AQS51/61-KAM  COMBINED CO

2

-/TEMPERATURE  DUCT SENSOR/CONTROLLER

EN0B-1023 GE02R0500

4

OPERATION

General

Each of these devices can be used as transmitter for

measurement of CO

2

 concentration and temperature or as a

very flexible controller for proportional and integral control of

mixed air dampers or variable speed controlled fans in stand

alone applications.
The relay output can be used for CO

2

 limit monitoring or

plant/system ON/OFF control.
If used as a transmitter, it converts the actual measured

values of the CO

2

 concentration and temperature into

standard output signals 0(2) to 10 Vdc or 0(4)...20 mA

depending on the adjusted measurement ranges.
Directly connected to the analog inputs of Honeywell DDC

systems it allows the required flexibility for a wide range of

applications and the use of different demand controlled

ventilation strategies to match exactly the requirements of the

control system.
If used as a controller the actual measured values are

compared with the programmed setpoints. Depending on the

deviation the control output values are calculated and

converted into two separate 0(2)...10Vdc or 0(4)...20mA

outputs which can drive directly final control devices. The

proportional  band settings control the output spans.
In this application the AQS-USP22 software package can be

used to configure the available two analog outputs for

temperature and ventilation control, and to assign for each

output a number of functions to provide different ventilation

control strategies.

All sensor measurements can be addressed to these

functions and mixed together by this software to form two

independent and intelligent P+I controllers.

The relay output contact CM-NO is closed, if the CO

2

 level

exceeds the factory adjusted limit of 1000ppm and the

contact CM-NC is closed, if the CO

2

 level is equal or below

900ppm. These parameters are programmable within the

specified measurement range.

APPLICATION ADVICE

For rooms where are the occupants the source of the main

air pollution, a CO

2

 concentration of max. 1200ppm should

not be exceeded.

MOUNTING

The AQS51-KAM and AQS61-KAM sensor/controllers are

supplied with the sensor printed circuit board already

mounted into the aspiration box.

Mount the unit in the return or outside air duct in a position

far away from external heat sources and where it is easy

accessible for service and maintenance purposes.
Since there might be a substantial pressure difference

between the duct and ambient air, it is indispensable that the

sealings of the cable entry bushings, the cable feed through,

the box cover and the duct entrance are absolutely tight to

avoid ambient air from suction into the aspiration box. The

duct entrance may need additional sealing paste in order to

prevent leakage.

Fig. 2  Parts list and mounting of the aspiration box to the sampling probe

1

8

4

3

2

9

6

7

10

5

Open

Closed

1 Sampling probe

6 O-ring

2 Sealing gasket

7 PG9 cable entry bushing

3 Duct flow direction label

8 PG7 cable entry bushing

4 2 washers BRB 5.3x10x1

9 PCB (factory supplied mounted in the box)

5 2 screws RXS 4.8x16

 10 Snap-in lid

Содержание AQS51-KAM

Страница 1: ...s analog output configuration the software program STRATEGY is available which is part of the User Interface Program Software package AQS USP22 used for re calibration change of the measurement range or other service or set up purposes The switching setpoint and differential of the relay output for CO2 limit monitoring or plant system ON OFF control can be adjusted within the measurement range Thi...

Страница 2: ...D indication Yellow Maintenance required Red Relay activated Power up time 1 min Ambient operating limits Temperature 0 50 C General Humidity 0 95 rh non condensing Operating principle Non dispersive infrared NDIR Gas sampling mode Diffusion and 3 mm gas inlet push on barb Response time 2 min diffusion or 10 sec 0 2 ltr min gas flow Measurement range 0 3000 ppm Converting range 0 2000 ppm 0 10 Vdc...

Страница 3: ...using the PC software STRATEGY Version 3 Digital relay output Single pole double throw SPDT switching potential free contact Factory adjusted switching setpoint and differential 1A 50 Vac 50VA or 1 A 24 Vdc 30 W Relay activated 1000 ppm Relay deactivated 900 ppm Sensor housing 84 x 142 x 46 mm Dimensions Sampling probe 203 mm Zigzag traces accessible after removing the cover Shortage with a screwd...

Страница 4: ...ions to provide different ventilation control strategies All sensor measurements can be addressed to these functions and mixed together by this software to form two independent and intelligent P I controllers The relay output contact CM NO is closed if the CO2 level exceeds the factory adjusted limit of 1000ppm and the contact CM NC is closed if the CO2 level is equal or below 900ppm These paramet...

Страница 5: ...Pos 7 cable entry bushings To make a hole insert a screwdriver into the groove and hit firmly Mount for each cable a cable entry bushing into the aspiration box and seal properly 7 Mounting the aspiration box to the sampling probe is performed by a snap in bayonet fitting Pos 10 Insert first the temperature sensor placed on the end of a 150mm long soldered on lead Fig 3 Pos 2 into the air inlet to...

Страница 6: ...G0 permitting a 3 wire configuration A single transformer may be used for the entire system Situations can occur where different transformers must be used NOTE2 AQS51 61 can supply both a voltage or a current output for OUT1 OUT2 To change between voltage and current output mode the hardware jumpers have to be set in accordance There is one jumper for AN1 and one for AN2 so that one output can be ...

Страница 7: ...2 Error code 3 CO2 concentration in ppm 4 Temperature in C 5 OUT1 value full scale 6 OUT2 value full scale To access the maintenance level short at level 5 OUT1 value ENTER MENU ENTER in sequence The maintenance mode is restricted to competent trained service personnel only For detailed information see the Service Checkout Instruction EN2B 0461GE02 LED Signals The standard sensor has two different...

Страница 8: ...sor probes are checked against failure by checking the valid dynamic measurement ranges Error Code and Actions Error Code Suggested Action 4 Indicate problems with the power supply Check power supply voltage 8 Indicates problem with OUT1 Could be too high an output load connected to the output Check OUT1 with a voltmeter and compare the output with the LCD reading for AQS61 KAM Disconnect the outp...