in accordance There is one jumper for AN1 and one for AN2 so that one output can be ...

Страница 7: ...2 Error code 3 CO2 concentration in ppm 4 Temperature in C 5 OUT1 value full scale 6 OUT2 value full scale To access the maintenance level short at level 5 OUT1 value ENTER MENU ENTER in sequence The maintenance mode is restricted to competent trained service personnel only For detailed information see the Service Checkout Instruction EN2B 0461GE02 LED Signals The standard sensor has two different...

Страница 8: ...sor probes are checked against failure by checking the valid dynamic measurement ranges Error Code and Actions Error Code Suggested Action 4 Indicate problems with the power supply Check power supply voltage 8 Indicates problem with OUT1 Could be too high an output load connected to the output Check OUT1 with a voltmeter and compare the output with the LCD reading for AQS61 KAM Disconnect the outp...